Adey MagnaClean CP1-03-01123 Installation And Servicing Download Page 2

 

Installation instructions

MagnaClean

®

 is an incredibly powerful magnetic 

fi ltration range designed to tackle demanding 
light commercial heating systems through to heavy 
industrial applications.

The exceptional design characteristics and 
high quality production of MagnaClean make 
installation and ongoing maintenance extremely 
straightforward.

Correct installation and servicing is essential to 
ensure optimum operating performance and a 
longer operational life for the system.

 

Flexible magnetic 

fi ltration options

MagnaClean’s powerful and proven magnetic 
fi ltration capability and robust design make 
it ideal for the broadest range of commercial 
heating and ventilation systems.

As can be seen in the following diagrams, MagnaClean provides 
a number of installation solutions in terms of unit size and location. 
The typical HVAC system illustrated identifi es two of these options within the various circuits.

   K 

 H1 

 J 

 G 

 H2 

   C 

 A 

 B 

 E 

   L  No. of  M 

 

 D 

D

E

F

C

B

A

3

2

1

5

C

D

4

6

7

8

A

B

D

E

F

C

B

A

3

2

1

5

C

D

4

6

7

8

A

B

Drawn

Unless Otherwise Stated: 

0 - ±0.5  

0.X - ±0.2 

0.XX - ±0.1

angular tols. ±0.1°

Size:

Rev

Scale:

COMMERCIAL FILTER 

GENERIC SIZE 

INFORMATION

Title:

DWG NO.

NTS

1 of 1

A3

Material:

Finish:

Checked By

Date:

Phone: +44 (0)1242 546700   

Email: [email protected]

This drawing remains the property of

ADEY Ltd. and must not be 

copied or passed to a third party 

without written permission.

Adey Ltd.

Gloucester Road

Cheltenham

GL51 8NR

Change No

Change No

Drawn

Date:

Checked By

Rev

Drawn

Rev

Checked By

Date:

Change No

Sheet:

Professional Heating Solutions

E

F

Tolerances

For chiller systems, it is recommended that a MagnaClean is installed on the return of the system before the chiller.

 

Step by step guide to installation

Follow the illustrations and measurements for easy installation of MagnaClean. There are four key steps to 
successful installation:

Step 1 

Use the measurements table to identify the correct length of pipework to be cut-out, allowing for your 
isolation valves (refer to measurement A). We recommend installing on the primary circuits on the return to 
the boiler. Ensure to leave enough room above the MagnaClean to access and remove the magnets easily 
during servicing.

Step 2 

Install the isolation valves and connect the two PN16 fl anges to the isolation valves.

Step 3 

Install MagnaClean, ensuring that all fi ttings are aligned correctly and secure, integral lifting eyes are 
provided for safe working practice. Install a fi xed drainage pipe and drain valve to the 1¼” BSPP drain point 
at the base of the unit. Alternatively, remove the drain plug and connect to a drain hose when servicing.

Step 4 

Having checked the installation, run the system for a period of time. Ensure the isolation valves are fully open 
and there are no leaks.

ADEY product 

code

Description

Filter 

diameter 

(mm)

Inlet 

size 

(mm)

No. of 

magnetic 

rods

Measurement (mm)

A

B

ØC

ØD

ØE

F

G

H1

H2

J

ØK

L

M

CP1-03-01123

2’’ fi lter

160

50

5

262

18

245

165

60

125

51

291

253

-9.5

160

18

4

CP1-03-01124

3’’ fi lter

210

80

6

330

15

295

200

92

160

60

331

278

2.5

210

18

8

CP1-03-01125

4’’ fi lter

216

100

7

360

15

299

220

113

180

72

347

303

15.5 216

18

8

CP1-03-01126

6’’ fi lter

324

150

9

470

18

430

285

164

240

73

446

333

2

324

22

8

 

Measurements table

Installation with a 

Low loss header

Installation with Cascade (zoned) system

* Postition A is the recommended best practise installation option. Position B could be added in as an  
   option to further protect the system.

Installation with a 

Plate to plate

Pressure differential fl ow

A

B

B

N.B. Flow analysis created with CFD

For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - [email protected] 0844 556 1818   