– 24 –
Question 5
CS ID
Enter the primary central station’s system ID number, 1-7F
Question 6
Channel#
Enter the AlarmNet channel number, 1-14
Question 7
HS Ant. Tst (Y/N)
Press Y for 135 second interval antenna test. Press N if no antenna
test is desired.
Question 8
AC Loss RPT (Y/N)
If AC LOSS RPT is answered yes (Y), the radio will report the loss of
AC voltage within a 10 to 40 minute window, from its detection. If
this feature is disabled (N), this message will be suppressed. NOTE:
In either case, low battery messages will be sent as detected.
Question 9
USE RADIO # (Y/N)
If Y is selected, the Radio ID number will replace the panel Subscriber
ID in panel-generated messages.
If N is selected, the radio will send panel-generated messages with the
panel Subscriber ID number.
Question 10
2
nd
CS ID
This must be programmed with a value, even if it is the same as the
primary central station. The control panel has the option to send a
selected message to the second central station.
Question 11
REVIEW?
Press “Y” to review the programming options and to ensure that the
correct responses have been made. Parameters can be changed during
review. Press “N” to end programming session.