Document code: MN674-A006_ENG Revision 1.000 Page 19 of 47
Page 19 of 47
SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, Modbus and PROFINET.
By Pressing the “
Set Communication
” button from the main window of SW674-A006 (Fig. 2) the window
“Set Communication” appears (Fig. 3).
The meaning of the fields of “PROFINET” are:
In the field “
IP ADDRESS
” the IP address of the PROFINET side of the converter is defined;
In the field “
SUBNET
Mask
” the SubNet Mask of the PROFINET side of the converter is defined;
In the field “
GATEWAY
” the default gateway of the network is defined. This feature can be enabled
or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “
Tunneling Port
” the tunneling port used for transparent communication is defined
(see page 28 for more info);
In the field "
PROFINET Name of Station
" the name to the PROFINET side of the converter is
defined;
In the field "
PROFINET -> Gateway
" the number of byte from the PROFINET to the converter is
defined (at maximum it is possible to use 1439 byte);
In the field "
PROFINET <- Gateway
" the number of byte from the converter to the PROFINET is
defined (at maximum it is possible to use 1439 byte);
In the field “
Diagnostic
” the starting byte of the PROFINET array where saving the diagnostic of
Modbus side is defined. It is possible to enable/disable this function using the checkbox.
For more informations about the diagnostic, see page 36;
In the field “
En.
Modbus Polls
” the starting byte of PROFINET array used to enable/disable the
Modbus requests is defined. Each Modbus request is represented by a bit, ‘0’ means ‘Enabled’ and
‘1’ means ‘Disabled’. The requests are mapped from first Modbus reading request to last Modbus
writing request. It is possible to enable/disable this function using the checkbox.
The means of the fields for the “Modbus Master” section are:
In the field “
Serial
” the serial port to use is defined (RS232 or RS485);
In the field “
Baudrate
” the baudrate for the serial line is defined;
In the field “
Parity
” the parity of the serial line is defined;
In the field “
Stop Bits
” the number of Stop Bits of the serial line is defined;
Figure 3: “Set Communication” window