User Manual
IEC61850 Client / PROFIBUS Slave
Document code: MN67777_ENG Revision 1.000 Page 22 of 28
In the lower part, it is possible to see the variables which belong to the selected Dataset. The meanings of the fields are:
In the field “
bType
” the data format of the IEC61850 variable is defined;
In the field “
Reference
” the path of the IEC61850 variable is defined;
In the field “
Position
” the starting byte of the internal memory arrays where saving/getting the value is defined;
In the field “
Start Bit
” the starting bit of the byte of the field “Position” is defined (only for BOOLEAN data);
In the field “
Conversion
” the type of conversion of the value is defined (only for FLOAT32/FLOAT64 data);
In the field “
Molt Fact
” the multiplication factor for the conversion is defined (if “Conversion” is defined as “ItoF/FtoI”);
In the field “
Mnemonic
”
a description of the variable is defined.
Note:
The variables of a IEC61850 Dataset can only be read.
PROFIBUS GSD:
By pressing the “
PROFIBUS GSD
” button it is possible to save the GSD file for the PROFIBUS side.
With this feature you can save the configuration of the converter of the PROFIBUS side.
Note:
When you import the .gsd file on your Master PROFIBUS it is necessary to add all the modules that are present inside it.