Industrial
Electronic Devices
ADFweb.com S.r.l.
User Manual
Modbus TCP Master / MQTT
Document code: MN67935_ENG Revision 1.001 Page 28 of 37
M
ODBUS
W
RITE
The means of the fields are:
If
the
field
“
Enable
”
is
checked, the Modbus request
is enabled;
In
the
field
“
Slave
IP
Address
” the IP address of
the Modbus TCP device to
read is defined;
In the field “
Port
” the TCP
port
used
for
the
communication is defined;
In the field “
Slave ID
” the
address of the Modbus device
that you have to write is defined;
In the field “
Type
” the data type of the register to write is defined. It is possible to choose between the following:
o
Coil Status;
o
Holding Register.
In the field “
Address
” the start address of the register to be written is defined;
In the field “
NPoint
” the number of consecutive registers to be written is defined;
In the field “
Poll Time
” the delay time to make the request is defined;
If the field “
On Change
” is checked, the converter sends the writing request when the data from MQTT side change value;
If the field “
On CMD
” is checked, the converter sends the writing request when the data from MQTT is received;
In the field “
Max Error
” the number of consecutive errors that the converter waits before suspending the request is defined;
In the field “
Position
” the address of the internal array where taking the information is defined;
In the field “
Start Bit
” the starting bit of the first byte of the field “Position” is defined;
If the field “
Swap
” is checked, the data written the Modbus registers are swapped;
If the field “
Swap Word
” is checked, the Modbus words are swapped;
In the field “
Mnemonic
” the description for the request is defined.
Figure 7b: “Set Access
Modbus Write” window