Troubleshooting
Error
Code
Error
Type
Cause
Reset and Recovery
0
Cam
Sense
Error
The valve drive took
longer than 6 minutes
to advance to the
next regeneration
position.
Unplug the unit and examine the power head. Verify that all
cam switches are connected to the circuit board and
functioning properly. Verify that the motor and drive train
components are in good condition and assembled properly.
Check the valve and verify that the piston travels freely.
Replace /reassemble the various components as necessary.
Plug the unit in and observe its behavior. The unit should cycle
to the next valve position and stop. If the error re-occurs,
unplug the unit and contact your water treatment dealer.
1
Cycle
Step
Error
The control
experienced an
unexpected cycle
input
Unplug the unit and examine the power head. Verify that all
cam switches are connected to the circuit board and
functioning properly. Enter Master Programming mode and
verify that the valve type and system type are set correctly
with regard to the unit itself.
Step the unit through a manual regeneration and verify that it
functions correctly. If the error re-occurs unplug the unit and
contact you water treatment dealer.
2
Regen
Failure
The system has not
regenerated for more
than 99 days
Perform a manual regeneration to reset the error code.
Enter the Master Programming Mode and verify that the unit
is configure properly.
3
Memory
Error
Control board
memory failure
Perform a Master Reset and reconfigure the system via Master
Programming mode. After reconfiguring the system, step the
valve through a manual regeneration. If the error re-occurs
unplug the unit and contact your local water treatment dealer.
UD
Upper
Drive
Sync
Power failure install
programming change
Valve will automatically recover.
Resets
Soft Reset
: Press and hold the Extra Cycle and Down Buttons for 25 seconds while in normal service mode.
This resets all parameters. Check and verify all parameters in master programming.
Master Reset:
Hold the Extra Cycle button while powering up the unit. This resets all parameters. Check and
verify all parameters in mater programming