N.B Make sure that once the extractor is installed there is no accidental access to the moving parts.

Flexible

ducting

Mixflo fan

screwed to joist

External

grey grille

Internal White

Grille

Electrical Connections

1.  The extractor fan must be connected to a single phase mains network, 220 - 240VAC.
2.  The installation must have an omnipolar switch with a contact separation of at least 3mm. The circuit 

must be protected by a 3 Amp fuse. 

3.  Earthing is not required as this extractor is a class II insulated appliance.
4.  The extractor must be connected permanently to a fixed installation cable secured in fixed 

channelling. (Flex of two conductor wires of minimum section 1mm

2

 and maximum 1.5mm

2

To make the Electrical Connections

5.  Loosen the 4 screws (A) and take off the connection cover 
6.  Perforate the flex holder (B) to allow the power supply wires to pass through.
7.  Make the connections as indicated on the next page.

B

A

Body can be rotated to accomodate tight spaces.