Adesys SVA Manual Download Page 6

Page 6

Manual SVA alarm dialler | Back to 

Index

Adesys B.V. | Wateringen

The use of a ‘Prepaid’ SIM card for dialling purposes is strongly discouraged. The mobile network cannot 

automatically request the call credit, which means that this can be run down without anyone noticing, 

resulting in outgoing notifications coming to a standstill.

2.4. 

Antenna

Connect the antenna cable to the SVA’s antenna connection. The antenna plus associated cable can be 

obtained from Adésys. The antenna should be affixed to as high a point as possible to obtain the best 

possible range.

After installation, always check the field strength of the antenna signal (max. is 5 flashes of the yellow 

‘network’ LED). Notification of changes in signal strength will always take place after a long delay (± 30 

seconds). Take this into account if, for example, the antenna is moved.

2.5.  Power supply

2.5.1. 

SV-20 mains adapter and SV-19 DIN rail power supply

To power the SVA, a 230VAC / 24VDC mains adapter with article number SV-20 or a 100-240VAC / 24VDC 

DIN rail mounting power supply with article SV-19 can be ordered as an option via the webshop. 

When fitting the terminal block to the power supply cable, ensure that the polarity plus (+) and minus (-) is 

correct.

 

An extra power supply fuse is not necessary here.

If the SVA is not supplied with power using the above-mentioned mains adapter or DIN rail power supply, 

the connection regulations in the section below apply.

2.5.2. Power supply

Connect the SVA to a DC power supply of 15 to 35VDC (at least 8.5 W) or a transformer of 20 to 30VAC. 

The power supply input of the SVA is not galvanically isolated from the other connections. The GND 

connection of the power supply connector is directly connected internally to the GND connection of the 

input connector and the COM port.

If the SVA is connected to an application (process controller, PLC, computer, active sensor, etc.) without 

galvanic isolation and the SVA is connected to the same power supply, there is a real chance of earth loops 

and/or short circuits in this power supply.

2.6.  Reset key

The reset key has four functions: first of all, it is used to interrupt the alarm. Pressing this briefly ends the 

current notification; the SMS messages that have not yet been sent are not sent.

A second function of the reset key is to restart the dialler. The dialler can be restarted by holding this key 

down for a period of 8 seconds. This only occurs if a power supply is connected.

If no power supply is connected, the reset key functions as an off button. Holding the key down for a 

period of 8 seconds switches off the dialler.

Statuses of inputs will 

not 

be stored in a permanent memory. If the supply voltage fails, and the built-in 

supercap is entirely discharged, the contents of this memory is lost. If the SVA is restarted manually, this 

status will also be reset. When the supply voltage is restored, the SVA behaves as if it is being started up 

for the first time. This means that:

•  After the supply voltage has been restored, only active inputs are reported once again;

•  No recovery message will be sent if the status of the input has been recovered during this power failure. 

The fourth functionality is for when there is something wrong and there seem to be no connection. By 

pushing the reset key for a duration of 3 seconds, releasing it 3 seconds and doing this 3 times the DHCP 

will be enabled. By enabling the DHCP it is possible to make changes with SV-prog.

2.7.  Ethernet

The Ethernet connection can be used for an external connection. This is set up in the SVA: see chapter 

“3. 

SV-prog”. By default this is set up to connect to Checkmyproces.com.

Summary of Contents for SVA

Page 1: ...MEASURING ALERTING CONNECTING EN Manual SVA Version 02 2021 ...

Page 2: ...y 6 2 7 Ethernet 6 2 8 2G 4G connection 7 2 9 Inputs and outputs 7 3 SV prog 7 3 1 Installation 7 3 2 Status screen 7 3 3 Call list 7 3 4 I O 7 3 4 1 Input delay 8 3 4 2 Recovery report idle 8 3 4 3 System errors 8 3 5 Connections 8 3 5 1 Checkmyproces com 8 3 5 2 Own server 8 3 6 System 8 3 6 1 Device 8 3 6 2 Ethernet 8 3 6 3 GSM and mobile data 8 3 6 4 Factory reset 9 4 Notification procedure 9 ...

Page 3: ...e placed in an environment protected against electrostatic discharge ESD The SVA is intended for use as a modem or alarm dialler The SVA is not intended for use as part of a critical safety system in a critical process 1 4 Checking the delivery Check the packaging for damage Contact your supplier immediately if the delivery is found to be damaged or incomplete upon receipt The standard delivery in...

Page 4: ...vent damage You should therefore discuss the remaining risk with your insurer 1 8 Identification Figure 1 Identification SVA 1 2 3 4 5 6 7 8 9 10 1 Reset button 2 LED status indicator general status on busy antenna level network error messages error 3 Antenna connection type SMA female 4 SIM card holder 5 Ethernet connection 6 Information sticker 7 Input output connection terminals 8 Supply voltag...

Page 5: ...the SVA onto the DIN rail at an angle 1 It is important that the SVA s DIN rail clip is positioned on the top of the DIN rail Tilt the SVA to clip it into place 2 Then check whether it is securely seated The SVA is removed from a DIN rail as follows Place a screwdriver on the underside of the DIN rail clip 3 Use this as a lever after approx 3 mm the SVA can be tilted to release it from the DIN rai...

Page 6: ...nected internally to the GND connection of the input connector and the COM port If the SVA is connected to an application process controller PLC computer active sensor etc without galvanic isolation and the SVA is connected to the same power supply there is a real chance of earth loops and or short circuits in this power supply 2 6 Reset key The reset key has four functions first of all it is used...

Page 7: ...ing the installation process As soon as the installation process is complete start the program via the shortcut or via the program menu in MS Windows Connect the SVA to a power source and connect the SVA to the PC using the Ethernet cable set supplied The SVA can be connected to the local network or directly to the PC As soon as the SVA has been switched on the tool will display this in the overvi...

Page 8: ...reen and by looking on the side of de dialler Remote configuration It is possible to remotely make changes to the settings of the dialler This is possible by ethernet and by 4G GPRS For using remote configuration it is necessary to have a constant connection When using 4G GPRS keep in mind of the extra cost If the network is secured by use of a firewall Please make the following exceptions Data co...

Page 9: ...ation into an Email message and sends this to the Email address that has been entered The structure of the message is the same as the SMS 4 2 Notification of status changes After input channel 1 has been activated the following can be observed The green LED on busy flashes 1x to indicate that input channel 1 is active After a few seconds the green LED on busy flashes faster to indicate that the SM...

Page 10: ... SMS message The SMS message should be structured as follows Command parameter1 parameter2 Command O Output Parameter1 A Active or I Idle or P switch Pulse default 2 seconds active Parameter2 I O number The output number is not the same as the relay number Relay number 1 is output 5 Figure 3 Connectsticker Example SMS message to relay 1 Output 5 active OA5 Output 5 Idle OI5 Output 5 with default P...

Page 11: ...ched off On SVA is switched on Faster Starting up sending message 1x Input 1 active 2x Input 2 active 3x Input 3 active 4x Input 4 active 5x Input 5 active 6x Input 6 active 7x Input 7 active 8x Input 8 active 7 2 Technical specifications Systeemeigenschappen SVA0000 I Type of detector alarm dialler Weblogger modem Number of digital inputs Number of GPIO inputs Number of PT100 inputs Number of rel...

Page 12: ...tes so that a power failure can still be reported Expected service life Calculated MTBF 88167 hours 10 years according to componentcounting method Enclosure and operating conditions Enclosure DIN rail TS35 mounting enclosure fire retardant UL94 V0 Dimmensions W x H x D 23 x 95 x 102 mm Weight 125gr Operating temperature 20 C 50 C Air humidity 20 85 not condensed IP code IP10 Maximum heigth Up to 2...

Page 13: ... Also available in this SV product line SVL Weblogger SVM 4G modem Checkmyprocess com Industrial 4G Weblogger for sending alerts in relation to limit values being exceeded Industrial 4G modem sms alarm dialler for connection to applications in the field Convenient display of current measured values from your process Version 02 2021 ...

Reviews: