AddSecure Tor V, PDK-11606 

13 

6.9

 

Serial ports 

Whenever serial ports are included in the service, S2 is connected to the serial equipment. The 
connector is of the type RJ12, and the electrical user interface is RS232. 

 

 

 

 

 

Note that serial interface is only for additional information. You must use the 
input interfaces to follow the regulations (EN 54-21:2006, EN 50136/SSF 
114) 

 

6.9.1

 

Example of a cable for connecting the control panel 

 

 

 

 

 

 

 

A 5-meter ready-to-go is available as an option and can be ordered. Article number: 80 321 329 

6.9.2

 

Example of a null modem cable for connecting a PC  

 

 

 
 
 
 
 
 
 
 

 
 
 
 

S2 

NAME 

FUNCTION 

Tx 

Transmit 

Rx 

Receive 

RTS 

Request to send 

CTS 

Clear to send 

Power 

+5VDC 

GND 

Ground 

PIN CPU 

CABLE 

PIN 

CONTACT 

FUNCTION 

Green 

Tx 

  Tx 

Yellow 

Rx 

  Rx 

Orange 

RTS 

  RTS 

Brown 

CTS 

  CTS 

Red 

 

+5VDC   

 

Black 

GND 

 

GND 

PIN CPU 

PIN 

CONTACT  FUNCTION 

Tx 

 

Rx 

Rx 

 

Tx 

RTS 

 

CTS 

CTS 

 

RTS 

 

+5VDC 

 

 

GND 

 

GND 

Figure 11 

 Example of a null 

modem cable

 

Figure 10 

 Example of cable  

for control panel 

Summary of Contents for Tor V

Page 1: ...Installation manual Tor V PDK 11606 version 6 0 May 28 2019 Tor V Alarm transmitter Installation manual...

Page 2: ...6 6 Ethernet connection broadband 12 6 6 1 Firewall configuration 12 6 7 Wireless connection 12 6 8 Reading the signal strength 12 6 9 Serial ports 13 6 9 1 Example of a cable for connecting the contr...

Page 3: ...EN 54 21 2011 EN 54 21 2006 EN 50130 5 2011 EN 50130 4 2011 A1 2014 Alarm transmission and fault warning routing equipment for intruder and fire alarm systems installed in buildings Notified body App...

Page 4: ...ess connection and the installation is to follow specific instructions for the installation of fire alarms See section 3 1 for all conditions For the alarm transmitter to meet the requirements of SSF...

Page 5: ...r with a resistor to detect failure The alarm transmitter is to be mounted and voltage supplied from the control panel Access to voltage supply from the control panel with 2A fuses Externally mounted...

Page 6: ...llation EN 54 21 2006 For a fire alarm installation it s easiest to mount the alarm transmitter inside the control panel This is so that the installation complies with EN 54 21 2006 Attach the include...

Page 7: ...satisfactory radio coverage See the signal strength using a computer see the appendix or LEDs during installation see 6 8 Satisfactory signal strength is between 14 and 32 Relieve the various cables t...

Page 8: ...AddSecure Tor V PDK 11606 8 5 CONNECTIONS Figure 1 Plastic encasement side 1 Figure 2 Plastic encasement side 2 Figure 3 Plastic encasement from above...

Page 9: ...tput Connect the control panel s output for error indication to optional alarm input Balance the output from the control panel with 4 7k 6 2 Alarm installation EN 50136 SSF 114 To meet security grade...

Page 10: ...er are analogue balanced at 4 7k the resistor is to be mounted as such This connection can keep the control panel galvanically isolated from the alarm transmitter Figure 6 Voltage of 5V to 12V with li...

Page 11: ...n and pin 9 common to the alarm panel at the appropriate input so that the alarm panel can detect a short circuit open circuit on the connection Status Ok The relay is closed when the alarm transmitte...

Page 12: ...28 corresponds to 85 117 163 240 28 corresponds to 85 117 160 240 85 117 160 255 85 117 163 240 85 117 163 255 6 7 Wireless connection The alarm transmitter is equipped with an FME male connector for...

Page 13: ...necting the control panel A 5 meter ready to go is available as an option and can be ordered Article number 80 321 329 6 9 2 Example of a null modem cable for connecting a PC S2 NAME FUNCTION 1 Tx Tra...

Page 14: ...al that the SIA or Contact ID protocol uses In this way the alarm transmitter receives and acknowledges messages that the control panel sends through its telephone connection After the transmission fr...

Page 15: ...ckup 9 2 The A diode is blinking and the C diode is turned off The alarm transmitter does not have contact with the mobile network Check the cables and the antenna The cables must not be spliced or pi...

Page 16: ...nnector Modular RJ12 ESPA support ESPA 4 4 4 Maximum cable length 15 meters ALARM INPUTS Inputs 8 analogue or digital inputs with internal pull up Maximum cable length 30 meters Voltage across open in...

Page 17: ...down 6 The LEDs display as normal no matter whether the interference protection is affected Table 1 signal strength Indicator Status Signal strength Satisfactory LED color LED A On 25 Yes Green LED B...

Page 18: ...tions Here are only the details necessary to measure signal strength in your web browser 1 Configure your computer for DHCP you automatically get an IP address between 172 20 20 20 and 172 20 20 250 2...

Page 19: ...le You are notified by the alarm center or through for example AddView that there is a disturbance causing your service to not work The alarm center will ask you to trigger a test alarm The alarm will...

Page 20: ...AddSecure Tor V PDK 11606 20 STOCKHOLM OSLO LONDON G TEBORG MALM ESPOO ZUG WWW ADDSECURE COM...

Reviews: