![ADF Web HD67D03-B2-868MHz User Manual Download Page 16](http://html1.mh-extra.com/html/adf-web/hd67d03-b2-868mhz/hd67d03-b2-868mhz_user-manual_2851180016.webp)
Industrial
Electronic Devices
ADFweb.com S.r.l.
User Manual
LoRaWAN / Modbus TCP Master
Document code: MN67D03_ENG Revision 1.000 Page 16 of 29
SET COMMUNICATION:
By Pressing the “
Set Communication
” button from the main window for SW67D03 (Fig.
2) the window “Set Communication” appears (Fig. 3).
The means of the fields for the “LoRaWAN” section are:
In the field “
RF Band
” the wireless band used for LoRaWAN communication is
defined;
In the field “
Network Type
” the type of LoRaWAN network is defined;
If the field “Adaptive Data Rate” is checked, the converter will enable the ADR
functionalities to select the best data rate to be used in relation to the
environmental conditions;
In the field “
Data Rate
” the data rate for LoRaWAN communication is defined;
In the field “
Transmission Type
” the type of LoRaWAN communication is defined;
In the field “
Max Payload Size
” the maximum dimension of the LoRaWAN
messages is defined (fixed in relation to the data rate selected);
In the field “
Activation Method
” the method used to join into a LoRaWAN network
is defined;
In the field “
Device Address
” the device identifier (DevEUI) is defined (only for
ABP method);
In the field “
Application Identifier
” the application identifier (AppEUI) is defined
(only for ABP method);
In the field “
Network Session Key
” the key used for the communication with the
LoRaWAN gateway (NwkSKey) is defined (only for ABP method);
In the field “
Application Session Key
” the key for encryption and decryption of
the payload (AppSKey) is defined (only for ABP method);
If OTAA method is selected, in the field “
Application Key
” the secret key for the
dynamic activation of the converter in the LoRAWAN network is defined.
Figure 3: “Set Communication” window