www.advancedco.com
59
Section 7.11
Delays to Outputs.
It must be possible to override the operation of any delays at Level 1. Refer to Section
for information on overriding delays.
For compliance, the maximum total delay permitted is 10 minutes.
3.3.21.1
Overriding Delays at Level 1
A facility to override any programmed delays and immediately activate the sounder circuits should be provided
at Level 1. It is possible to override the delay using the panel controls (see the user manual for details). This can
also be achieved from an input device (such as a manual call point) that is programmed to turn on all outputs
immediately.
3.3.22 Test
This function is the same as User Level 2 function
– refer to User Manual for further information.
The following functions can be tested:
Zones / Inputs
Display
Buzzer
Printer
Outputs
3.3.23 LED Indications
This option is not provided from Software Version 050-04.
The operation of all MXP-513-XXX LED Indicator Cards MUST be configured using the PC Tool.
Panels equipped with integral panel LED indicators on the display card will default to indicate fire alarms in
Zones 1-20. The operation of these can be adjusted using the PC Tool.
P
P
C
C
O
O
N
N
L
L
Y
Y
Each LED can be individually configured via the PC Tool to either zone assignment, output
group assignment or other function.