Summary of Contents for MXPro4 Mxp-007

Page 1: ...roup to provide full support for the MxPro 4 system s DynamiX zoning facilities In addition each output has a number of programmable operational parameters including fail safe can silence allow walk test and delayed operation These features not only aid commissioning and cut down on expensive ancillary hardware but also allow the system to be easily configured to provide full support for the more ...

Page 2: ... Way or 8 Way Relay Output Cards can be fitted to an Mx 4800 control panel Compatibility The Mxp 007 is fully compatible with the Mx 4100 Mx 4200 Mx 4400 and Mx 4800 Fire Alarm Control Panels The Mxp 008 is fully compatible with the Mx 4200 Mx 4400 Mx 4800 Fire Alarm Control Panels Mounting pillars are provided to mount these cards as follows Mx 4200 Mx 4400 Mx 4800 on the panel chassis Mx 4100 L ...

Page 3: ...E MX 4200 MX 4400 MX 4800 4 1 2 1 Mounting the Card 4 1 2 2 Internal Wiring 4 1 3 INSTALLING THE MXP 008 IN THE MX 4200 MX 4400 MX 4800 5 1 3 1 Mounting the Card 5 1 3 2 Internal Wiring 5 1 4 EXTERNAL WIRING 5 2 PROGRAM THE RELAY OUTPUTS 6 2 1 MAY SILENCE 7 2 2 INVERTED OUTPUT 7 2 3 MAY WALK TEST 7 2 4 INVESTIGATION 7 www acornfiresecurity com www acornfiresecurity com ...

Page 4: ...d header on the base card 1 2 Installing the Mxp 007 in the Mx 4200 Mx 4400 Mx 4800 1 2 1 Mounting the Card Base Card M3 Fixing Screws Mxp 007 The card mounts on 4 pillars in the top left hand corner of the control panel chassis adjacent to the Mx4200 Mx 4400 base card See diagram opposite Use the four M3 screws supplied to securely affix the card to the chassis It is not possible to install the M...

Page 5: ...Mx 4400 then use the deeper back box Mxm 020 or use the Termination Enclosures Mxm 028 or Mxm 029 as appropriate RELAY 1 RELAY 2 RELAY 3 RELAY 4 RELAY 5 RELAY 6 RELAY 7 RELAY 8 COM NC NO COM NC NO COM NO COM NO COM NO COM NO COM NO COM NO All electrical wiring installation work should be carried out in accordance with the code of practice applicable in the country of installation To maintain elect...

Page 6: ...ll in the same Output Group 199 but this can be changed as required In the example below the relays have been assigned to groups 180 to 187 These output groups can be programmed as required For a more detailed explanation of assigning output groups refer to PC Net manual see document reference 680 021 The properties that can be assigned to each relay output are depicted in the boxes on the Point D...

Page 7: ...uiescent state and de energised when its Output Group setting is activated 2 3 May Walk Test If this parameter is ticked the relays assigned with this parameter will be allowed to energise when a Walk Test with ring bells option is enabled The relay will energise for a short time along with the bells sounders when a walk test alarm is generated 2 4 Investigation If this parameter is ticked the rel...

Page 8: ...8 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...

Page 9: ...USER NOTES www acornfiresecurity com www acornfiresecurity com ...

Page 10: ...www acornfiresecurity com www acornfiresecurity com ...