ADEMCO 4208U Installation And Setup Manual Download Page 3

 

3

 

Set the DIP switches on the 4208U as instructed below (see 
Figure 1):   

1.  Select fast/slow response for loops A and B using DIP 

Switch 1:  Fast = OFF (10msec) Slow = ON (400msec).   

2.  Select mode of operation (serial number or zone 

assignment mode) using DIP Switch 6:  Serial Number 
mode = ON Zone Assignment mode = OFF.   

3.  Select the group setting using DIP Switches 2, 3, 4, and 

5.  See Table 1 for zone assignments or Table 2 for 
serial number assignments.  If using more than one 
4208U, be sure to set each one to a different group 
setting.   

4.  DIP Switch 7:  Not used, set to OFF.   

5.  Select the 4208U Tamper Protection setting using DIP 

Switch 8:  Tamper Disabled = ON Tamper Enabled = 
OFF.  Tamper will report for every active zone on the 
4208U module.   

PROGRAMMING 

When setting the 4208U to a group of zone numbers, each 
zone must be programmed as follows:   

• 

On 4140XMP and earlier controls, these zones must be 
programmed as Left Loop Polling Loop Zones.   

• 

On VISTA-40 and later controls, these zones must be 
programmed in the #93 Menu Mode Zone Programming 
as INPUT TYPE “7” -- DIP Switch type polling device 
(DP).   

When setting the 4208U to a group of serial numbers, each 
zone must be programmed as INPUT TYPE “6” --SL (Serial 
Number Polling Loop Device).  Loops can be learned in any 
order and assigned to any legitimate zone number.   

When prompted to learn the serial number for a particular 
zone, you may either enter it manually through the keypad 
or through V-Link, or “learn” it by momentarily faulting 
(shorting) the terminals of that zone as required by the 
control.  If entering a serial number manually through the 
keypad, enter it and press “*” to advance to the next 
prompt, which will ask you for the loop number.  Entering a 
“1” for each serial number entered.   

If learning or entering a serial number, “Duplicate of Zone 
XX” 

Duplicate of Zone XX” is displayed; another device with that 
same serial number is already in the system.  In that case, 
use a different serial number group setting on the 4208U.   

 

 

If learning a serial number by faulting 
its associated loop, make sure that 
other polling loop devices are not 
activated, as they may interfere with 
the device being learned.  
 

VERIFICATION OF PROGRAMMING 

To verify proper programming, the following test should be 
performed:   

1.  Be sure to enable expansion zone tamper protection at 

the control (program field *24 = 0). 

2.  Set DIP Switch 8 to OFF (tamper enabled).   

3.  Replace the 4208U cover and clear the keypad of any 

faulted zones.   

4.  Remove the 4208U’s cover and verify (on the keypad) 

that only the zones you designated for this 4208U are 
indicating a check (or trouble) condition.   

Table 3.  Current Draw Calculations 

Power Input Source 

(Input Voltage:  11 – 14VDC) 

Current Draw 

(All zones shorted) 

 

From Polling Loop 

From External Power 

Polling Loop Only 

27.3 mA 

 

Polling Loop and External 

Power Input 

0.6 

mA 28 

mA 

 

SPECIFICATIONS 

Physical: 

Width:  6-7/16”(163mm) 

Height:  4-1/4” (108mm) 

Depth:  1-1/4” (32mm) 

Electrical: 

Polling loop input:  7.3 – 14 VDC 

Current draw:  28.6mA max. External power and polling loop 
(see Table 3) 

External Power Input (optional): 

12VDC @ 28mA (from control panel’s auxiliary power) 

Sensor Loop Response: 

Slow:  400 msec (all loops) 

Fast:  10 msec (option for loops A and B) 

Sensor Loop Current:   

(@ Polling loop input = 11 VDC, no external power input): 

0.52mA (normal) 

1.3mA (shorted) 

Sensor Loop Max. Resistance:   

Up to 300 ohms of wire resi 10k EOLR.   

For UL Listed Commercial Fire Usage

Use N.O. contacts.  Style B supervise these loops using Model # EOL 100 fire listed 
10k EOLRs (purchased separately).   

For UL Listed Commercial Burglary Usage:   

Use N.O. or N.C. contacts.  Supervise using EOLRs supplied.   

Reviews: