aTCA-81514PA
4 Shelf Ground Connection
The ATCA Shelf provides a Shelf ground terminal at the left rear side. The Shelf
ground terminal provides two threads (M6) with a 15.88 mm (5/8“) spacing between
thread centers to connect a two hole lug Shelf ground terminal cable.
Figure 8: Shelf Ground Terminal
1
Ground Terminal
4.1 Specification for the Shelf Ground Connection Cable
Required wire size:
#3 AWG or #2 AWG, maximum length 3 m.
Required terminals:
Use only two hole lug terminals. (For example PANDUIT
LCC2
‐
14AHQ or LCD2
‐
14AHQ with 45° angle)
Hazardous voltage!
Before powering
‐
up the Shelf, make sure that the Shelf Ground terminals are
connected to Protective Earth (PE) of the building.