3.3.3.2 Procedure if the Panel finds Devices Missing
When the panel cannot communicate with a device previously programmed into the panel, the Auto Learn
process is suspended and the display shows a pop-up window with options. For example:
KEEP THIS DEVICE
.
DELETE THIS DEVICE
KEEP ALL MISSING
DELETE ALL MISSING
! Address 002 DEVICE MISSING
If the missing device is kept (or all missing devices are kept), the panel remembers the programming for these
devices. The panel will report a fault condition until such time as the missing devices are reconnected.
If the missing device is deleted (or all missing devices are deleted), the panel clears all previous programming
for these devices. This includes any sensitivity threshold changes, text assignments, zone assignment, action,
etc.
Press the
buttons to highlight the required menu option and then press the
✔
button to confirm. The pop-up
window will disappear and the panel will continue with the auto learn process.
If a single device is deleted and another missing device is subsequently registered, the display will once again
show the pop-up window to keep or delete this device.
3.3.3.3 Procedure if the Panel finds Devices Added
When the panel finds a device not previously learnt and programmed in the panel, the Auto Learn process is
suspended and the display shows a pop-up window with options. For example:
ACCEPT NEW DEVICE
.
REJECT NEW DEVICE
ACCEPT ALL NEW DEVICES
REJECT ALL NEW DEVICES
! Address 002 NEW DEVICE
If the new device is accepted (or all new devices are accepted), the panel will configure the memory to register
these devices. All data will be configured to initial settings for sensitivity threshold changes, text assignments,
zone assignment, action, etc. for these devices.
If the new device is rejected (or all new devices are rejected), the panel clears all programming for these
devices and will not attempt to communicate with the devices at these addresses.
Press the
buttons to highlight the required menu option and then press the
✔
button to confirm. The pop-up
window will disappear and the panel will continue with the auto learn process.
If a single device is accepted / rejected and another new device is subsequently registered, the display will once
again show the pop-up window to accept or reject this device.
3.3.3.4 Procedure if the Panel finds Devices Changed
When the panel finds a new type of device installed at an address previously learnt and programmed in the
panel, the Auto Learn process is suspended and the display shows a pop-up window with options. For example:
ACCEPT NEW DEVICE
.
KEEP OLD DEVICE
ACCEPT ALL NEW DEVICES
REJECT ALL NEW DEVICES
! Address 002 TYPE CHANGE
This situation could arise for example if a heat detector has been installed in place of an optical smoke detector.
If the new device type is accepted (or all new device types are accepted), the panel will configure the memory to
register these devices. All data will be configured to initial settings for sensitivity threshold changes, text
assignments, zone assignment, action, etc. for these devices.
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for MX-4200V
Page 68: ...68 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 69: ...69 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 70: ...70 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 71: ...71 USER NOTES www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...