background image

 

 

 

AddSecure Tor V, PDK-11606 

14 

6.10

 

Analogue dialler 

The alarm transmitter acts as a switchboard and picks up automatically when the control panel 
dials using the modem’s output. If the control panel sends information in SIA format or 
Contact ID (CiD), it is read and then forwarded to the connected alarm center. For this to 
happen, you need to have ordered the plain text SIA service or Contact ID. The control panel 
is to be programmed with an optional telephone number, consisting of six (6) digits.  

 

Connecting the control panel with an analogue dialler is done with the tele 
terminal pair; see Figure 12. The number of the pin is not important. 

Transferring alarms through the control panel’s telephone connection 
(PSTN) is also called dial-capture. With this service, the alarm transmitter 
acts as an analogue telephone network, which it simulates by: 

 

Producing line voltage (approx. 30 volt). 

 

Generating a dial tone when the connected control panel picks up the receiver. 

 

Receiving DTMF signals from the control panel (number dialing). 

  

The next step in receiving a SIA or Contact ID message that the control panel transmits 
through its telephone connection is for the alarm transmitter to simulate an alarm receiver. 

It does this by sending and receiving the signal that the SIA or Contact ID protocol uses. In 
this way, the alarm transmitter receives and acknowledges messages that the control panel sends 
through its telephone connection. After the transmission from the control panel is complete, 
the message is stored in the alarm transmitter and is forwarded through AddSecure’s system to a 
preset alarm receiver. The alarm transmitter deletes the locally stored messages when the system 
acknowledges that the messages have been forwarded on. 

Note that dialler interface is only for additional information. You must use 
the input interfaces to follow the regulations (EN 54-21:2006, EN 50136/SSF 
114) 

Must not be connected to the general telephone network (ordinary telephone 
jack/PSTN). The telephone line connection can only be connected to the 
control panels to use the analogue dialler.

  

 

The terminal block supplies 30V of line voltage with a ring signal according to the 
PSTN standard. 

 

7

 

TESTING THE FIRE ALARM INSTALLATION (EN 54-21:2006) 

To test the communication alarm between the control panel and the alarm transmitter as well 
as between the alarm transmitter and the alarm receiver, disconnect the current power supply 
for the alarm transmitter. Then check the control panel for errors (see 6.5.1) and with the alarm 
receiver for a disruption in communication. Then reconnect the power supply, and check that 
the control panel and the alarm receiver have been reset for each alarm.  

Figure 12 

 

Tele terminal block 

Summary of Contents for Tor V

Page 1: ...Installation manual Tor V PDK 11606 version 6 0 May 28 2019 Tor V Alarm transmitter Installation manual...

Page 2: ...6 6 Ethernet connection broadband 12 6 6 1 Firewall configuration 12 6 7 Wireless connection 12 6 8 Reading the signal strength 12 6 9 Serial ports 13 6 9 1 Example of a cable for connecting the contr...

Page 3: ...EN 54 21 2011 EN 54 21 2006 EN 50130 5 2011 EN 50130 4 2011 A1 2014 Alarm transmission and fault warning routing equipment for intruder and fire alarm systems installed in buildings Notified body App...

Page 4: ...ess connection and the installation is to follow specific instructions for the installation of fire alarms See section 3 1 for all conditions For the alarm transmitter to meet the requirements of SSF...

Page 5: ...r with a resistor to detect failure The alarm transmitter is to be mounted and voltage supplied from the control panel Access to voltage supply from the control panel with 2A fuses Externally mounted...

Page 6: ...llation EN 54 21 2006 For a fire alarm installation it s easiest to mount the alarm transmitter inside the control panel This is so that the installation complies with EN 54 21 2006 Attach the include...

Page 7: ...satisfactory radio coverage See the signal strength using a computer see the appendix or LEDs during installation see 6 8 Satisfactory signal strength is between 14 and 32 Relieve the various cables t...

Page 8: ...AddSecure Tor V PDK 11606 8 5 CONNECTIONS Figure 1 Plastic encasement side 1 Figure 2 Plastic encasement side 2 Figure 3 Plastic encasement from above...

Page 9: ...tput Connect the control panel s output for error indication to optional alarm input Balance the output from the control panel with 4 7k 6 2 Alarm installation EN 50136 SSF 114 To meet security grade...

Page 10: ...er are analogue balanced at 4 7k the resistor is to be mounted as such This connection can keep the control panel galvanically isolated from the alarm transmitter Figure 6 Voltage of 5V to 12V with li...

Page 11: ...n and pin 9 common to the alarm panel at the appropriate input so that the alarm panel can detect a short circuit open circuit on the connection Status Ok The relay is closed when the alarm transmitte...

Page 12: ...28 corresponds to 85 117 163 240 28 corresponds to 85 117 160 240 85 117 160 255 85 117 163 240 85 117 163 255 6 7 Wireless connection The alarm transmitter is equipped with an FME male connector for...

Page 13: ...necting the control panel A 5 meter ready to go is available as an option and can be ordered Article number 80 321 329 6 9 2 Example of a null modem cable for connecting a PC S2 NAME FUNCTION 1 Tx Tra...

Page 14: ...al that the SIA or Contact ID protocol uses In this way the alarm transmitter receives and acknowledges messages that the control panel sends through its telephone connection After the transmission fr...

Page 15: ...ckup 9 2 The A diode is blinking and the C diode is turned off The alarm transmitter does not have contact with the mobile network Check the cables and the antenna The cables must not be spliced or pi...

Page 16: ...nnector Modular RJ12 ESPA support ESPA 4 4 4 Maximum cable length 15 meters ALARM INPUTS Inputs 8 analogue or digital inputs with internal pull up Maximum cable length 30 meters Voltage across open in...

Page 17: ...down 6 The LEDs display as normal no matter whether the interference protection is affected Table 1 signal strength Indicator Status Signal strength Satisfactory LED color LED A On 25 Yes Green LED B...

Page 18: ...tions Here are only the details necessary to measure signal strength in your web browser 1 Configure your computer for DHCP you automatically get an IP address between 172 20 20 20 and 172 20 20 250 2...

Page 19: ...le You are notified by the alarm center or through for example AddView that there is a disturbance causing your service to not work The alarm center will ask you to trigger a test alarm The alarm will...

Page 20: ...AddSecure Tor V PDK 11606 20 STOCKHOLM OSLO LONDON G TEBORG MALM ESPOO ZUG WWW ADDSECURE COM...

Reviews: