Operation & Maintenance Manual

Table of Contents:

1.0 

Introduction

1

2.0 

Unpacking your COOL-

SPACE

®

1

3.0 

Set-up of COOL-

SPACE

®

unit

1

3.1 

Connecting the water supply

1

3.2 

Connecting the electrical supply

2

4.0 

Operating procedures

3

4.1 

Filling the unit with water

3

4.2 

Starting the fan

3

4.3 

Starting the pump and adjusting the water flow

4

5.0 

Maintenance and storage

4

5.1 

Removing the cooling media & accessing the inside of the unit

4

5.2 

Daily maintenance

4

5.3 

Periodic maintenance

5

5.4 

Storage

5

6.0 

Troubleshooting/Repair

6

6.1 

Troubleshooting

6 - 9

6.2 

Repair procedures

10

6.3 

Technical support

10

7.0 

Warranty

11

7.1 

Warranty form

11

7.2 

Warranty parts

11

7.3 

Optional accessories and replacement parts

11

Due to continuous product innovations, we reserve the right to change product 

specification without due notice.

New evaporative cooling media 

contains a harmless odor; similar to 

new carpet or paint. The media 

should be flushed with water to 

remove the construction odor. A 

REFRESH™ tablet will help control 

odor and bacteria in the reservoir 

and the cooling media.

Instructions:

Fill the reservoir with water

1.
2.

3.

4.

5.

Place the REFRESH™ tablet in the 

reservoir
Turn on the pump,  leaving the fan 

off, and cycle water for 8 hours or 

overnight
Drain used water and refill the 

water reservoir
Repeat when necessary to remove 

odors

Part# CS-T106

To learn more about COOL-

SPACE 

coolers and accessories visit us 
online at

.com

Summary of Contents for CS5-16-VD-TB

Page 1: ...Operation and Maintenance Manual GLACIER CS5 18 VD TB2 CS5 16 VD TB 120V 60HZ TALL BASE ...

Page 2: ......

Page 3: ... procedures 10 6 3 Technical support 10 7 0 Warranty 11 7 1 Warranty form 11 7 2 Warranty parts 11 7 3 Optional accessories and replacement parts 11 Due to continuous product innovations we reserve the right to change product specification without due notice New evaporative cooling media contains a harmless odor similar to new carpet or paint The media should be flushed with water to remove the co...

Page 4: ...lly examine the carton for damage before opening If the carton is damaged notify the shipping company immediately 3 0 Set up of the COOL SPACE unit The COOL SPACE unit is factory tested and ready to use The unit should be placed on a level surface and the casters locked to prevent inadvertent movement Follow instructions below to connect water and electrical supply 3 1 Connecting the water supply ...

Page 5: ...er to Table 2 for the proper 3 conductor heavy duty cord required Do not exceed the amperage ratings of the extension cord Undersized extension cords result in excessive drops in voltage which cause the electric motors to generate excessive heat This condition results in inefficient motor operation and premature motor failure WHICH WILL VOID THE WARRANTY Table 1 Electrical requirements CS Model Nu...

Page 6: ... unit must be placed on a level surface to operate correctly Units create an oval shaped air pattern Obstacles such as racks and workbenches may interfere with the air flow An attempt should be made to locate the unit in such a manner that interruption of the air pattern is held to a minimum Multiple units may be required to cover larger areas When the COOL SPACE unit is placed near a wall or othe...

Page 7: ...d to be adjusted on initial start up It is located at the side of the unit it controls the volume of water that is delivered to the top of the cooling pads Prolonged use of hard water without proper water treatment will create mineral deposit build up causing the pump to fail which is NOT COVERED BY WARRANTY Pump is equipped with a LOW WATER CUT OFF which may take up to 5 minutes to reset each tim...

Page 8: ...incoming air stream These particles will flow into the sump and collect there Also impurities in the water will collect in the sump Draining the Water Sump 1 Close the water flow valve and open the drain valve 2 Run pump until sump is dry then immediately shut off pump 3 Turn unit off and disconnect the power supply 4 Remove cooling pads refer to section 5 1 5 Clean out reservoir with either a tow...

Page 9: ... system has a problem you must define the associated problem e g the pump is not running Although this might seem a bit simplified several things may cause this particular problem So while defining the problem a careful check of all systems should be made to fully understand the extent of the problem If you have a complete understanding of all of the systems of the COOL SPACE unit and how they dep...

Page 10: ...ce motor Breaker trips or fuse blows when fan is started Motor stall Check power source for min 120volt 15 amp Extension cord Replace motor Upgrade power supply Replace with heavier cord Motor overheating and shutting off Restarting several minutes later Extension cord gauge too small Inlet air obstructed or too close to wall Faulty motor Replace with heavier cord Provide minimum 3 feet inlet clea...

Page 11: ...to allow float valve to shutoff 120psi max Float valve is not seating properly Tighten connections and or replace hose washers Reduce water pressure by adding an inline reducer Check all hoses for leaks Water spitting from the unit Flow control Cracked Hose Valve Assembly Hose connection loose Reduce flow Replace Hose Valve Assembly Tighten hose Water leaking from drain valve For worn washer worn ...

Page 12: ...e running Object s in impellor impellor loose Pump bearings bad Remove object s Replace pump Breaker trips or fuse blows when switch is turned on Check power cord length and breaker rating Check for locked up pump Refer to page 2 for unit amperage draw and to determine required cord gauge Replace pump Pump won t run and power is available Pump is functional Make certain switch is working Is water ...

Page 13: ...e motor fan and support braces complete fan assembly 4 Replace new fan assembly 5 Secure with 4 nuts and bolts 6 Replace any wire ties that were removed when taking out the old fan assembly 7 Replace the black motor wiring plate 8 Reinstall pads and connect power GLACIER CS5 16 VD TB Pump Replacement 1 Loosen PVC Union 2 Remove pump and PVC pipe 3 Unplug the cord from the top of the pump by removi...

Page 14: ...d your COOL SPACE unit If you have any questions or concerns please contact us direct at 1 800 557 5716 or at sales cool space com Please have your model number and serial number ready DO NOT DISCARD FAULTY PARTS Check with the Manufacturer as they may need to be returned for warranty credit 7 3 Optional Accessories and Replacement Parts Accessories and replacement parts are available from your lo...

Page 15: ......

Page 16: ...CS MAN 18 TB V60H 06272017al 315 N Madison Street Fortville IN 46040 1 800 557 5716 sales cool space com www COOL SPACE com ...