2.2  Basic Configuration 

 

Each card connected to the 485 Communication Line must have 
its  own  address.  This  address  should  be  set  so  that  it  matches 
the  corresponding  card  within  the  Advanced  PC  Config  Tool 
design.  

 

Move the “Earth Monitor” DIP switch to the ON position to enable 
local earth monitoring. Leave it in the OFF position if the card is 
local to the Fire panel  or is grouped  with another card (which is 
responsible for earth monitoring). 

Only 1 card should ever be set to monitor the earth state. 

 

Move the PBUS EOL DIP switch to the On position if the card is 
the  last  device  in  the  communication  line.  No  external  resistors 
are required. 

 

 

 

2.2.1  PSU Mon / Input 10   

 

By default, input 10 is set to operate as a PSU monitor. Detectable conditions are: 
 

Line State 

Input Interpretation 

Associated PSU Monitor State 

EOL Present 

Normal Operation  

PSU Monitor Ok 

EOL Missing 

Open Circuit Fault 

PSU Monitor Fault 

Short 

Active / PSU Fault 

PSU Monitor Fault 

 
 

When  set  to  behave  as  a  “PSU  Monitor”  the  input  becomes  task  specific. 
Monitored/Unmonitored settings assigned by the configuration tool are ignored. 
The  input  is  always  interpreted  by  the  Fire  Panel  as  a  PSU  Fault  regardless  of  any 
other action (if any) that is assigned to it in the PC Configuration Tool design.

 

  

Setting the “Input 10 EN” DIP switch to the “On” position allows the input operation mode to be set by the  PC 
Configuration Tool. This allows the input to operate in Monitored or Unmonitored mode, and it will no longer be 
interpreted by the Fire Panel as a PSU fault signal; freeing up the input to be used for other tasks. 
 

2.2.2  Disabling PSU Mon / Input 10   

 

Should an installation not require the use of input 10 at all, it can be easily disabled without the need for extra 
wiring/resistors. To bypass the input: 

-

 

On the card, Set DIP 

switch “Input 10 EN” to the “On” position  

-

 

In the PC Configuration Tool d

esign, Set Input to “No Action” 

 

 

 

 

Summary of Contents for Mxp-537

Page 1: ...pheral Input Card The operation and functions described in this manual are available from Software Version Mx5000 050 04 onwards Individually Configurable Inputs Monitored Unmonitored Operation Mode S M A R T Power Management ...

Page 2: ...cess to the following functionality EN54 13 Fault state reporting Item Specification Details Applicable Standards BS EN54 18 BS EN54 13 Operating Temperature 5 C to 40 C Relative Humidity 95 Non Condensing maximum PCB 20mm H x 105mm W x 125mm L 105 grams D C Supply 24V 17V to 28V DC Quiescent Current 25mA 10 I Ps wired with 6K8 EOLs Vs 24V Max Current 30mA 10 I Ps wired with 6K8 EOLs Vs 20V Input ...

Page 3: ... 2 1 MODULE OVERVIEW 4 2 2 BASIC CONFIGURATION 5 2 2 1 PSU Mon Input 10 5 2 2 2 Disabling PSU Mon Input 10 5 2 3 WIRING CONFIGURATION 6 2 3 1 Supply Wiring 6 2 3 2 Comms Wiring 7 2 3 3 Input Wiring 7 3 CARD CONFIGURATION SETUP 8 ADDING A CARD TO THE DESIGN 8 CONFIGURING INPUTS 8 4 GENERAL NOTES 9 ...

Page 4: ...nitor circuit in the event that the card is mounted remotely to its parent Fire Panel With up to 16 supported cards this allows an extra 160 monitored inputs to be operated from a single Fire Panel The Mxp 537 Peripheral Input card makes use of Software Monitoring And Real Time Power Management techniques This allows the card to minimise energy requirements without compromising input monitoring ca...

Page 5: ...l Operation PSU Monitor Ok EOL Missing Open Circuit Fault PSU Monitor Fault Short Active PSU Fault PSU Monitor Fault When set to behave as a PSU Monitor the input becomes task specific Monitored Unmonitored settings assigned by the configuration tool are ignored The input is always interpreted by the Fire Panel as a PSU Fault regardless of any other action if any that is assigned to it in the PC C...

Page 6: ...heral Input Card 24V GND PSU MON 485 A B A B I P 1 I P 2 I P 3 I P 4 I P 5 I P 6 I P 7 I P 8 I P 9 I P 10 Mxp 537 Peripheral Input Card GND NO COM Supply wiring with Remote PSU monitoring PSU 24V Fault Relay Com NC NO Supervising Relay To Peripheral Loop Input Module 24V GND PSU MON 485 A B A B I P 1 I P 2 I P 3 I P 4 I P 5 I P 6 I P 7 I P 8 I P 9 I P 10 Mxp 537 Peripheral Input Card 24V GND PSU M...

Page 7: ...al Input Card Set PBUS EOL to ON on last card 2 3 3 Input Wiring PSU Fault Relay Un Monitored Monitored EOL 470R EOL PSU Monitor SW 1 OUT SW 2 OUT SW 1 IN SW 2 IN Mxp 053 Latch Stretch I P Module The Mxp 053 is an optional module that provides Latch Stretch functionality for fast inputs 200ms It also provides Input Isolation The MXP 053 Should be located local to the MXP 537 The MXP 537 Input shou...

Page 8: ...ust be added to the same DIP Switch address as the one set on the card Configuring Inputs Input configuration is performed along the same line as configuring any other input device Setting the Input Action to No Action has the following impact Input is disabled at the hardware end overall power consumption is reduced End of Line resistors are not required for unused inputs By default all inputs ar...

Page 9: ...ply should be configured for earth monitoring This equipment is constructed with static sensitive components Observe anti static precautions at all times when handling printed circuit boards Wear an anti static earth strap connected to panel enclosure earth point The unit must be grounded this is normally achieved via the screw terminals used to secure the card to the enclosure Should this not be ...

Page 10: ...www advancedco com 10 This page is intentionally left blank ...

Page 11: ...www advancedco com USER NOTES ...

Page 12: ...anced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 189 Revision 01A First Issued 2013 mm dd ...

Reviews: