Page 11
Table 1: gas categories and pressure values
COUNTRY
APPLIANCE
CATEGORY
GAS
RATED PRESSURE
(mbar)
MINIMUM
PRESSUR
E
(mbar)
MAXIMUM
PRESSURE
(mbar)
IT GB BE
CH CY CZ
CZ ES FR
LT SK PT
IE GR
I3+
G30 29
25
35
G31 37
25
45
AT BE DE
IT CH NO
PT ES SE
I2H
G2
20
17
25
DE GR AT
CH SI
I3B/P
G30
50
42.5
57.5
BE FR LU
I2E
G20
20
17
25
The appliance should be connected to the gas supply by means of metal pipes --either rigid or flexible-- having an adequate diameter.
When joining pipe fittings, never use oakum or Teflon as their residues could get into the valve and jeopardize its operation. Instead,
interpose a seal gasket suitable for using in gas systems. Do not forget to fit a shutoff valve on the gas supply line upstream of the
appliance, which should be closed whenever the appliance is not in operation.
After connecting the appliance to the gas system, check for leaks at joints and pipe fittings; to do so, use soapy water or a specific leak
detector (spray).
4.11 Checking gas supply pressure after installation
Gas supply pressure can be measured with a liquid-filled pressure gauge (for example, a U-shaped pressure gauge, minimum scale
division 0.1 mbar) or a digital gauge. Proceed as follows:
Remove the left grate, burners, and drip pan;
Unscrew the screw on the pressure port
Place the pressure gauge;
Start up the appliance by following the instructions in the user’s manual;
Check supply pressure;
If the measured pressure value is within the range shown in
"Table 1: gas categories and pressure values"
, the appliance can be
started up. Otherwise, contact the gas utility company.
Remove the pressure gauge;
Replace the sealing screw;
Check for leaks.