Site Planning
74
Installation and Commissioning Manual
F
S
P
3000R
7 R
11
.1 8000
0015930
Issue
B
, ©
2012
ADVA AG Optical Netw
orking
ADVA Conf
idential
Ethernet Straight-Through Cables and Crossover
Cables
Cat 5e and Cat 6 cables terminated with RJ-45 connectors should be used.
Cable length is reduced for an unshielded cable to 3m (9.8 ft) at the most.
Cables in lengths ranging from 3 m (9.8 ft) to 100 m (328 ft.) must be shielded,
otherwise EMC compliance cannot be guaranteed
.
The cables must be compli-
ant with the IEEE 802.3:1998 Ethernet standard. See
details.
EIA/TIA-568 standard is the basis for Cat 5/Cat 6 cable wiring scheme. Whether
you are using striped twisted pair or solid color twisted pair, follow the appropri-
ate wiring diagrams according to 568B as shown in
.
Table 10: Ethernet Cable Types Used by the FSP 3000R7
Cable Category Level
Cable
Type
Frequency
Bandwidth
Uses
Cat 5e* (TIA/EIA-568-B.2)
4-pair
STP
up to 100 MHz
100BASE-TX, 10Base-T
Cat 6*
(ANSI/TIA/EIA-568-B.2-1)
4-pair
STP/FTP
up to 250 MHz
1000Base-T, 100BASE-TX,
10Base-T
* Maximum segment distance = 100 meters (328 ft.)