connected to the connecting pipe under the combustion chamber. The amount of air needed for combustion
is 25m3/h.
The connecting pipe has an external diameter of 78 mm, to which you need a pipe with a diameter of 80 mm.
If the pipe work is further than 1 m, the pipe diameter must be increased to 100 mm and a correspondingly
larger wall valve must be chosen. In warm rooms the channel should be insulated with 30 mm mineral wool
covered with a damp-proof course (plastic). It is important that the lead-in between the pipe and the wall (or
floor) is sealed with jointing compound. You can eventually use the complete Aduro fresh air kit.
The pipe with external supply of combustion air can be taken out at the bottom of the back side of the stove
or under the stove (see illustration below):
2.5 Ways of installation
Indirect through
external wall
Through
floor and
foundation
Through
wall
Trough floor
and crawl
space