– 34 –
8/5HTXLUHPHQWV
Below is a list of UL requirements that must be met for UL installations.
NOTE: The 7835C is not UL Listed for fire alarm service. For fire, the 7835CF can be used as the backup dialer. 7835CF is
not approved for use as the primary fire dialer.
1.
There are no UL Listed siren drivers available for commercial burglar alarm use.
2.
When the 7835C is set for Zone Mode operation on a UL commercial burglar alarm installation, all interconnecting
wiring between the control unit and the 7835C must be no more than 3 feet in length and contained within the same
room. All interconnecting wiring must be installed in rigid conduit or EMT (where exposed on interior walls) or in
flexible metal tubing if run in the walls or ceiling.
3.
The wiring method shown in Figure 11 (page 23) is required on UL installations. The Low Current Mode may not be
used on UL installations.
4.
For all modes of operation, commercial burglar alarm installations must be in accordance with the National Electrical
Code and UL681, Installation and Classification of Burglar and Hold-Up Alarm Systems.
5.
For all modes of operation, residential burglar alarm installations must be in accordance with the National Electrical
Code and UL1641, Installation and Classification of Residential Burglar Alarm Systems.
6.
For Zone Mode operation, the 7835C must be connected to either dry contacts or voltage trigger outputs of a Listed
compatible control unit.
7.
For ECP Mode, the 7835C must be connected to a Listed compatible ECP capable control unit.
8.
The antenna (and thereby the 7835C) may be mounted remotely from the control panel when ECP mode is used.
9.
The 7835C must be programmed as follows:
a.
The 7835C must be registered as described in the Installation Instructions.
b.
Zones must be programmed “No” for “Pulsed” and “00” for “Delay” (Questions 9-14)
c.
Enable restoral signals (Questions 21-26).
d.
At least one zone must be set to provide opening and closing signals (Question 28).
e.
At least one zone must be programmed to provide Telco Channel monitoring (Question 29).
f.
Either zone 7 or 8 must be enabled as the Tamper zone (Question 30).
g.
The Old Alarm Time must be set to 10 minutes (Question 31)
h.
AC Loss Report must be enabled (Question 32).
i.
Bat Present must be enabled (Question 33).
j.
Fault Relay On must be enabled (Question 34).
k.
24 Hour Supervision must be enabled (Question 5).
Summary of Contents for AlarmNet 7835C
Page 35: ...35 127 6...