MQTT: 

 
This section is used to define the main parameters of MQTT line. The means of the 
fields are: 

 

In the field “

Server  URL

” the URL or the  IP  Address of the MQTT Server is 

defined; 

 

In the field “

Server Port

” the port used for MQTT communication is defined; 

 

In the field “

Client ID

” the Client ID of the converter is defined (if ned); 

 

In  the  field  “

Keep  Alive  (seconds)

”  the  delay  with  which  the  Keep  Alive 

message is sent on MQTT is defined; 

 

If the field “

Clean Session

” is checked, the last MQTT messages are deleted 

by  the  Server  and  the  Client  in  case  of  missing  ACK.  If  unchecked,  the 
Server and the Client hold the last MQTT messages and, in case of incorrect 
disconnection or missing ACK, they try to send again them since all the ACK 
messages are exchanged correctly (valid only for QoS 1 and QoS 2); 

 

If the field “

Will Flag

” is checked, the converter will publish the Will topic at 

the  connection  to  the  Server.  With  this  feature,  in  case  of  incorrect 
disconnection,  the  Server  will  publish  this  topic  to  all  the  MQTT  Clients  that 
subscribed it; 

 

In the field “

Topic Name Will

” the topic used for Will message is defined; 

 

In the field “

Message Will

” the payload of the Will message is defined; 

 

In  the  field  “

Retained  Will

”  the  converter  will  send  the  Will  message  with 

Retain flag enabled. In this way, the Server will hold the last Will message; 

 

In the field “

QoS Will

” the QoS type for Will message is defined; 

 

Im the field “

Username

” the username for the connection to the MQTT server is defined; 

 

In the field “

Password

” the password for the connection to the MQTT server is defined; 

 

In the field “

Send Time (seconds)

” the delay with which the MQTT messages are published is defined. 

Summary of Contents for HD67954-B2

Page 1: ...Product HD67935 Modbus TCP Master www adfweb com Product HD67936 Modbus TCP Slave www adfweb com Product HD67937 BACnet Master www adfweb com Product HD67938 BACnet Slave www adfweb com Product HD679...

Page 2: ...ES AND TECHNICAL SUPPORT 31 RETURN POLICY 31 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related...

Page 3: ...e can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation of...

Page 4: ...Industrial Electronic Devices ADFweb com S r l User Manual SNMP Agent MQTT Document code MN67954_ENG Revision 1 000 Page 4 of 31 EXAMPLE OF CONNECTION...

Page 5: ...Industrial Electronic Devices ADFweb com S r l User Manual SNMP Agent MQTT Document code MN67954_ENG Revision 1 000 Page 5 of 31 CONNECTION SCHEME Figure 1 Connection scheme for HD67954 B2...

Page 6: ...istics Mountable on 35mm Rail DIN Wide power supply input range 18 35V DC and 8 24V AC Wide temperature range 40 C 85 C 40 F 185 F CONFIGURATION You need Compositor SW67954 software on your PC in orde...

Page 7: ...4_ENG Revision 1 000 Page 7 of 31 POWER SUPPLY The devices can be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 8V 24V 12V 35V Consumption at...

Page 8: ...e position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip1 of Dip Switch A at ON position is used for...

Page 9: ...Blinks very slowly 0 5Hz update in progress 2 SNMP communication yellow Blinks when SNMP communication is running Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 3 MQTT status y...

Page 10: ...communication The Ethernet connection must be made using Connector2 of HD67954 B2 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to t...

Page 11: ...verter use the available software that runs with Windows called SW67954 It is downloadable on the site www adfweb com and its operation is described in this document The software works with MS Windows...

Page 12: ...iguration A device s configuration can also be imported or exported To clone the configurations of a Programmable SNMP Agent MQTT Converter in order to configure another device in the same manner it i...

Page 13: ...language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possible to ch...

Page 14: ...SNMP Agent MQTT Document code MN67954_ENG Revision 1 000 Page 14 of 31 In the section Software Settings it is possible to enable disable some keyboard s commands for an easier navigation inside the t...

Page 15: ...ON By Pressing the Set Communication button from the main window for SW67954 Fig 2 the window Set Communication appears Fig 3 The window is divided in different sections in order to define the differe...

Page 16: ...is used for going out of the net In the field SNMP Name of Station the name for SNMP Agent station is defined In the field Contact the contact for SNMP Agent station is defined In the field Location...

Page 17: ...incorrect disconnection or missing ACK they try to send again them since all the ACK messages are exchanged correctly valid only for QoS 1 and QoS 2 If the field Will Flag is checked the converter wil...

Page 18: ...P Address WI FI This section is used to define the general parameters of Wi Fi It is possible to defined the type of Wi Fi communication Access Point Client The means of the fields for Access Point co...

Page 19: ...d The means of the fields for Client configuration are If the field Obtain an IP Address automatically is checked the converter gets the IP Address using DHCP Otherwise the IP Address is defined as st...

Page 20: ...enabled in the field Server Certificate the certificate from the Server is defined If the field Client Authentication is checked the authentication of the Client using TLS is enabled If enabled o in...

Page 21: ...to SNMP MQTT PUBLISH The means of the fields are In the field Topic the MQTT topic is defined If the field Retained is defined the retained flag is enabled The MQTT server will hold the last topic pu...

Page 22: ...the field QoS the QoS level is defined In the field Data Type the type of data to use is defined In the field Dimension the dimension in byte of the data is defined In the field Position the starting...

Page 23: ...TT side change If the field On CMD is checked the OID is sent as Trap when the a MQTT message is received If the field On Timer is checked the OID is sent as Trap cyclically In the field Time ms the d...

Page 24: ...fined For Int type the dimension is in bit for String type the dimension is in bytes In the field Description the description name of the OID is defined In the field Conversion it is possible to selec...

Page 25: ...cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip1 of Di...

Page 26: ...restart the PC Check the LAN settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 or 10 make sure that you have...

Page 27: ...s necessary in order to define the structure of the payload of the MQTT message and the info contained It is possible to have a simple text format or a JSON format The definition of the template can b...

Page 28: ...dustrial Electronic Devices ADFweb com S r l User Manual SNMP Agent MQTT Document code MN67954_ENG Revision 1 000 Page 28 of 31 Figure 8 Mechanical dimensions scheme for HD67954 B2 MECHANICAL DIMENSIO...

Page 29: ...alid combination of the following HD67954 B 2 Connectors Type 2 Fixed Screw Terminal Enclosure Type B Modulbox 2M 35mm DIN Rail mounting Device Family HD67954 SNMP Agent MQTT Converter Order Code HD67...

Page 30: ...systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recyclin...

Page 31: ...he following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to the...

Reviews: