ADTRAN 6-Amp Power Installation And Maintenance Practice Download Page 9

Description

61180043L2-5D

3

Battery Disconnect Protection Circuit

During battery operation a protection circuit disconnects battery from the main output when 
battery voltage drops below 39 VDC, preventing over discharge. When AC returns, the main 
output provides regulated –54 VDC, batteries recharge, and the system returns to normal. 
Refer to 

“LED Indication”

.

After the protection circuit initiates, the LEDs remain on (red), continuing to slowly drain the 
battery. When battery voltage drops to 35 VDC, all load is removed from the battery. If AC 
power will not be available for an extended period (several days), disconnect the battery to 
prevent unnecessary discharge.

DC Over Voltage Protection

The PS/BC has a protection circuit that disables the rectifier to protect the load from a high 
output voltage caused by rectifier failure. The backup battery or redundant PS/BC supports 
the load in this instance. The over voltage event can permanently disable the PS/BC. Confirm 
this by performing the following procedure:

1. Disconnect the PS/BC from the AC source.
2. Wait 30 minutes minimum.
3. After 30 minutes plug back into the AC source.
4. If the unit has recovered, the 

AC FAIL/UNIT FAIL/OVERLOAD

 LED will turn on green and the 

unit returns to service. If the LED does not turn on green, replace the PS/BC.

Alarm Relays

There are two uncommitted alarm relays associated with PS/BC operation:

• AC Fail (ACF): Alarms if AC fails, the rectifier overloads, or the rectifier fails
• Battery Low Voltage (BV): Alarms if either or both battery voltage drops below 42 VDC

Fuse

A standard 5

×

20 mm 5-amp fuse adjacent to the AC power cord protects AC power feed 

overload in case of rectifier failure.

Summary of Contents for 6-Amp Power

Page 1: ...Total Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice Document Number 61180043L2 5D CLEI VAPUKT0C_ _ June 2005...

Page 2: ...lder of the Manual The contents of this publication are current as of the date of publication ADTRAN reserves the right to change the contents without prior notice In no event will ADTRAN be liable fo...

Page 3: ...font indicates references to other documentation and is also used for emphasis This font indicates on screen messages and prompts This font indicates text to be typed exactly as shown This font indic...

Page 4: ...ude overviews on product features and functions while covering applications of ADTRAN s product lines ADTRAN provides a variety of training options including customized training and courses taught at...

Page 5: ...4 Installation 5 Shipping Contents 5 Mounting the PS BC 6 Alternate Mounting 7 Provisioning 7 Wiring Descriptions 7 Ground 7 120 VAC Power Input 7 DC Power Output 8 PS BC to Battery Configurations 8 B...

Page 6: ...ation and Maintenance Practice vi 61180043L2 5D Figures Figure 1 Total Access PS BC 1 Figure 2 PS BC Mounted On Battery Pack 6 Figure 3 Wiring Block Diagrams 8 Tables Table 1 LED Descriptions 4 Table...

Page 7: ...illustrates the PS BC P N 1180043L2 right and left side panels Figure 1 Total Access PS BC Features The Total Access PS BC features include the following 54 VDC at 6 amps output for multiple use Modu...

Page 8: ...any appli cation using 120 VAC input and requiring up to 54 VDC 6 amps output In the Total Access 1500 configuration the rectifier performs AC to DC conversion and when used with the dual battery pro...

Page 9: ...les the rectifier to protect the load from a high output voltage caused by rectifier failure The backup battery or redundant PS BC supports the load in this instance The over voltage event can permane...

Page 10: ...vice must accept any interference received including interference that may cause undesired operation Changes or modifications not expressly approved by ADTRAN could void the user s authority to operat...

Page 11: ...ents Place modules in antistatic packing mate rial when transporting or storing When working on modules always place them on an approved antistatic mat that is electrically grounded Shipping Contents...

Page 12: ...f the PS BC 10 foot power cord 2 Determine the most convenient direction to view the status LEDs and position the PS BC accordingly 3 Align the mounting tabs to the threaded mounting holes on the batt...

Page 13: ...sioning Aside from various PS BC and battery mounting and wiring configurations there are no end user controls adjustments or options associated with the PS BC WIRING DESCRIPTIONS The wiring required...

Page 14: ...Block Diagrams These would include one or two PS BCs none one or two batteries or some combination of PS BC and battery The most reliable configuration would be two PS BCs with two batteries each and...

Page 15: ...mination of the output is customer designated The alarm outputs AC Fail Battery Low Voltage are assigned the following wire color codes ACF orange orange white BV blue blue white OPERATION The PS BC s...

Page 16: ...watts Table 3 PS BC Specifications Specification Description Environmental Operating Temperature Derated Operation Linear Storage Temperature Relative Humidity Max Heat Dissipation 40 C to 50 C 50 C...

Page 17: ...s support Customer and Product Service CAPS requests or further information ADTRAN Sales Pricing Availability 800 827 0807 ADTRAN Technical Support Pre Sales Applications Post Sales Technical Assistan...

Page 18: ...Carrier Networks Division 901 Explorer Blvd Huntsville AL 35806...

Reviews: