Industrial
Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO:
www.adfweb.com
Phone +39.0438.30.91.31
User Manual
M-Bus / RS232 / RS485
Document code: MN67021_ENG Revision 2.100 Page 17 of 25
UPDATE DEVICE (for HD67021M / HD67022M):
By pressing the “
Update Device
” button it is possible to load the created Configuration into the
device, and also the Firmware if is necessary, using the RS232 port.
In order to load the parameters or update the firmware in the device, follow these instructions:
Turn OFF the Device;
Connect the RS232 cable from your PC to the Converter;
Insert Jumper1;
Select the “
COM port
” and press the “
Connect
” button;
Turn on the device;
Check the “Device state” Led. It must blink quickly (see “LEDS” section);
Press the “
Next
” button;
Select which operations you want to do.
Press the “
Execute update firmware
” button to start the upload;
When all the operations are “OK” turn off the device;
Remove Jumper1;
Disconnect the RS232 cable;
Turn ON the device.
Figure 4: “Update via Serial” windows