39
Press the
buttons to scroll through the list of zones.
Press the
buttons to select the fields for a particular zone.
Press the
✔
button to select a particular field option to change its setting.
3.3.10.1 Default Output Settings
On initial installation, or after clearing the configuration memory, all outputs are assigned to specific Output
Groups and will turn on immediately a single fire alarm occurs in any zone (any fault condition for the fault
relay). The default assignments are as follows:
Output Device
Output Group
Cause and Effect
On-board Sounder A
1
Any fire in any zone
– no delay
On-board Sounder B
2
Any fire in any zone
– no delay
On-board Sounder C
11
3
Any fire in any zone
– no delay
4
Any fire in any zone
– no delay
On-board Relay 1
12
200
Any fault in any zone
– no delay
199
Any fire in any zone
– no delay
On-board Open Collectors
199
Any fire in any zone
– no delay
Fault Routing Output
13
200
Any fault in any zone
– no delay
Fire Routing Output-A
199
Any fire in any zone
– no delay
Fire Routing Output-B
199
Any fire in any zone
– no delay
All Loop Output Devices
199
Any fire in any zone
– no delay
3.3.10.2 Cause
Each Output Group can be programmed to respond in a unique way to events from each individual zone. An
input event may be a fire alarm condition or it may be a fault, disablement or other condition. A combination of
criteria may also be applied to each zone.
The Cause field determines what type of input event (or a combination of input events) will generate an output
response for the selected input zone.
To inspect or change the Cause, press the
button to highlight the cause option. For example:
[Output Group 1] [ 3.9% Mem used]
ZONE CAUSE STYLE=Delay->MODE Wait
1
ANY FIRE
00 - On
2 ANY FIRE+ 00 - On
3 ANY FIRE 00 - On
4 ANY FIRE 00 - On
Press the
✔
button to change the setting and a pop-up window will appear showing the options available. For
example:
[FIRE ] [D/K FIRE] [ALARM][PRE-ALARM]
✔
- - -
[FAULT] [I/P DISABLE][TEST ][ CONTROL ]
- - - -
11
Mx-4400V & Mx-4800V Only
12
This Output is used for routing if the non-monitored routing option is selected.
13
This Output is available on the optional Routing Interface Peripheral Card.
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for MX-4200V
Page 68: ...68 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 69: ...69 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 70: ...70 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 71: ...71 USER NOTES www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...