ADEMCO 5881L - Ademco 8 Zone Wireless Receiver Installation Instructions Manual Download Page 2

2

h. Do the same with the other ground lug and antenna

block.

i.

Insert the receiver’s two antennas through the two
openings in the top of the cabinet, one into each block’s
right-hand terminal, and tighten the screws to secure
them.

j.

Affix the receiver's Summary of Connections label to the
inside of the control's cabinet door.

k. Discard the receiver's unused plastic cover and base.

3. If the receiver is to be located remotely from the

control in its own plastic enclosure (not in a cabinet):
The circuit board mounting clips, grounding lugs and screws
included with the receiver will not be needed.

a. If concealed wiring is to be used, route it through the

rectangular opening at the rear of the base before
mounting.  For surface wiring entry, a thin breakaway
area is provided along the base's right edge.

b. Mount the receiver in the selected location. For greatest

security, use all four mounting holes (two keyslot holes
and two round holes) provided in the plastic base.

c

Affix the receiver's Summary of Connections label to the
inside of the housing cover.

4. Mounting the 5881EH in a Separate Cabinet For

Commercial Fire  Applications.
For commercial fire applications, the 5881EH must be
mounted in a separate cabinet,  part # N4868V4–BE, using
the Ademco Cam Lock, Part #N6277, and Retainer Clip,
Part # N6277–1.  Refer to the control’s instructions for
installing the Cam Lock and Retainer Clip in a cabinet.
The cabinet containing the receiver must be located no
farther than 20 feet from the alarm control cabinet., with no
intervening walls or barriers):

a. Remove the receiver's cover by inserting and twisting a

screwdriver blade in the slot at the center of the cover's
lower edge.

b. Remove the receiver's circuit board from its base by

bending back the two flexible plastic tabs that hold the
board's lower edge.

c. Mount the receiver board in the cabinet as follows:

Insert the top of the receiver board into the supporting
slots provided at the top of the cabinet (see Diagram 1
and Detail A which show how the top of the receiver
board is secured).
Secure the bottom of the receiver board with 2 screws
(not supplied) using an insulating washer between the
head of each mounting screw and the PC board.

d. Affix the receiver's Summary of Connections label to the

inside of the cabinet door.

e. Discard the receiver's unused plastic cover and base.

5. Setting The DIP switches (All Receivers):

Set the receiver's DIP switch to identify the receiver's
address (refer to the DIP switch chart in Diagram 2).

5881EH Only:

DIP switch #5 is used on the 5881EH, as follows:

For commercial fire applications, DIP switch #5 MUST be
in the ON position.
Note:  All other system components, including the

control, must be approved for use in commercial
fire applications.

When the 5881EH is not used in a commercial fire
application, switch #5 should be placed in the OFF
position.

6. Insert the wiring plug (with 4 flying leads) into the

mating socket on the receiver  (see Diagram 2 for socket
location). Connect the  4 wires to the control's corresponding
remote keypad connection points (see “Interface Wiring” in
the 

SPECIFICATIONS section).

7. Install the antennas  in the 

right-hand terminals of the two

terminal blocks at the upper edge of the circuit board, one
into each block’s right-hand terminal, and tighten the screws
to secure them.
If the receiver is mounted in a cabinet, insert the antennas
through the holes in the cabinet's top first, and then into the
terminal blocks.
Important!  If the receiver is mounted in a separate cabinet
in a commercial fire installation do not use the antenna
grounding lugs.

8. Replace the receiver's cover if the receiver is not mounted

within a cabinet.

9. Proceed with any programming of the control that may

be necessary for RF operation, and the installation of
the system's wire less transmitters, 
as described in the
QED control's installation in structions.

10. The LED located on the receiver's circuit board  should

be used as an indicator of strong local radio frequency
interference. If this LED is continuously illuminated, the
receiver should be relocated.

SPECIFICATIONS

Dimensions:

7-3/8" W x 4-3/8" (10-7/8” w/antennas) H x  1-7/16" D.
188mm W x 112mm H (277mm w/antennas) x  37mm D.

Input Voltage:

12VDC (from QED control’s remote keypad terminals).

Current:

4281/4281CN: 35mA.  5881/5882: 60mA.

Interface Wiring:

RED

12VDC input (+) Aux Power

GREEN:

Data Out to Control

YELLOW:

Data In from Control

BLACK:

Ground (–)

Operating Temperature:

0-50

°

C

Range:

200ft (60m) nominal indoors from wireless transmitters
(the actual range to be determined with the security
system in the TEST mode).

TO THE INSTALLER

Regular maintenance and inspection (at least annually) by the installer and frequent testing
by the user are vital to con tinuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular
maintenance program to the user, as well as ac quainting the user with the proper op eration
and limitations of the alarm system and its component parts. Recommendations must be
included for a specific program of frequent testing (at least weekly) to insure the system's
operation at all times.

Summary of Contents for 5881L - Ademco 8 Zone Wireless Receiver

Page 1: ...h it is used See the QED control panel s instructions for specific details If a receiver is connected to a system in which more than the permitted number of wireless zones have been programmed a SET U...

Page 2: ...IP switch chart in Diagram 2 5881EH Only DIP switch 5 is used on the 5881EH as follows For commercial fire applications DIP switch 5 MUST be in the ON position Note All other system components includi...

Page 3: ...ng an indoor antenna have a quality outdoor antenna installed Reorient the receiving antenna until interference is reduced or eliminated Move the radio or television receiver away from the receiver co...

Page 4: ...UCTIONS INTERFERENCE INDICATOR LED CIRCUIT BOARD DIP SWITCH PLUG SOCKET INSERT IN RIGHT HAND TERMINALS ANTENNAS MODEL No IS INDICATED ON CIRCUIT BOARD YELLOW RED BLACK GREEN TO CONTROL S REMOTE KEYPAD...

Page 5: ...beams They cannot detect motion or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of an...

Page 6: ...O ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY...

Page 7: ...7 ALARM DEVICE MANUFACTURING CO A DIVISION OF PITTWAY CORPORATION 165 Eileen Way Syosset New York 11791 Copyright 1994 PITTWAY CORPORATION N7635V2 10 96...

Reviews: