SET COMMUNICATION:

 

 

 

This  section  define  the  fundamental  communication  parameters  of  HART  and  PROFIBUS 
buses. 
 
By  Pressing  the  “

Set  Communication

”  button  from  the  main  window  for  SW67911  (Fig. 

2) the window “Set Communication” appears (Fig. 3). 
 
The means of the fields for the “HART Master” section are: 

 

In the field “

Address

” the type of Master is defined; 

 

In the field “

Retry Limit

” the maximum number of retries in case of missing 

response from HART device is defined. 

 
The meaning of the fields of “PROFIBUS” are: 

 

In the “

ID Device

” field the PROFIBUS Slave ID is defined; 

 

In  the  “

Baudrate

”  field  the  PROFIBUS  Slave  baudrate  is  defined  (fixed  to  Auto 

Baudrate); 

 

In  the  field  “

Number  Byte  IN

”  the  number  input  bytes  of  PROFIBUS  Slave  is 

defined (max 244 bytes); 

 

In  the  field  “

Number  Byte  OUT

”  the  number  output  bytes  of  PROFIBUS  Slave  is 

defined (max 244 bytes). 

 

The meaning of the fields of “Ethernet” are: 

 

In the field “

IP ADDRESS

” the IP address to assign to the converter is defined; 

 

In the field “

SUBNET

 

Mask

” the SubNet Mask of the converter is defined; 

 

In the field “

GATEWAY

” the default gateway of the network is defined. This feature 

can  be  enabled  or  disabled  pressing  the  Check  Box  field.  This  feature  is  used  for 
going out of the net. 

 
The means of the fields for the “Web Pages” section are: 

 

In the field “

User

” the user name for webserver’s authentication is defined; 

 

In the field “

Password

” the password for webserver’s authentication is defined.

Figure 3: “Set Communication” window 

Summary of Contents for HD67911-A1

Page 1: ...Master to www adfweb com Product HD67900 Serial www adfweb com Product HD67901 BACnet Slave www adfweb com Product HD67902 CAN www adfweb com Product HD67903 CANopen www adfweb com Product HD67904 DeviceNet Slave www adfweb com Product HD67905 Ethernet www adfweb com Product HD67906 EtherNet IP Slave www adfweb com Product HD67907 J1939 www adfweb com Product HD67908 Modbus Slave www adfweb com Pr...

Page 2: ...ARRANTIES AND TECHNICAL SUPPORT 31 RETURN POLICY 31 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To obtain the most recently updated document note the document code that appears at the top right hand corner of each page of this document With this Document Code go to...

Page 3: ...evice can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation of this equipment and who have appropriate qualifications for their job RESIDUAL RISKS The device is state of the art and is safe The instruments can represent a potential hazard if they are inapprop...

Page 4: ...Industrial Electronic Devices ADFweb com S r l User Manual PROFIBUS HART Master Document code MN67911_ENG Revision 1 000 Page 4 of 31 EXAMPLES OF CONNECTION ...

Page 5: ...Industrial Electronic Devices ADFweb com S r l User Manual PROFIBUS HART Master Document code MN67911_ENG Revision 1 000 Page 5 of 31 CONNECTION SCHEME Figure 1 Connection scheme for HD67911 A1 ...

Page 6: ...Supply PROFIBUS HART HART Power Supply Two directional information between Ethernet bus and HART bus Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V DC Wide temperature range 40 C 85 C 40 F 185 F CONFIGURATION You need Compositor SW67912 software on your PC in order to perform the following Define the parameters of PROFINET line Define the parameters of HART line Define...

Page 7: ...911_ENG Revision 1 000 Page 7 of 31 POWER SUPPLY The devices can be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 8V 24V 12V 35V Consumption at 24V DC Device Consumption W VA HD67911 A1 3 5 HD67911 A1 Caution Do not reverse the polarity power ...

Page 8: ...with Dip2 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip2 of Dip Switch A at ON position is used for uploading the Project and or Firmware For the operations to follow for the updating see UPDATE DEVICE section According to the functioning mode the LEDs will have specific functions see LEDS section Warning Dip1 of Dip Switch A must be at ON positio...

Page 9: ...oot state Blinks very slowly 0 5Hz update in progress 2 PROFIBUS communication green It blinks when PROFIBUS communication is running Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 3 Not used green OFF Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 4 Ethernet link green ON Ethernet cable connected OFF Ethernet cable disconnected ON Ethernet cable conne...

Page 10: ...nals at a low level on top of the 4 20mA This enables two way field communication to take place and makes it possible for additional information beyond just the normal process variable to be communicated to from a smart field instrument It is possible to provide the current loop for HART communication and an additional low power supply 24 V DC for feeding HART devices by setting Dip Switch D at ON...

Page 11: ... HART Master Document code MN67911_ENG Revision 1 000 Page 11 of 31 PROFIBUS The PROFIBUS uses a 9 pin D SUB connector The pin assignment is defined like in the right figure Here some codes of cables Belden p n 183079A Continuous Armor DataBus ISA SP 50 PROFIBUS Cable ...

Page 12: ...cation must be made using Connector4 of the HD67911 A1 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to the T568 norms relative to connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recommended the use of a cross cable ...

Page 13: ...runs with Windows called SW67911 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present on our web site The software works with MSWindows XP Vista Seven 8 10 32 64bit When launching the SW67911 the window below appears Fig 2 Note It is necessary to have installed Net Framework 4 Figure 2 Ma...

Page 14: ...s configuration A device s configuration can also be imported or exported To clone the configurations of a programmable PROFIBUS HART Master in order to configure another device in the same manner it is necessary to maintain the folder and all its contents To clone a project in order to obtain a different version of the project it is sufficient to duplicate the project folder with another name and...

Page 15: ...he language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possible to check if there are some updatings of the software compositor in ADFweb com website Checking the option Check Software Update at Start of Program the SW67911 checks automatically if there are updating...

Page 16: ...PROFIBUS HART Master Document code MN67911_ENG Revision 1 000 Page 16 of 31 In the section Software Settings it is possible to enable disable some keyboard s commands for an easier navigation inside the tables contained in the different sections of the software ...

Page 17: ...In the Baudrate field the PROFIBUS Slave baudrate is defined fixed to Auto Baudrate In the field Number Byte IN the number input bytes of PROFIBUS Slave is defined max 244 bytes In the field Number Byte OUT the number output bytes of PROFIBUS Slave is defined max 244 bytes The meaning of the fields of Ethernet are In the field IP ADDRESS the IP address to assign to the converter is defined In the ...

Page 18: ...nable is checked the HART variable is enabled In the field Device Address the address of HART device is defined In the field Preamble Count the number of bytes for the synchronization is defined If the field Type the type of HART parameter is defined In the field Var Cmd Number the identification of variable command to read write is defined From HART standard the most used numbers are o 246 Primar...

Page 19: ...c a description of the variable is defined Note In order to configure the HART devices and their variables it is possible to scan the HART network and get the data automatically It is enough to click on Scan button See page 23 for more info PROFIBUS GSD By pressing the PROFIBUS GSD button it is possible to save the GSD file for the PROFIBUS side With this feature you can save the configuration of ...

Page 20: ...net cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip2 of Dip Switch A in OFF position Turn ON the device If you know the actual IP address of the device you have to use this procedure Turn ON the Device with the Ethernet cable inserted Insert the actual IP...

Page 21: ...program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 or 10 make sure that you have the administrator privileges In case you have to program more than one device using the UDP Update you have to cancel the ARP table every time you connect a new device on Ethernet For do this you have to launch the Command Prompt and write the command arp d ...

Page 22: ...strial Electronic Devices ADFweb com S r l User Manual PROFIBUS HART Master Document code MN67911_ENG Revision 1 000 Page 22 of 31 MECHANICAL DIMENSIONS Figure 7 Mechanical dimensions scheme for HD67911 A1 ...

Page 23: ...iables section It has the following characteristics Possibility to scan HART network Automatic decode of HART messages Easy connection directly through the Ethernet port of the converter In order to start the Scan it is necessary to use this procedure after having set the IP Address inside the converter Connect the converter in Normal Mode to the PC using Ethernet port Open the section HART Variab...

Page 24: ... configured in the converter Start the Scan by clicking on Start Scan button The window will appear like below When the Scan is complete the software will show the results You can import the data by clicking on OK button after having selected the required variables The results will be displayed as below Figure 8b HART Scan window Figure 8c HART Scan window ...

Page 25: ...ke Internet Explorer Google Chrome Mozilla Firefox by editing the IP Address of the converter in the address bar of the browser WELCOME As soon as the connection to the Webserver interface of the Data Logger is done Welcome window appears Fig 9 It has the following structure HART Scan button it is possible to go to the HART scan section where you can discover the connected HART devices HART Contro...

Page 26: ...S HART Master Document code MN67911_ENG Revision 1 000 Page 26 of 31 When one of the buttons of the Welcome page are pressed it is necessary to do the login using the Admin and Password defined in the section Set Communication of SW67911 Fig 10 Figure 10 Login window ...

Page 27: ...n button is pressed the HART Scan window appears Fig 11 It has the following fields NUMBER OF DEVICES TO SEARCH FOR Maximum 16 field number of Hart devices connected Scan Start button it is possible to start the scan of the HART network and discover the devices Read Results button it is possible to read the result of the last HART scan Figure 11 HART Scan window ...

Page 28: ...discovered HART node from HART Scan section is selected the HART Control window appears Fig 12 It has the following fields UNIQUE ID button it is possible to insert the unique ID of the HART device to control POLLING it is possible to insert the new address to assign to the HART device WRITE LONG TAG it is possible to defined the description of the HART device Figure 12 Data Logger Commands window...

Page 29: ...alid combination of the following HD67911 xx Connectors Type 1 Removable 5mm Screw Terminal Enclosure Type A 1M 35mm DIN Rail mounting Device Family HD67911 PROFIBUS HART Master Converter Order Code HD67911 A1 PROFIBUS HART Master Converter ACCESSORIES Order Code AC34011 35mm Rail DIN Power Supply 220 240V AC 50 60Hz 12 V DC Order Code AC34012 35mm Rail DIN Power Supply 220 240V AC 50 60Hz 24 V DC...

Page 30: ...ion systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recycling of electrical and electronic equipment If the product is disposed correctly you will help prevent potential negative environmental factors and impact of human health which could otherwise be cau...

Page 31: ...o the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to the address provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve months it will be repaired or excha...

Reviews: