Page 4
High Efficiency - High Intensity
KMI_02142017al
LAYOUT RECOMMENDATIONS
MODEL
NO.
RATE
btu/hr
HEATER
MOUNTING HEIGHT
ft
(m)
DISTANCE OF
FIRST HEATER
ROW FROM
OUTSIDE WALL
ft
(m)
DISTANCE
BETWEEN
HEATERS ALONG
OUTSIDE WALL*
ft
(m)
DISTANCE
BETWEEN ROWS
- OUT-SIDE WALL
ROW TO NEXT
INTERIOR ROW
ft
(m)
0-10°
ANGLE
30°
ANGLE
KMI-20
20,000
10 - 15
(3 - 4.6)
9 - 13
(2.7 - 4)
6 (1.9)
8 - 20
(2.5 - 6.1)
30 - 60
(9.2 - 18.3)
KMI-40
40,000
12 - 19
(3.7 - 5.9)
11 - 17
(3.4 - 5.2)
10 (3.1)
15 - 30
(4.6 - 9.2)
50 - 80
(15.2 - 24.4)
KMI-60
60,000
14 - 22
(4.3 - 6.7)
13 - 19
(4 - 5.9)
12 (3.7)
20 - 40
(6.1 - 12.2)
75 - 110
(22.9 - 33.5)
KMI-90
90,000
15 - 24
(4.6 - 7.3)
14 - 22
(4.3 - 6.7)
14 (4.3)
30 - 50
(9.2 - 15.2)
90 - 115
(27.5 - 35.0)
KMI-120
120,000
17 - 29
(5.2 - 8.8)
16 - 25
(4.9 - 7.6)
16 (4.9)
40 - 60
(12.2 - 18.3)
100 - 125
(30.5 - 38.1)
* Distance between heaters along interior rows should be up to twice the indicated number
AMBIENT AIR
TEMPERATURE
btu/hr per sq ft OF FLOOR AREA TO BE HEATED
AT 50 ft/min OF WIND
15.2 m/min
AT 100 ft/min OF WIND
30.5 m/min
40°F / 4°C
150 - 165
165 - 180
55°F / 13°C
75 - 88
85 - 100
Suggested Heat Load
Example:
A work counter for light assembly is 15 ft x 25 ft. (4.5 m x 7.6 m)
Ambient air temperature 40°F / 4°C, located near shipping doors.
Approximately 170 BTU/hr/sq. ft x (15x25) sq. ft = 63,750 BTU/hr
Two heaters at opposing locations would be preferred
Full Building Heat
Calculate the total heat input required, ensuring the inclusion of any unheated make-up air due to exhaust fans.
Use the following chart as guidance to heater placement.