SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, IEC61850
and BACnet.
By Pressing the “
Set Communication
” button from the main window for SW67767
(Fig. 2) the window “Set Communication” appears (Fig. 3).
The means of the fields for “IEC61850 Client” are:
In the fields “
IP Address
” the IP address for IEC61850 side of the converter is
defined;
In the fields “
SubNet
Mask
” the SubNet Mask for IEC61850 side of the
converter is defined;
In the fields “
Gateway
” the default gateway of the net is defined. This feature
can be enabled or disabled pressing the Check Box field. This feature is used for
going out of the net;
In the field "
VLAN
" the identifier for the VLAN is defined;
In the field “
Application ID
” the Goose identification string is defined.
In the section “BACnet Master” it is possible to select the type of BACnet to use from:
BACnet/IP (it uses Ethernet);
BACnet MS/TP (it uses RS485).
If selected “BACnet/IP” the means of the fields for “BACnet” are:
In the fields “
IP ADDRESS
” the IP address of BACnet/IP side of the converter is
defined;
In the fields “
SUBNET
Mask
” the SubNet Mask of BACnet/IP side of the
converter is defined;
In the fields “
GATEWAY
” the default gateway of the network is defined. This
feature can be enabled or disabled pressing the Check Box field. This feature is
used for going out of the net;
Figure 3: “Set Communication” window