TCX 226 

Two-Wire Isolated Thermocouple Transmitter 

Instruction Manual 

1.0  INTRODUCTION 

These instructions refer to the above model. Supplementary 

sheets are attached if the unit has special options orfeatures. 

For detailed specifications, see page 4 or refer to the Data 

Bulletin. All ADTE CH instruments are factory calibrated and 

supplied with a label detailing the calibration.  Adjustments 

are normally not necessary. A simple calibration should be 

performed to verify calibration before installation. 

2.0  GENERAL DESCRIPTION 

The  ADTECH  Model  TCX  226  Isolated  Two-Wire 

Thermocouple  Transmitter  provides  high  accuracy  con­

version of ISA type J, K, T, E, R, Sand B thermocouples and 

mv to a standard 4-20 ma de process signal. 

The TCX 226 provides 600 volts ac or 1000 volts de isolation 

from the input to output/power supply. 

The primary features of the TCX 226 are: 

• Wide  range-covers  the  full  range  of  ISA  standard

thermocouples and mv.

• Field adjustable via plug in jumpers and potentiometers.

• Zero suppression of up to 1 00% of the major range with

a16 position switch.

• High accuracy, repeatability, and ambient temperature

effect stability.

• RFI Resistant.

• NO INTERACTION of zero and span controls.

• Small  size-DIN  mounting  package  provides.  Only

1 "w x 3.1 "h x 3.6"d.

• Options  for  NEMA  4  and NEMA  7 housings,  SNAP

TRACK and surface mounting.

3.0  INSTALLATION 

The instrument is supplied in a non-metallic general purpose 

DIN  rail mount  enclosure  as  standard. NEMA  4,  7  or  12 

enclosures are optionally available.  Installation area/loca­

tion  must  agree  with  the  supplied  instruments  including 

operating temperature and ambient conditions. For detailed 

mounting and installation information refer to page 4 inside. 

Electrical Connections 

The  wire  used  to  connect  the  instrument  to  the  control 

system 

Input/ Output 

should be twisted pair(s) and sized 

according to normal practice. Shielded cable is not normally 

necessary  (if  used,  the  shield  must  be  grounded  at  the 

negative input of the AD TECH instrument and left floating at 

the sensor). 

A six 

position compression terminal block is provided for the 

1/0 and power connections. A housin

·

g ground terminal is not 

required due to non-metallic housing. 

Controls 

Instrument controls consist of the following: 

• Two  16  position  switches  for 

COARSE 

ZERO  and

COARSE 

SPAN control.

• One 4 position jumper for selection of major range.

• One 4-position jumper for TC-type.

• One 2-position jumper for 20 mv elevation.

• Two multiturn potentiometers; 

FINE 

ZERO and SPAN

controls.

The FINE ZERO and SPAN controls are accessible through 

the front of the instrument. 

4.0  MAINTENANCE 

These instruments are electronic and require no maintenance 

except periodic cleaning and calibration  verification.  If the 

unit appears to be mis-operating,  it should be checked as 

installed per section 6.0 or removed for a bench check per 

sections 6.0  and 7.0.  MOST problems are  traced to field 

wiring and / or associated circuits. If the problem appears to 

be with the instrument, proceed to sections 6.0 and 7.0. 

5.0  CONNECTIONS 

Standard connections are shown below and on the instrument 

face  plate,  Data  Bulletin  or  on  attached  supplementary 

sheets. 

ADTECH 

TCX226 

TWO WIRE 

TRANSMTR 

OUTPVT 

LOOPSU'!'\.Y 

-1-

(9/96)  190-A-000077-A 

Summary of Contents for TCX 226

Page 1: ...llation area loca tion must agree with the supplied instruments including operating temperature and ambient conditions For detailed mounting and installation information refer to page 4 inside Electrical Connections The wire used to connect the instrument to the control system Input Output should be twisted pair s and sized according to normal practice Shielded cable is not normally necessary if u...

Page 2: ... g 1 5 vdc across 250 ohms MILLIVOLT SOURCE DVM D Apply an input corresponding to the zero input temperature Rotate the FINE ZERO control fully counterclockwise Rotate the COARSE ZERO switch SWI to apositionwhere the zero leveljust goes above 4 00 ma output Rotate the COARSE ZERO switchbackone numberless thanthepreviousposition but not less than zero E With the input set at the zero input adjust t...

Page 3: ...d J2 C TABLE 2 INPUT ZERO ELEVATION CONTROL 20mV J3 A 0mV J3 B Jumper J6 A Fixed TABLE 3 TC BURNOUT ACTION Up Scale JS A Down Scale J5 B E J T K R S B TABLE 4 TC TYPE J1 A J1 B J1 C J1 D J1 Out 8 1 PCB LAYOUT COARSE SPAN COARSEZERO FINE ZERO FINE SPAN TB1 P1 G G I I 3 9 96 190 A 000077 A ...

Page 4: ...F 31 to 85 C operating 40 to 200 F 40 to 93 C storage k Power Supply Effect 0 005 over operating range m Isolation Input output case 1000 vdc or 600 vac n Cold Junction Compensation Error 1 5 C max 0 to 50 C o Burnout Current 0 1 micro amperes nominal Note All accuracies are given as a percentage of span POWER a 8 to 42 vdc standard MECHANICAL a Electrical Classification General purpose b Connecti...

Reviews: