7 Specifications
AV-VBM and AV-VB Specifications
AV-VBM and AV-VB
Temperature 32–120
0
F (0-48
0
C)
Humidity
10-95% (non condensing)
Enclosure Dimensions
16”W x 19
1
/
8
”H x 5”D
Weight 19lb
5oz
AX-PSU-6
Operating Voltage
120 -240 VAC
Output Voltage/Current
24 VDC nominal @ 6 Amp
Charger Current
1.5 Amp maximum (subtracted from 6 Amp supply)
45 Ah maximum batteries
PCB Status LEDs
Seven (7): Earth Fault, Heart Beat, Battery Connect, Battery Low, Battery O-C, Charger
Fault and PSU Fault.
Driver Output LEDs
Two (2): AC Power and Power Supply Trouble
Form “C” Relay Contact
Fail-safe power supply charger trouble contact
AV-AMP-80
Operating Voltage
24 VDC nominal
Operating Current
Quiescent
Alarm
0.04 Amp typical
5.2 Amp (includes full speaker load)
Amplifiers
Wiring
Speaker Circuit EOL
Two (2) independent 40 Watt amplifiers (speaker circuits)
Class A or B
4.7K End of Line Resistor
Trigger Inputs
Three (3)
Trigger Input 1 = message/tone #1
Trigger Input 2 = message/tone #2
Trigger Input 3 = activate distributed audio booster mode
Amplifier Inputs
(Audio Boost Input)
Two (2)
Amplifier 1 Audio Input
Amplifier 2 Audio Input
Form “C” Relay Contact
Fail-safe amplifier trouble contact
USB Port
For Windows® compatible program for message/tone programming
RS485 Input
Not Used
DIP Switch
Not Used
Mic Input
6 pin microphone input header w/mic supervision (AV-VBM only)
Supervision jumper installed on AV-VB
PCB Status LEDs
Six (6): Transmit, Heart Beat, AMP 1 Fault, AMP 2 Fault, 40V Status and USB in use
AV-ZS (Optional)
Operating Voltage
24 VDC nominal
Operating Current
Quiescent
Alarm
0.100 Amp
0.075 Amp (all zone circuits active)
Zone Circuits
Wiring
Speaker Circuit EOL
Four (4) independent speaker circuits
Class A or B (jumper selection per circuit [J5, J9, J10 & J11])
100K End of Line Resistor
Audio Inputs
Audio In Jumpers
J1, J6 & J7
Two (2) 25 or 70 VRMS Inputs
1 x 4 one audio input to four audio outputs
2 x 2 two audio inputs to two audio outputs
PCB Status LEDs
Eight (8)
One O/C (Open Circuit) & S/C (Short or Ground Circuit)
Trouble Contact
Fail-Safe trouble contact (COMM / N/O [closed when normal])
Input Zone Selection
Individual and all circuit activation inputs via switch common
14-Pin Cable Port
Optional AV-ZS-CM panel mount splitter switch module