Adtech SCT 302 Instruction Manual Download Page 1

SCT 302 

Isolated Convertor-DC Powered 
Instruction Manual 

1.0  INTRODUCTION 

These instructions refer to the above model. Supplementary 

sheets are attached if the unit has special options orfeatures. 

For detailed specifications, see page 4 or refer to the Data 

Bulletin.  All ADTE CH instruments are factory calibrated and 

supplied with a label detailing the calibration.  Adjustments 

are  normally  not necessary.  A  simple  check  should  be 

performed to verify calibration before installation to ensure 

that it matches the field requirement. 

2.0  GENERAL DESCRIPTION 

The ADTE CH SCT 302 is an Isolated Signal Transmitter that 

accepts  process  input  signals  such  as  4-20  ma  de  and 

converts them into a standard control signal output such as 

4-20 ma de,  1-5 vdc or 0-1 O vdc.

The  input  is  electrically  isolated  from  the  output  and  the 

power supply by 600 volts ac or 1000 vdc peak.The SCT 302 

is powered by 15-42 vdc. The negative rail of the output is 

common with the negative rail of the de power supply. 

The  output is a true current source and provides process 

signals such as 4-20 mA, 0-20 mA DC, 0-1 mA, 0-10 mA, or 

alternatively,  a  voltage  signal  of  5  VDC  full  scale.  Other 

current and voltagle Inputs/Outputs (1/0) 

are available as 

spectified on the Data Bulletin and on page 4 inside. 

3.0  INSTALLATION 

The  instrument  is  supplied  in  a  DIN  rail  mount  general 

purpose enclosure as standard. NEMA 4 and 7 enclosures 

are optionally available. Installation area/location must agree 

with the supplied instruments including operating temperature 

and ambient conditions. 

Electrical Connections 

The  wire  used  to  connect  the  instrument  to  the  control 

system 1/0  should be a twisted pair(s) and sized according 

to normal practice. Shielded cable is not normally necessary 

(if used, the shield must be grounded at the input negative 

of the ADTECH instrument and left floating at the sensor). 

Six  position compression terminal blocks are provided for 

1/0 and power connection. A housing ground terminal is not 

required due to non-metallic housing. 

Controls 

Multiturn ZERO and SPAN controls are provided to calibrate 

the instrument. The multiturn controls are accessible through 

the instrument front panel and are clearly marked for ease 

of use. Other internal range selection jumpers are provided 

for ease of field rangeability as listed below. 

one 16-position coarse ZERO SWITCH (SWI) 

one 16-position coarse SPAN SWITCH (SW2) 

4.0  MAINTENANCE 

These instruments are electronic and require no maintenance 

except  periodic  cleaning and calibration verification.  If the 

unit appears to be mis-operating it should be checked as 

installed per section 6.0 or removed for a bench check per 

sections 6.0-7.0.  MOST problems are traced to field wiring 

and/or associated circuits. If the problem appears to be with 

the instrument, proceed to sections 7.0. 

5.0  CONNECTIONS 

Standard connections are shown below and on the instrument 

face  plate,  Data  Bulletin  or  on  attached  supplementary 

sheets. 

ADTECH 

SCT302 

COM. 

-1-

( 4-98)  190-A-000076· 8-