Introduction

Advanced Air (UK) Ltd have been manufacturing a comprehensive range of fire dampers and fire smoke 

dampers since 1975. We have always taken pride in our products and tested to the highest standards, 

originally to BS476 and now more stringent testing to CE labelling under the Construction Product Regulation 

which was introduced 1st July 2013.
All our fire, fire smoke and smoke control dampers have been tested to BS EN 1366-2 and BS EN 1366-10. 

This is to cover a variety of installations used on sites today. Under CE labelling all dampers must follow the 

Product Standards BS EN 15650 and BS EN 12101-8 which ensures the product is consistent and supplied to 

the same specification and standard as tested. Any deviation or changes from the installations in this manual 

would require the dampers to be subject to a new test or approval sought from Local Building Control.
In line with product standards we are pleased to offer this installation manual covering installation, operation 

and maintenance instructions together with Health and Safety information. We have also included within this 

manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to 

be completed by the installer. A separate certificate is required per damper.
The installation contained in this manual cover most installation on site. However, there are still installation 

which Advanced Air (UK) Ltd have not yet tested. We are continually reviewing requirements and continuously 

developing the products. As additional installation tests are carried out and classified, installations will be 

added to this manual, and the Declaration of Performance (DoP) updated accordingly.

Health and Safety

Any instruction contained within this manual must be undertaken by competent trained personnel. When 

completing the installation standard PPE should be used, steel toe cap boots, hard hat, gloves, protective 

eyewear along with any other specific site or material instructions.
The size and weight of dampers vary, and it may require two or more persons to safely handle and move 

them. Do not lift the dampers by the blades or the actuator.
For the installation of dampers at high level, the correct lifting equipment shall be used in accordance with 

the Work at Height Regulations 2005 and specific site rules.
All waste materials should be collected and disposed of defined by the suppliers.

Summary of Contents for AIR CONTROL 0400FME

Page 1: ...0400_IOM_1 1_Mar21_1 1 AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL MODEL 0400 FIRE DAMPER...

Page 2: ...er Model 0400MAN Two hour flexible wall 4 Two hour rigid wall 5 Circular fire damper Model 0400FME Two hour flexible wall 6 Two hour rigid wall 7 Operation and Maintenance Model 0400MAN 8 Model 0400FM...

Page 3: ...luded within this manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Page 4: ...it and pushed into place All cut edges must be sealed with a fire batt sealant to BS EN 13501 2 A fire rated intumescent mastic to BS EN 13501 2 shall be applied to each joint 7 The galvanised mild st...

Page 5: ...l be applied to each joint 6 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm leaving a 10mm clearance for any duct expansion in a fire situation 7 The galvan...

Page 6: ...cent mastic to BS EN 13501 2 shall be applied to each joint 7 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm leaving a 10mm clearance for any duct expansion...

Page 7: ...30mm leaving a 10mm clearance for any duct expansion in a fire situation 7 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild steel ductwork sealer and fix...

Page 8: ...blade may have been incorrectly positioned or the damper may be faulty Please contact Advanced Air for advice Maintenance 0400MAN dampers are installed as a life safety product and it is essential tha...

Page 9: ...ion For other faults contact Advanced Air Sales Office Complete any relevant reports Maintenance 0400FME dampers are installed as a life safety product and it is essential that they are always maintai...

Page 10: ...5 6 7 8 G PRODUCTS DMP 0400 Series 02 Drawings D0400 ES Electrical Schematics D0400 ES001 Wiring diagram fire smoke damper actuator D0400 ES001 rev B Wiring diagram 0400 FME dwg Wiring detail for dam...

Page 11: ...o damper also through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the in...

Reviews: