background image

Document 50934     Rev B     5/15/00     PN 50934:B

23

Loop Number (64 - 65)
For Contact ID format only.  Factory default is '00'.  Maximum value is '97'.  Refer to
Section 5.0 for additional information.

Device/Zone Number (66 - 68)
For Contact ID format only.  These entries apply to the general reports only, i.e. general
alarm, general trouble, general supervisory.  Factory default is '000'.  Maximum value is
'999'.  Refer to Section 5.0 for additional information.

Note: For the Contact ID Format, Loop Number and Device Number do not directly
correspond to the SLC Loop or Device Number, instead, it is a convenient way to transmit
data to the Central Station.  Using the default Loop Number of '00' allows the reporting of
a maximum of 999 devices or zones (001-999).  To report device addresses or zones
higher than 999 (the Unimode 2020 can report up to 2,040 addresses), the Loop Number
is incremented by one to report up to an additional 1,000 device addresses or zones on
the same panel.  Following is an example (using the factory defaults) of Loop Number and
Device Number settings for the ADT-UDACT on a single Unimode 2020 control panel:

Loop Number '00'

reports points/zones 00 001 to 00 999

Loop Number '01'

reports points/zones 01 000 to 01,999

Loop Number '02'

reports points/zones 02 000 to 02,040

If the Loop Number (54-65) is programmed to 10, the devices are reported as:

Loop Number '10'

reports points/zones 10 001 to 10 999

Loop Number '11'

reports points/zones 11 000 to 11,999

Loop Number '12'

reports points/zones 12 000 to 12,040

In applications which network multiple Fire Alarm Control Panels, the group number
may be used to help identify each facility being monitored.  For example, each ADT-
UDACT can report its panel's devices by designating different Loop Numbers for each
panel.  The Loop Numbers assigned to a particular panel must be sequential, but the Loop
Numbers from one panel to the next need not be sequential; i.e., the Loop Numbers
assigned for the ADT-UDACT on one Unimode 2020 might be 00, 01 or 02 while the
Loop Numbers for another FACP might be 10, 11 or 12 or any other set of unused
consecutive numbers.  For additional information on the Unimode 2020/1010 control
panels, refer to Appendix D.

Programming Event Codes (69-208)
The type of reports and 'event codes' that are sent to the Central Station are in Tables 3-2
through 3-7.  The selections made for the Primary Central Station Number Communication
Format (address 16) and the Secondary Central Station Number Communication Format
(address 42) automatically program addresses 69-208 with factory default selections.

Any of the event codes may be changed.  Consult your Central Station prior to altering
the event codes.
  For the 3+1, 4+1 and 4+1 Express Formats, entering an event code of '0'
will cause the communicator to NOT transmit the report.   Enter two zeroes for 4+2 and
4+2 Express Formats.  For Ademco Contact ID format enter three zeroes.  Transmission of
reports to either or both Central Station phone numbers may be disabled.

Note the special 'System Abnormal Test Report' event code.  This report was added per
new UL DACT requirements.  This report is generated in place of the normal test report
when an alarm and/or trouble condition exists at the time the test report is due to be sent.

Summary of Contents for ADT-UDACT

Page 1: ...versal Digital Alarm Communicator Transmitter Product Information Installation Programming and Operation Manual Document 50934 5 15 00 Rev B udactnot wmf One Town Center Road Boca Raton FL 33431 Phone 561 988 3600 FAX 561 988 3675 Security Services Inc ...

Page 2: ...explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least ...

Page 3: ... anticipated or encountered Disconnect AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former and ...

Page 4: ... Wiring 14 2 1 General 14 2 2 Output Circuits 14 Figure 2 1 Wiring Phone Jacks 14 Figure 2 2 Relay Driver Connections 15 Figure 2 3 Monitoring for ADT UDACT Trouble 16 2 3 UL Power limited Wiring Requirements 17 Figure 2 4 Typical Wiring Diagram for UL Power limited Requirements 17 3 0 Programming Instructions 18 3 1 Entering Program Mode 18 3 2 Switch Functions 19 Figure 3 1 ADT UDACT Keypad 19 3...

Page 5: ...Assignments Unimode 300 400 47 Appendix B Point Assignments Unimode 300 400 48 Appendix C Point Assignments ADT MNNA 51 Appendix D Unimode 2020 1010 56 Figure D 1 ADT UBS 1F 56 Figure D 2 ADT UDACT Mounting in CHS 4 56 Figure D 3 EIA 485 Connection to Panel Mounted ADT UDACT 57 Figure D 4 EIA 485 Connection to Remote ADT UDACT 58 Appendix E Unimode 300 400 59 Figure E 1 ADT ABS8RF 59 Figure E 2 AD...

Page 6: ...lly Actuated Signaling Boxes UL 217 Smoke Detectors Single and Multiple Station UL 228 Door Closers Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Sig...

Page 7: ...red 7 segment LED display Manual test report function Manual master transmission clear function Mounts in separate ADT ABS 8RF or ADT UBS 1 enclosure Communicates vital system status including ü Independent zone point alarm ü Independent zone point trouble ü Independent zone point supervisory ü AC mains power loss programmable ü Low battery and earth fault ü System off normal ü 12 or 24 hour test ...

Page 8: ... UDACT Assembly Primary Phone Line Secondary Phone Line Modular Cables P N MCBL 7 Order Separately 24VDC Power in use power limited source EIA 485 Connector use power limited source Comm Fail Output power limited 24 VDC power limited DO NOT USE udactfea wmf ...

Page 9: ...odular phone jacks allow easy connection to telephone lines Modular jacks are labeled PH1 and PH2 for the Primary and Secondary phone lines Telephone line Primary and Secondary Active red LEDs are provided as well as a green Kissoff LED The integral digital communicator provides the following functions Line Seizure takes control of the phone lines disconnecting any premises phones Off On Hook perf...

Page 10: ...ctions are made to the RS RS and Shield terminals of TB1 on the ADT UDACT The EIA 485 circuit cannot be T Tapped and must be wired in a continuous fashion from the control panel to the ADT UDACT and if installed annunciators The wire must be 12AWG to 18AWG twisted shielded pair cable with a Characteristic Impedance of 120 Ohms 20 Limit the total wire resistance to 100 Ohms on the EIA 485 circuit D...

Page 11: ...le Connector Supervision Threshold less than 4 0 volts for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive REN s on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of the REN s should not exceed five 5 0 To be certain of the number of devices that may be ...

Page 12: ...smitted includes general alarm trouble and supervisory It also transmits either the number of zones or points activated or the specific point s activated depending upon the compatible panel programming selections and transmission format selection Specific system trouble conditions and specific ADT UDACT troubles are also transmitted 1 9 2 Program Mode Program mode is used to program the ADT UDACT ...

Page 13: ...ed it causes the ADT UDACT to immediately stop transmissions hang up from the telephone network clear out any messages that were waiting for transmission and reset 1 9 7 Manual Test Function The manual test function allows for a test report message to be sent to both Central Stations upon activation ...

Page 14: ...g Telco Phone Lines Mounting Options For information on mounting the ADT UDACT in a specific fire alarm control panel refer to the appropriate Appendix Telephone Circuits Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 Primary and PH2 Secondary Telephone line control command is possible via double line seizure as well as usage of an RJ31X st...

Page 15: ...acts must remain in the same room as the ADT UDACT When the ADT UDACT is programmed for Receive Only typically this occurs when annunciators are also used and are set for Receive Transmit the relay output is used to provide a ADT UDACT trouble input to the host control panel For Unimode 2020 1010 applications use a monitor module to supervise the relay closure Refer to Figure 2 3 Program the custo...

Page 16: ...ntact will open causing the monitor module to transmit trouble condition to FACP Figure 2 3 Monitoring for ADT UDACT Trouble udactrbl wmf ADT UDACT SLC Loop to Fire Alarm Control Panel 3 9K EOL Resistor included Wiring in same room as ADT UDACT M300 Series Monitor Module 0 18 24 115 230 All wiring to relay must be in the same room within 20 feet of ADT UDACT and in conduit NC C NO ON Earth Grnd Co...

Page 17: ...mited circuit wiring Furthermore all power limited circuit wiring and nonpower limited circuit wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram for the ADT UDACT is shown below 2 3 UL Power limited Wiring Requirements Figure 2 4 Typical Wiring Diagram for UL Power limited Requirements Power limited circuits Use power limited source DO NOT ...

Page 18: ...from 0 and a valid phone number is entered transmission of the ADT UDACT off Normal report will occur Programming of the ADT UDACT is possible at any time including while the ADT UDACT is communicating with a Central Station The ADT UDACT has been designed for many different types of applications After examining your specific application review the programming options and choose the entries best s...

Page 19: ... keypad B on a Touchtone phone keypad C look for secondary dial tone for up to 2 seconds then dial anyway D 3 second pause E 5 second pause F end of phone number Note F must be entered The Function of each switch in program mode is shown below 3 2 Switch Functions No function in this mode 3 3 Programming Options Increment memory address Decrement memory address Select operating mode Figure 3 1 ADT...

Page 20: ...te Consult your Central Station for proper selection or consult our factory representatives For any format chosen the ADT UDACT automatically programs all of the event codes See Tables 3 2 3 3 3 4 3 5 3 6 and 3 7 Primary Number Account Code 17 20 Four locations at addresses 17 20 default to all 0 s Valid entries are 0 9 and A F The number of digits entered must match the format selection If progra...

Page 21: ...es 43 46 in the same manner as the primary phone number Account Code Default entries are all 0s Secondary Number 24 Hour Test Time 47 50 is programmed in addresses 47 50 in the same manner as the primary number 24 Hour Test Time Default is 00 00 12 00 midnight Secondary Number 24 12 Hour Test Time 51 The test message sent to the Secondary phone number may be sent every 12 or 24 hours If the messag...

Page 22: ...iggers Touchtone dialing over both phone lines Select 1 for rotary dialing Make Break Ratio 59 Use this address only if you have chosen 1 for address 58 The make break ratio is factory set to 0 which is 67 33 but may be changed to 1 which is a 62 38 ratio Address 60 Leave default of 0 Address 61 Leave default of 0 AC Loss Reporting Delay 62 1 is factory default which causes a 6 hour time delay for...

Page 23: ... which network multiple Fire Alarm Control Panels the group number may be used to help identify each facility being monitored For example each ADT UDACT can report its panel s devices by designating different Loop Numbers for each panel The Loop Numbers assigned to a particular panel must be sequential but the Loop Numbers from one panel to the next need not be sequential i e the Loop Numbers assi...

Page 24: ...ress Description Setting 69 Primary General Alarm Code 1 70 Primary Zone Point Alarm Code 0 71 Primary General Supervisory Code 8 72 Primary Zone Point Supervisory Code 0 73 Primary General Fault Code F 74 Primary AC Fault Code F 75 Primary Zone Point Fault Code 0 76 Primary Low Battery Fault Code F 77 Primary Telco Primary Line Fault Code F 78 Primary Telco Secondary Line Fault Code F 79 Primary ...

Page 25: ... Trouble Code FE 97 98 Primary System Off Normal Code FF 99 100 Primary ADT UDACT Off Normal Code FF 101 102 Primary General Alarm Restore Code E1 103 104 Primary Zone Point Alarm Restore Code 00 105 106 Primary General Supervisory Restore Code E2 107 108 Primary Zone Point Supervisory Restore Code 00 109 110 Primary General Fault Restore Code E3 111 112 Primary AC Fault Restore Code E6 113 114 Pr...

Page 26: ...est 602 00 120 122 Primary System 24 Hour Test w active event 608 00 123 125 Primary Manual Test Message 601 00 Notes 1 Note Zero entries prevent the transmission of the report to the Central Station 2 Refer to Contact ID program locations 64 68 3 The identification of the zone device number is automatically transmitted by the ADT UDACT and is added to the main event code See Table 5 3 for more in...

Page 27: ... 160 Secondary AC Fault Restore Code E 161 Secondary Zone Point Fault Restore Code 0 162 Secondary Low Battery Fault Restore Code E 163 Secondary Telco Primary Line Fault Restore Code E 164 Secondary Telco Secondary Line Fault Restore Code E 165 Secondary NAC Fault Restore Code E 166 Secondary Comm Trouble Primary Restore Code E 167 Secondary Comm Trouble Secondary Restore Code E 168 Secondary 485...

Page 28: ...Number Code FE 165 166 Secondary 485 Comm Trouble Code FE 167 168 Secondary System Off Normal Code FF 169 170 Secondary ADT UDACT Off Normal Code FF 171 172 Secondary General Alarm Restore Code E1 173 174 Secondary Zone Point Alarm Restore Code 00 175 176 Secondary General Supervisory Restore Code E2 177 178 Secondary Zone Point Supervisory Restore Code 00 179 180 Secondary General Fault Restore C...

Page 29: ...y Comm Trouble Secondary Code 354 00 178 180 Secondary 485 Comm Trouble Code 300 00 181 183 Secondary System Off Normal Code 308 00 184 186 Secondary ADT UDACT Off Normal Code 350 00 187 189 Secondary System 24 Hour Test 602 00 190 192 Secondary System 24 Hour Test w active event 608 00 193 195 Secondary Manual Test Message 601 00 Notes 1 Note Zero entries prevent the transmission of the report to...

Page 30: ...sions reset and return to normal system processing To perform the Clear function press the Clear Key followed by 2 5 3 2 then press the ENTER STORE key If the Test Key is pressed three times in rapid succession the ADT UDACT will transmit a test message to both Central Stations The message reported is the same as the automatic test message for all formats except Ademco Contact ID Pressing the Mode...

Page 31: ...dary Phone Line Fault PH_1 PH_2 no_1 no_2 Individual LEDs are provided for EIA 485 A yellow LED that turns on steady when a fault on the EIA 485 circuit is detected Comm Fail This yellow LED turns on to indicate the loss of both telephone lines or that the maximum number of attempts to communicate with both Central Stations has been unsuccessful Note During a comm fail the display will show either...

Page 32: ... the ADT UDACT to the telephone lines The ADT UDACT supervises both telephone lines for proper voltage A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble When a fault is detected the 4 character display will show either no 1 or no 2 depending upon which telephone line has the fault no 1 Primary Line no 2 Secondary Line and the trouble conditio...

Page 33: ...upervisory 4 Zone Point Supervisory N 5 General System Trouble 6 AC Power Loss 7 Zone Point Trouble N 8 Low Battery 9 Telco Primary Line Fault 10 Telco Secondary Line Fault 11 NAC Fault Code 12 Communication Trouble Primary Number 13 Communication Trouble Secondary Number 14 EIA 485 Communication Bus Trouble 15 System Off Normal Code 16 System Automatic Test Report 17 System Abnormal Automatic Tes...

Page 34: ...ally every 24 hours Should there exist an abnormal condition in the fire alarm system such as an alarm trouble or supervisory condition at the time when the test report is due to be transmitted the ADT UDACT will report the system abnormal test report If the system is normal the report transmitted will be the normal system test report EIA 485 Communications Trouble Report The ADT UDACT supervises ...

Page 35: ... of devices on a single zone To change the type definition of the zone or point from the factory default of 0 select 2 to F corresponding to the type of device s used do not mix device types for these settings or select 1 to disable alarm reporting of any zone or point The digit entered will appear on the far right display Next press the ENTER STORE key This stores the entry into E2 memory and inc...

Page 36: ...phone Line Testing Pressing C for touchtone dialing or D for rotary dialing followed by ENTER STORE causes seizure of the Primary phone line which in turn lights the red LED signifying Primary phone line active After a delay of three seconds the ADT UDACT goes off hook to acquire a dial tone The ADT UDACT keypad may be used as a telephone touchpad for number dialing Once the first digit is pressed...

Page 37: ...th Primary and Secondary Lines To perform a Lamp Test press MODE then 5267 followed by ENTER STORE This will test all system LEDs The LEDs will stay on for five seconds then the ADT UDACT will return to normal mode 5267 spells LAMP on a Touch Tone phone 4 4 Lamp Test Mode UDACTNOT WMF ...

Page 38: ...ic zone or point identification 5 0 Reporting Formats Format 0 2 4 6 8 Format 1 A C Report 3 1 4 1 Standard 4 1 Express 4 2 Standard 4 2 Express Alarm SSS S A SSSS AA2 Alarm Restore SSS S RA SSSS RARA2 Zone Trouble Zone Open SSS S RTZ SSSS TZTZ2 Zone Trouble Restore SSS S RTZ SSSS RTZRTZ2 System Trouble SSS S TS SSSS TSTS2 System Trouble Restore SSS S RTS SSSS RTSRTS2 Low Battery SSS S L SSSS LL2 ...

Page 39: ...it RTS2 System Trouble Restore 2nd digit L Low Battery 1st digit L2 Low Battery 2nd digit RL Low Battery Restore 1st digit RL2 Low Battery Restore 2nd digit P AC Loss 1st digit P2 AC Loss 2nd digit RP AC Loss Restore 1st digit RP2 AC Loss Restore 2nd digit V Supervisory Condition 1st digit V2 Supervisory Condition 2nd digit RV Supervisory Condition Restore 1st digit RV2 Supervisory Condition Resto...

Page 40: ...eporting Structure follows Time Date SSSS QXYZ GG CCCC4 11 28 03 25 11 7777 E110 00 C000 general alarm 11 28 03 25 11 7777 E111 00 C046 alarm SD46 11 28 03 25 11 7777 E300 00 C000 general trouble 11 28 03 25 11 7777 E380 00 C046 trouble SD46 11 28 03 25 11 7777 R110 00 C000 general alarm restore 11 28 03 25 11 7777 R111 00 C046 alarm SD46 restore 11 28 03 25 11 7777 R300 00 C000 general trbl resto...

Page 41: ...0 0 4 1 1 E 5 m r a l A w o l f r e t a W 5 5 0 0 C 0 0 3 1 1 E 6 m r a l A r o t c e t e D t c u D 6 6 0 0 C 0 0 6 1 1 E 7 m r a l A r o s n e S e m a l F 7 7 0 0 C 0 0 7 1 1 E 8 m r a l A e n o Z e k o m S l a n o i t n e v n o C 2 2 0 0 C 0 0 1 1 1 E 9 y r a l g r u B 8 8 0 0 C 0 0 0 3 1 E A y r a l g r u b n o N r u o H 4 2 9 9 0 0 C 0 0 0 5 1 E B e r u t a r e p m e T h g i H 0 1 0 1 0 C 0 0 ...

Page 42: ...ACT Ademco 685 1 Silent Knight 9000 ITI CS 4000 3 FBI CP220FB Osborne Hoffman Quick Alert Models 1 2 Radionics 6000 6500 5 Linear Sescoa 3000R 7 1 With 685 8 Line Card with Rev 4 4d software 2 With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A software 3 Rev 4 0 software 4 FBI CP220FB Rec 11 Line Card with Rev 2 6 software and a memory card with Rev 3 8 software 5 Model 6500 with R...

Page 43: ...unication 1 for zone reporting receive only communication 2 for zone reporting receive transmit communication 3 for point reporting receive only or 4 for point reporting receive transmit 57 Backup Reporting Enter 0 to have secondary phone number act as backup only 1 to have secondary phone number receive all reports and messages along with primary phone number 58 Touchtone Rotary Select Enter 0 fo...

Page 44: ... 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 Programming Reference Sheet...

Page 45: ... 1800 2300 43 44 45 46 Secondary Account Code 47 48 49 50 Secondary 24 Hour Test Time 0000 12 00 midnight 51 Secondary Number Test Time Interval 0 for 24 hour 52 53 Start Monitoring Address 54 55 End Monitoring Address 56 ADT UDACT Communication Selection 0 for ADT UDACT Communication disabled 57 Backup Reporting 0 for backup 58 Touchtone Rotary Select 0 for Touchtone 59 Make Break Ratio 0 for 67 ...

Page 46: ... 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 1 1 0 0 8 1 0 0 F 1 F 6 0 0 F 8 F A F B F C F D F E F E F F F F E 1 0 0 E 2 0 0 E 3 E 6 0 0 E 8 E A E B E C E D E E E E E F E F 9 9 9 1 9 2 1 1 0 0 8 1 0 0 F 1 F 6 0 0 F 8 F A...

Page 47: ...he system for proper reporting Caution When selecting burglar zones modify the general supervisory report at addresses 75 77 and 145 147 to report general burglary Zone No Zone Function Zone No Zone Function Zone No Zone Function 1 34 67 2 35 68 3 36 69 4 37 70 5 38 71 6 39 72 7 40 73 8 41 74 9 42 75 10 43 76 11 44 77 12 45 78 13 46 79 14 47 80 15 48 81 16 49 82 17 50 83 18 51 84 19 52 85 20 53 86...

Page 48: ... 0 2 2 1 2 7 1 3 2 0 3 7 0 3 2 1 3 7 1 4 2 0 4 7 0 4 2 1 4 7 1 5 2 0 5 7 0 5 2 1 5 7 1 6 2 0 6 7 0 6 2 1 6 7 1 7 2 0 7 7 0 7 2 1 7 7 1 8 2 0 8 7 0 8 2 1 8 7 1 9 2 0 9 7 0 9 2 1 9 7 1 0 3 0 0 8 0 0 3 1 0 8 1 1 3 0 1 8 0 1 3 1 1 8 1 2 3 0 2 8 0 2 3 1 2 8 1 3 3 0 3 8 0 3 3 1 3 8 1 4 3 0 4 8 0 4 3 1 4 8 1 5 3 0 5 8 0 5 3 1 5 8 1 6 3 0 6 8 0 6 3 1 6 8 1 7 3 0 7 8 0 7 3 1 7 8 1 8 3 0 8 8 0 8 3 1 8 8 1 9...

Page 49: ... 8 1 3 8 6 3 9 1 2 9 6 2 9 1 3 9 6 3 0 2 2 0 7 2 0 2 3 0 7 3 1 2 2 1 7 2 1 2 3 1 7 3 2 2 2 2 7 2 2 2 3 2 7 3 3 2 2 3 7 2 3 2 3 3 7 3 4 2 2 4 7 2 4 2 3 4 7 3 5 2 2 5 7 2 5 2 3 5 7 3 6 2 2 6 7 2 6 2 3 6 7 3 7 2 2 7 7 2 7 2 3 7 7 3 8 2 2 8 7 2 8 2 3 8 7 3 9 2 2 9 7 2 9 2 3 9 7 3 0 3 2 0 8 2 0 3 3 0 8 3 1 3 2 1 8 2 1 3 3 1 8 3 2 3 2 2 8 2 2 3 3 2 8 3 3 3 2 3 8 2 3 3 3 3 8 3 4 3 2 4 8 2 4 3 3 4 8 3 5 3...

Page 50: ...0 4 5 5 4 6 0 4 6 5 4 7 0 4 7 5 4 8 0 4 8 5 4 9 0 4 9 5 4 0 1 4 0 6 4 1 1 4 1 6 4 2 1 4 2 6 4 3 1 4 3 6 4 4 1 4 4 6 4 5 1 4 6 1 4 7 1 4 8 1 4 9 1 4 0 2 4 1 2 4 2 2 4 3 2 4 4 2 4 5 2 4 6 2 4 7 2 4 8 2 4 9 2 4 0 3 4 1 3 4 2 3 4 3 3 4 4 3 4 5 3 4 6 3 4 7 3 4 8 3 4 9 3 4 0 4 4 1 4 4 2 4 4 3 4 4 4 4 4 5 4 4 6 4 4 7 4 4 8 4 4 9 4 4 0 5 4 Note Event Code cannot be altered Physical location is critical to...

Page 51: ...15 36 76 116 37 77 117 38 78 118 39 79 119 40 80 120 Note Use the following charts to carefully identify the function of each point in the system Take special precaution with any supervisory points in the system For the ADT UDACT to report a supervisory point to the central station both the FACP and the ADT UDACT must have the point programmed as supervisory Failure to program the panel or ADT UDA...

Page 52: ...09 130 170 210 131 171 211 132 172 212 133 173 213 134 174 214 135 175 215 136 176 216 137 177 217 138 178 218 139 179 219 140 180 220 141 181 221 142 182 222 143 183 223 144 184 224 145 185 225 146 186 226 147 187 227 148 188 228 149 189 229 150 190 230 151 191 231 152 192 232 153 193 233 154 194 234 155 195 235 156 196 236 157 197 237 158 198 238 159 199 239 160 200 240 Appendix C continued Poin...

Page 53: ...29 250 290 330 251 291 331 252 292 332 253 293 333 254 294 334 255 295 335 256 296 336 257 297 337 258 298 338 259 299 339 260 300 340 261 301 341 262 302 342 263 303 343 264 304 344 265 305 345 266 306 346 267 307 347 268 308 348 269 309 349 270 310 350 271 311 351 272 312 352 273 313 353 274 314 354 275 315 355 276 316 356 277 317 357 278 318 358 279 319 359 280 320 360 Appendix C continued Poin...

Page 54: ...49 370 410 450 371 411 451 372 412 452 373 413 453 374 414 454 375 415 455 376 416 456 377 417 457 378 418 458 379 419 459 380 420 460 381 421 461 382 422 462 383 423 463 384 424 464 385 425 465 386 426 466 387 427 467 388 428 468 389 429 469 390 430 470 391 431 471 392 432 472 393 433 473 394 434 474 395 435 475 396 436 476 397 437 477 398 438 478 399 439 479 400 440 480 Appendix C continued Poin...

Page 55: ...24 564 485 525 565 486 526 566 487 527 567 488 528 568 489 529 490 530 491 531 492 532 493 533 494 534 495 535 496 536 497 537 498 538 499 539 500 540 501 541 502 542 503 543 504 544 505 545 506 546 507 547 508 548 509 549 510 550 511 551 512 552 513 553 514 554 515 555 516 556 517 557 518 558 519 559 520 560 Appendix C continued Point Assignments ADT MNNA ...

Page 56: ...to TB1 on the ADT UDACT Note The ADT UDACT does not support voice and burglar options when used with the Unimode 2020 1010 Refer to the Unimode 2020 1010Manual for additional restrictions ADT UDACT mounting in a Unimode 2020 1010 Remove all power from the FACP by disconnecting AC and batteries Install the three supplied nylon support posts for the top and bottom left of the ADT UDACT one aluminum ...

Page 57: ...imited Figure D 3 EIA 485 Connection to Panel Mounted ADT UDACT TB5 Terminal 5 EIA 485 Terminal 6 EIA 485 Refer to Figure I 4 for power connections to ADT UDACT Install 120 ohm EOL resistor P N 71244 across terminals 3 4 if last or only device on EIA 485 line Note that Terminals 6 7 are not used at this time DO NOT USE ...

Page 58: ...connected to TB1 Terminal 5 Shield at ADT UDACT as shown in Figure D 4 NOTE The shield end that is not connected should be insulated to prevent accidental grounding Do not connect both ends of shield under any circumstance since a ground fault may result 4 Conduit is recommended for external wire runs Consult local building codes 5 Connect Ground Strap supplied with ADT ABS8RF enclosure from Earth...

Page 59: ...e control panel enclosure the ADT UDACT must be mounted remotely using an ADT ABS8RF enclosure Ferrite cores are recommended for this application Refer to Figure E 3 and the accompanying notes for wiring alternatives Connect the communication line between the EIA 485 terminal block TB4 on the Unimode 300 400 and TB 1 terminals 3 and 4 on the ADT UDACT being certain to observe polarity refer to Fig...

Page 60: ...commended for external wire runs Consult local building codes 5 Connect Ground Strap supplied with ADT ABS8RF enclosure from Earth Ground terminal on ADT UDACT to a solid building earth ground Conduit alone will not provide a reliable earth ground 6 ADT UDACT may be located up to 6 000 feet away from the host control panel 7 Refer to Specifications for power requirements EIA 485 ACS Mode TB4 1 TB4...

Page 61: ...99 For Point Reporting Loop 1 Modules 101 196 report as device numbers 01 96 Report defaults to 110 Loop 2 Modules 201 296 report as device numbers 101 196 Report defaults to 110 Loop 1 Detectors 101 196 report as device numbers 201 296 Report defaults to 111 Loop 2 Detectors 201 296 report as device numbers 301 396 Report defaults to 111 Output Modules 1 64 report as device numbers 401 464 Report...

Page 62: ...the control panel s main power supply 24 VDC nominal filtered nonresettable output to TB1 on the ADT UDACT Note The ADT UDACT does not support voice and burglar options when used with the ADT MNNA Refer to the ADT MNNA Manual for additional restrictions ADT UDACT mounting in an ADT MNNA Remove all power from the ADT MNNA by disconnecting AC and batteries Install the three supplied nylon support po...

Page 63: ...ervised and Power limited Figure F 1 EIA 485 Connection to Panel Mounted ADT UDACT TB1 Terminal 3 EIA 485 Terminal 4 EIA 485 power connections to ADT UDACT Install 120 ohm EOL resistor P N 71244 across terminals 3 4 if last or only device on EIA 485 line Note that Terminals 6 7 are not used at this time DO NOT USE TB1 ...

Page 64: ... may be connected to TB1 Terminal 5 Shield at ADT UDACT NOTE The shield end that is not connected should be insulated to prevent accidental grounding Do not connect both ends of shield under any circumstance since a ground fault may result 4 Conduit is recommended for external wire runs Consult local building codes 5 Connect Ground Strap supplied with ADT ABS8RF enclosure from Earth Ground termina...

Page 65: ... e t s y S s s o l C A t p e c x e 2 d e c n e l i S s l a n g i S d e c n e l i S s l a n g i S 3 d e s U t o N e d o M m a r g o r P 4 d e s U t o N y r o s i v r e p u S 5 y r o s i v r e p u S e l b u o r T l l e B 6 m r a l a e r P m r a l a e r P t r e l A e c n a n e t n i a M 7 l i a F C A y r e t t a B w o L 8 e l b u o r T l e n a P l i a F C A A N N M T D A 0 1 0 1 0 2 0 2 e d o m i n U...

Page 66: ...Document 50934 Rev B 5 15 00 PN 50934 B 66 ...

Page 67: ...Document 50934 Rev B 5 15 00 PN 50934 B 67 ...

Page 68: ...Document 50934 Rev B 5 15 00 PN 50934 B 68 ...

Reviews: