Utility Interconnect Specifications
Table 10‑4. Utility interconnect voltage and frequency trip limits and times
Voltage and Frequency Trip Limits and Times
The default trip limits and times meet UL1741 anti-islanding requirements.
Voltage trip limit field adjustment range as a percentage of nominal: 88% to 110%.
(The accuracy limit of time measurement is: 50 ms.)
VAC Configurations
Condition
Factory Setting
(VAC)
Field
Adjustable
Range (VAC)
Factory Setting
Trip Time
(seconds)
Field Adjustable
Trip Time
Range (seconds)
Voltage phase high
529.0
422.0 to 529.0
1.0
0.000 to 999.999
Voltage phase low
422.0
422.0 to 529.0
2.0
0.000 to 999.999
Voltage phase fast
high
529.0
422.0 to 529.0
0.16
0.000 to 999.999
Voltage phase fast
low
240.0
422.0 to 529.0
0.16
0.000 to 999.999
Frequency Trip Limits and Times
Condition
Factory Setting
(Hz)
Field
Adjustable
Range (Hz)
Factory Setting
Standard Trip
Time (seconds)
Field Adjustable
Trip Time
Range (seconds)
Line frequency low
59.3
57.0 to 63.0
0.2
0.000 to 999.999
Line frequency
high
60.5
57.0 to 63.0
0.2
0.000 to 999.999
Advanced Energy
A‑4
Specifications
570-1003552-05A
Summary of Contents for AE 3TL 1000 Series
Page 2: ......
Page 12: ...Advanced Energy xii 570 1003552 05A List of Tables...
Page 14: ...Advanced Energy xiv 570 1003552 05A List of Figures...
Page 26: ...Advanced Energy 1 12 Safety and Product Compliance Guidelines 570 1003552 05A...
Page 64: ...Advanced Energy 4 28 Installing 570 1003552 05A...
Page 86: ...Advanced Energy 6 4 Operating the Arc Fault Detection Unit 570 1003552 05A...
Page 92: ...Advanced Energy 7 6 Data Monitoring and Controls 570 1003552 05A...
Page 110: ...Advanced Energy 9 14 Troubleshooting and Solar Energy Technical Support 570 1003552 05A...
Page 116: ...Advanced Energy A 6 Specifications 570 1003552 05A...
Page 120: ...Advanced Energy B 4 System and Mechanical Diagrams 570 1003552 05A...