2.2 Pager Interface Communications Settings
The serial interface can be configured to the settings of the pager system. Refer to the pager system
documentation for further details on the settings required.
The table below shows the options available.
Item
Default
Options
Baud Rate
4800
600, 1200, 2400,
4800, 9600, 19200,
38400 and 57600
Data Bits
8
7, 8
Stop Bits
1
1, 2
Parity
None
None, Odd, Even
CTS
Disabled
Disabled, Enabled,
Switched
2.3 Pager Events
In the pager events option, it is possible to determine
to which pagers each type of event should be sent
and to configure some basic event parameters.
The active window shows and event tree with all of
the possible event types.
To configure an event type, click on the + symbol to
expand the tree.
The Basic options are described in the table below.
Right click on the item to edit its setting.
Item
Default
Options
Flag
Fire = Alarm
Alarm, Plant
Alarm, Pre-
Alarm and
Fault = High
Disable and
Enable =
Normal
Alarm
High
Normal
Beep
Code
1
0
– 9 Refer to the
pager documentation
to see if it supports
this option.
Text
Fire
Alarm
Plant Alarm
Pre-Alarm
Fault
Disable
Enable
Up to 16 characters
– this text is used in
the “Event Text”
string
– see the
section on Text Cuts.
There can be up to 8 shifts per day for
both weekdays and for weekend days.
Shifts that are not configured are crossed
out.