ST-LC OPERATION MANUAL(EN)    2011-04-27

 

3 / 35 

■ 

Reading stable functions

 

 

■ 

Relay Functions 

„

 

Average Display update 

[  

avg

]

 

Settable range: 1~99 times;   

      Jittery Display caused by the noise or unstable 
signal. User can set the times to average the readings, 
and to get smoothly display. 
Remark: To set the average times with higher will make 

the response time slower of Relay and 
Analogue output. 

The meter’s sampling is 15cycle/sec 

 

If the 

[  

avg

]

(Average) set to be 

    3

 to express the 

display update with 5 times/sec. 

The meter will calculate the sampling 1-3 and update 
the display value. At meantime, the sampling 4-6 will be 
processed to calculate. 

Average set to be 3 

                                           

 

 

 
 
 
 
 
 
 
 

…….

Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 

…….

Display Update Value =   
(Sample 1 + Sample 2 + Sample 3)/3 

Display Update Value =   
(Sample 4 + Sample 5 + Sample 6)/3

„

 

Moving Average update 

[

mVavg

]

 

Settable range: 0(no function)/1~10 times; 

      Jittery Display caused by the reasons as like as 
noise or unstable signal. User can set the times to 
average the readings, and get smoothly display. 
Remark: To set the moving average times with higher 

wouldn’t affect the response time of Relay and 
Analogue output except the 1

st

 updated display value 

will be slower. 

The meter’s sampling is 15cycle/sec. If the 

[

mVavg

]

(Moving Average) set to be 

    3

 expressed 

the display update with 15 times/sec.,   

In the first updated display value will be same as 

average function. In the next updated display value, the 
function will get the new fourth sample (sample 4) then 
throw away the first sample (sample 1) that the newest 
3 samples(sample 2,3,4) will be calculated for the 
updated display value.   

Moving Average set to be 3 

                                           

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 

……. 

In first 3 samples, Display Update Value 

= (Sample 1 + Sample 2 + Sample 3)/3 

Display Update Value   

= (Sample 2 + Sample 3 + Sample 4)/3

Display Update Value   

= (Sample 3 + Sample 4 + Sample 5)/3

Display Update Value   

= (Sample 4 + Sample 5 + Sample 6)/3

……. 

„

 

Digital filter 

[

Dfilt

]

 

Settable range from 0(None)/1~99 times.  

The digital filter can reduce the influence of spark 

noise by magnetic of coil. 

If the values of samples are over digital filter 

band(fixed in firmware and about 5% of stable reading) 
3 times (Digital Filter set to be 3) continuously, the meter 
will admit the samples and update the new reading. 
Otherwise, it will be as treat as a noise and skip the 
samples. 

 

ST-LC series offer the 2 relay outputs with more 

flexible and multi-functions. They can be programmable 
individually in 

[

relay group

]

Please refer to the 

description as following; 

„

 

Relay energized mode

 [ 

ry_.md

]

 Hi / Lo / Hi(Lo) latch / 

DO 

 

Hi (

   hi

) (Fig.1-

c

):

 Relay will be energized, 

when PV > Set Point 

 

Lo (

   lo

) (Fig.1-

d

):

 Relay will be energized, 

when PV < Set Point 

Hi / Lo Relay Energized 

Fig.1

                                           

 

 

 

 
 

 

 
 

 

 
 

 

 
 

 

 

Hi S etting

Hi  Re la y E nergized

ON 

Lo S etting

Hi  Re la y E nergized

ON 

 

hi
lo

[

ry_.sp

]

[

ry_.sp

]

[

ry_.md

]

d

c

 

 

 

Hi alarm & latch / Lo alarm & latch (

hIhld

 / 

lOhld

)

The relay energized with latched function is for 

electrical safety and human protection. 

For example, a current meter relay installed for the 

over current alarm of motor. Generally, over current of 
motor caused by over load, mechanical dead lock, aging 
of insulation and so on. Above cases will alarm in the 
meter, if the user doesn't figure out the real reason and 
re-start the motor. It may damage the motor. The 
functions of Hi.HLD & Lo.HLD are designed must be 
manual reset the alarm after checking out and solving 
the issue. It's very important idea for electrical safety 
and human protection. 

As the PV Higher (or lower) than set-point, the relay 

will be energized to latch except manual reset by from 
key in 

[

 user level

]

 

rYrst

 is closed. 

R elay Energized Latch & Reset 

                                           

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

H i. H Ld (H i  L at ch )

R e la y  En erg iz ed  

O N 

R eset Relay  Latch 

b y ECI or Fron t  Key

ON  

Le vel T rig ge r 

H i Settin g

hIhld

[

ry_.md

]

rYrst

[

eci._

]

[

ry_.sp

]

 

 

do(Digit Output) (

   do

):  

The function has been designed not only a meter but 

also an I/O interface. In the case of motor control 
cabinet

 

can't get the remote function. It's very easily to 

get the ON/OFF status of switch from ST-LC series with 
RS485 function. 
If the 

[

ry_.md

]

 had been set 

     

do

, the relay will be 

energized by RS485 command directly, but no longer to 
compare with set-point.

 

„

 

Start delay band 

rYsb

]

and Start delay time 

rYsd

]

The functions have Been designed for, 
1. To avoid starting current of inductive motor (6 times of 

rated current) with alarm. 

2. If  the 

ry_.md

 relay energized mode had been set to 

be 

     

lo

(Lo) or 

lOhld

(Lo & latch). As the meter is 

 

Summary of Contents for ST-LC

Page 1: ......

Page 2: ...ample input 1 is 4 20mA and input 2 is Pt100 Optional This two inputs may also establish the related parameter individually establish mathematics function between two inputs Input Range aIlo aOhi The...

Page 3: ...longer appear the input signal on the meter then the PV screen will display the data from RS485 command The data number will be same function as PV which it will compare with set point analogue output...

Page 4: ...ilter band fixed in firmware and about 5 of stable reading 3 times Digital Filter set to be 3 continuously the meter will admit the samples and update the new reading Otherwise it will be as treat as...

Page 5: ...alues Reverse slope output is decided by reversing point positions Output range selection aOtyp Voltage output specified Programming V0 10 0 10V V0 5 0 5V V1 5 1 5V Currnet output specified Programmin...

Page 6: ...T MULTI FUNCTION CONVERTER M H D H COM RL E ENT MULTI FUNCTION CONVERTER M H D H COM RL Field Calibration In pass time the engineers have to take a lot of time to adjust and calibrate meters or conver...

Page 7: ...deep Wiring Diagram Connector 10A 300Vac M3 0 1 3 3 5mm2 22 12AWG Max torque 13Kg cm 7 0mm max 7 0mm max Please set the torque of automotive screwdriver to match the limited of terminals OUTPUT 1 OUT...

Page 8: ...ls programmable None none no lock at all User can access to all level for checking and setting User Level user User Level lock User can access to User Level for checking but can not setting Programmin...

Page 9: ...nction index to access setting status 3 Setting Confirmed save to EEProm and go to next function index Shift key 1 In measuring page press for 1 second to access user level 2 In function index press f...

Page 10: ...t for energized latch of Relay yes no 0 8 Mrst no Mrst Maximum Minimum storage reset yes no 16 88 MEASURING PAGE 1 1 0 3 ry sp 10 00 ry sp Relay 1 Set point setting Settable Range 19999 29999 0 6 miN1...

Page 11: ...ized mode off lo hi lOhld hIhld do D 3 aOhs 10 00 aOhs Analogue High Output relative High Scale Settable Range 19999 29999 E 3 prity NstB2 prity Parity Nstb 1 Nstb 2 odd even A1 4 lOsC1 00 lOsC1 Low s...

Page 12: ...lo trKhi B 9 ry rd 0 0 ry rd Relay 2 energized delay time Settable Range 0 00 0 9 m 59 9 s A1 10 dsply pV12 dsply Display Function pV12 miN12 maX12 rs485 A2 10 dsply pV12 dsply Display Function pV12 m...

Page 13: ...lOsC1 or lOsC2 F2 or F7 and hIsC1 or hIsC2 F4 or F9 Please double check the lOsC1 or lOsC2 step A1 4 or A2 4 and hIsC1 or hIsC2 A1 5 or A2 5 are correct after selection the deflt or field Pass code de...

Page 14: ...ish the calibration lower point and go to next page F 7 lOsC2 88888 lOsC2 the value to be set is relative to Field Calibration low point of input 2 Press to set the value of lower scale F 8 ca hi 8888...

Page 15: ...table Range 19999 99999 Shift Up Down Enter 0 5 rYrst no no yes rYrst rY rSt Reset for energized hold of Relay If the ry_ md step B 3 7 set to be hIhld or lOhld and the present value PV reach to the c...

Page 16: ...the pass code please go to step A1 15 or A2 15 to set Please remind the new pass code Pass Code inpT1 group inpT2 group relay group ao group rs485 group INPUT 1 GROUP INPUT 2 GROUP RELAY GROUP ANALOG...

Page 17: ...o Adjustment for PV1 display For Zero Span of PV users can get the Fine Adjustment by front key It s an easy way to Just Key In the value that the user wants to show in the current input signal Especi...

Page 18: ...ontrol analogue output relay energized and so on Programmable pV12 PV 12 Show PV 12 miN12 Min 12 Minimum Hold of PV 12 maX12 MAX 12 Maximum Hold of PV 12 rs485 RS485 Remote displayed from RS485 comman...

Page 19: ...5 of stable reading 3 times Digital Filter set to be 3 continuously the meter will admit the samples and update the new reading Otherwise it will be as treat as a noise and skip the samples Settable...

Page 20: ...Please refer to the explanations in INPUT SCALING of FUNCTION DEFINE page 1 35 Settable range 0 00 100 00 Shift Up Down Enter A2 3 pv dp 0 0 0000 pv dp Pv2 dP Decimal Point of PV1 Programmable 0 0 00...

Page 21: ...pv sn Pv2 Sn Fine Span Adjustment for PV1 display It s same function as like as pv zo Settable range 19999 29999 Shift Up Down Enter A2 8 ZScl2 none none both ZScl2 Z S CL2 Clear Fine Zero Span Adjus...

Page 22: ...vG Average The meter s sampling is 15cycle sec If the avg Average set to be 3 to express the display update with 5 times sec The meter will calculate the sampling 1 3 and update the display value At m...

Page 23: ...not setting all All Level All lock User can access to all level for checking but can not setting Up Down Enter RELAY GROUP The group will not be displayed except the relay function is to be specified...

Page 24: ...int hIhld lOhld High Low Level energized hold High Low Level energize and latch As the PV Higher or lower than set point the relay will be energized to latch except manual reset by from key in User Le...

Page 25: ...AGE In following pages press for 1 second to back ANALOGUE GROUP INDEX PAGE D 1 aOtyp A4 20 A4 20 V0 10 aOtyp Ao tYP Analogue Output type Analogue output type had been fixed in mA or V as customer ord...

Page 26: ...the front key up or down key to adjust and check the output of meter Settable range 38011 27524 Shift Up Down Enter D 5 aOspn 0 00000 32767 aOspn Ao SPn Fine Span Adjustment for Analog Output Users c...

Page 27: ...lowing pages press for 1 second to back RS485 GROUP INDEX PAGE E 1 adres 1 001 255 adres AdrES Device number of the meter Settable range 1 255 Shift Up Down Enter E 2 baud 9600 9600 38400 baud bAUd Ba...

Page 28: ...lo CA1 Lo Field Calibration Low of input 1 The low calibration is not need the exactly zero to calibrate because of the field calibration function could be calibrate any lower point Waiting for the v...

Page 29: ...of machinery of input 2 to the lower signal output status or any lower status F 6 ca lo 0022h 052eh ca lo CA2 Lo Field Calibration Low of input 2 The low calibration is not need the exactly zero to ca...

Page 30: ...120 input low limit A Please check the aIlo and aIhi in input group are correct or not B Please changes another meter that is matching in the field Display shows ovfl ovfl 3 To inspect whether did th...

Page 31: ...t shown Check if the label of meter for detail specification A Please check the product number and output O P _____ description again for confirmation the relay output is specified or not B Please se...

Page 32: ...bright but no reply A Please confirms the CHECH SUM program is correct B Please check the interval of each command has to over 3 5byte Reply wrong data from the meter 2 Check if the square orange LED...

Page 33: ...12 0007h 19999 99999 The Maximum of PV 12 Low word 0 R RS485 0008h 19999 99999 PV 12 be written in by RS485 High word R W RS485 0009h 19999 99999 PV 12 be written in by RS485 Low word R W aOls 000Ah 1...

Page 34: ...R W dsply 0024h 0 3 Display Mode 0 PV 12 1 Minimum Hold 2 Maximum Hold 3 RS485 0 R W lOcT1 0025h 19999 19999 Low Cut of PV1 0 R W lOcT2 0026h 19999 19999 Low Cut of PV2 0 R W avg 0027h 1 99 Average 5...

Page 35: ...Digital Output 1 R W ry hy 0043h 0000 5000 Hysteresis of Relay2 0 R W ry rd 0044h 0000 5999 0 1second Energized Delay Time of Relay2 0 R W ry fd 0045h 0000 5999 0 1second De Energized Delay Time of Re...

Page 36: ...he information contained in this manual ADtek reserves the right to make improvements to this document and or product at any time without notice No part of this publication may be reproduced stored in...

Reviews: