Adesys SVA Manual Download Page 7

Page 7

Manual SVA alarm dialler | Back to 

Index

Adesys B.V. | Wateringen

2.8.  2G/4G connection

To use the SVA with a 2G/4G connection, a SIM card with Internet subscription should be installed in the 

SVA. It is important that the correct APN, APN user and APN password are entered, otherwise the SVA will 

not be able to connect. This can be entered in SV-prog in the 2G/4G window.

Network locking is possible. By entering a 2 or 4 in the GSM menu at the provider lock, it is possible to lock 

the detector to 2G or 4G.

The SVA does not provide a notification if something goes wrong with the APN. For more information 

about the APN, please contact your provider.

2.9. 

Inputs and outputs 

It is possible to connect several variants of inputs and outputs to the SVA, such as contact inputs , voltage 

inputs DC or a relay output. When connecting different inputs it is important to look carefully at the wiring 

diagram. This can be found on the side of the SVA.

3.  SV-prog 

3.1. 

Installation 

Setting up the SVA can be done in two ways, the fully adjustable way of the SV-prog tool and a limited 

adjustable way via Remote Setup. For Remote Setup, section 

“3.5.1. Checkmyproces.com”  can be 

consulted.

SV-prog is used to set up the SV series. This program can be downloaded free of charge from the Adésys 

website (www.adesys.nl/en/service/downloads

). All settings will be stored in the internal flash memory. It 

is 

not

 possible to store the settings on the SIM card!

SV-prog must be installed on your PC before it can be used. Follow the instructions displayed on your 

screen during the installation process. As soon as the installation process is complete, start the program 

via the shortcut or via the program menu in MS Windows. 

Connect the SVA to a power source and connect the SVA to the PC using the Ethernet cable set supplied. 

The SVA can be connected to the local network or directly to the PC.

As soon as the SVA has been switched on, the tool will display this in the overview after a few seconds 

and the SVA can be configured by clicking it. When search diallers is pressed, SV-prog shows all accessible 

diallers.

When SV-prog is not showing any diallers or when the error message ‘No ethernet cable’ is shown. There 

is a possibility the wrong network adapter is chosen. By opening SV-prog and opening the configuration 

on the top left side it is possible to adjust the network adapter.

Terms used

The terms you will encounter in SV-prog are explained below.

3.2. 

Status screen

The status screen provides you with information on the SVA. Examples of this information are the IMEI 

code, the serial number, the MAC address and the current status of the inputs and alarms/errors.

3.3. 

Call list

A call list is a group of contacts (SMS or Email) that can be coupled to the input to send an alarm message 

or alarm recovery message. One to eight contacts can be programmed into a call list

3.4.  I/O

Inputs are displayed in this window. All inputs can be set up separately from one another. Settings can 

also be established here for 

Mains Power Failure

 and 

System Errors

.

One call list can be set up for each input. As soon as an input becomes active, the notification procedure 

starts. The associated alarm message is sent to all set telephone numbers one after the other. This is 

explained further in the Notification Procedure section.

Summary of Contents for SVA

Page 1: ...MEASURING ALERTING CONNECTING EN Manual SVA Version 02 2021 ...

Page 2: ...y 6 2 7 Ethernet 6 2 8 2G 4G connection 7 2 9 Inputs and outputs 7 3 SV prog 7 3 1 Installation 7 3 2 Status screen 7 3 3 Call list 7 3 4 I O 7 3 4 1 Input delay 8 3 4 2 Recovery report idle 8 3 4 3 System errors 8 3 5 Connections 8 3 5 1 Checkmyproces com 8 3 5 2 Own server 8 3 6 System 8 3 6 1 Device 8 3 6 2 Ethernet 8 3 6 3 GSM and mobile data 8 3 6 4 Factory reset 9 4 Notification procedure 9 ...

Page 3: ...e placed in an environment protected against electrostatic discharge ESD The SVA is intended for use as a modem or alarm dialler The SVA is not intended for use as part of a critical safety system in a critical process 1 4 Checking the delivery Check the packaging for damage Contact your supplier immediately if the delivery is found to be damaged or incomplete upon receipt The standard delivery in...

Page 4: ...vent damage You should therefore discuss the remaining risk with your insurer 1 8 Identification Figure 1 Identification SVA 1 2 3 4 5 6 7 8 9 10 1 Reset button 2 LED status indicator general status on busy antenna level network error messages error 3 Antenna connection type SMA female 4 SIM card holder 5 Ethernet connection 6 Information sticker 7 Input output connection terminals 8 Supply voltag...

Page 5: ...the SVA onto the DIN rail at an angle 1 It is important that the SVA s DIN rail clip is positioned on the top of the DIN rail Tilt the SVA to clip it into place 2 Then check whether it is securely seated The SVA is removed from a DIN rail as follows Place a screwdriver on the underside of the DIN rail clip 3 Use this as a lever after approx 3 mm the SVA can be tilted to release it from the DIN rai...

Page 6: ...nected internally to the GND connection of the input connector and the COM port If the SVA is connected to an application process controller PLC computer active sensor etc without galvanic isolation and the SVA is connected to the same power supply there is a real chance of earth loops and or short circuits in this power supply 2 6 Reset key The reset key has four functions first of all it is used...

Page 7: ...ing the installation process As soon as the installation process is complete start the program via the shortcut or via the program menu in MS Windows Connect the SVA to a power source and connect the SVA to the PC using the Ethernet cable set supplied The SVA can be connected to the local network or directly to the PC As soon as the SVA has been switched on the tool will display this in the overvi...

Page 8: ...reen and by looking on the side of de dialler Remote configuration It is possible to remotely make changes to the settings of the dialler This is possible by ethernet and by 4G GPRS For using remote configuration it is necessary to have a constant connection When using 4G GPRS keep in mind of the extra cost If the network is secured by use of a firewall Please make the following exceptions Data co...

Page 9: ...ation into an Email message and sends this to the Email address that has been entered The structure of the message is the same as the SMS 4 2 Notification of status changes After input channel 1 has been activated the following can be observed The green LED on busy flashes 1x to indicate that input channel 1 is active After a few seconds the green LED on busy flashes faster to indicate that the SM...

Page 10: ... SMS message The SMS message should be structured as follows Command parameter1 parameter2 Command O Output Parameter1 A Active or I Idle or P switch Pulse default 2 seconds active Parameter2 I O number The output number is not the same as the relay number Relay number 1 is output 5 Figure 3 Connectsticker Example SMS message to relay 1 Output 5 active OA5 Output 5 Idle OI5 Output 5 with default P...

Page 11: ...ched off On SVA is switched on Faster Starting up sending message 1x Input 1 active 2x Input 2 active 3x Input 3 active 4x Input 4 active 5x Input 5 active 6x Input 6 active 7x Input 7 active 8x Input 8 active 7 2 Technical specifications Systeemeigenschappen SVA0000 I Type of detector alarm dialler Weblogger modem Number of digital inputs Number of GPIO inputs Number of PT100 inputs Number of rel...

Page 12: ...tes so that a power failure can still be reported Expected service life Calculated MTBF 88167 hours 10 years according to componentcounting method Enclosure and operating conditions Enclosure DIN rail TS35 mounting enclosure fire retardant UL94 V0 Dimmensions W x H x D 23 x 95 x 102 mm Weight 125gr Operating temperature 20 C 50 C Air humidity 20 85 not condensed IP code IP10 Maximum heigth Up to 2...

Page 13: ... Also available in this SV product line SVL Weblogger SVM 4G modem Checkmyprocess com Industrial 4G Weblogger for sending alerts in relation to limit values being exceeded Industrial 4G modem sms alarm dialler for connection to applications in the field Convenient display of current measured values from your process Version 02 2021 ...

Reviews: