LTPS-UM-8007-01, Issue 1
Installation
SPX-CABFIN01, SPX-CABFIN04
November 9, 2001
43
1
At the DC Distribution Panel, ensure that all circuit breakers are set to OFF. The panel is located in bay No. 2,
below the rectifier shelf as shown in
.
2
At the bottom front of the rectifier shelf, loosen the captive fasteners, and pivot the module retainer
downward. Remove the blank cover plates (if present).
3
Unpack the rectifier modules. On each rectifier module, ensure that the AC INPUT and DC OUTPUT circuit
breakers are set to OFF.
4
Insert a rectifier module in the left (No. 2) slot of the modular power supply chassis as shown in
Figure 37.
Installing a Rectifier Module
5
Confirm that the AC ON/RFA LED is lighted red. With the battery string installed and the rectifier module
not powered up, the normal indication is a red LED.
6
Install the other rectifier module in the second (No. 1) slot of the modular power supply chassis (at the right
of rectifier module No. 2). Confirm that the AC ON/RFA LED is lighted red.
7
Unpack the Alarm and Control Assembly (ACA).
8
Install the ACA plug-in in the third slot of the rectifier shelf; tighten the top captive fastener as shown in
9
Locate remote alarm connector P1; connect P1 to ACA connector J1 (the side connector nearest the front of
the ACA). Access to J1 is through the shelf side opening.
10
Reinstall the blank faceplate over the fourth (right-hand) slot on the shelf as shown in
11
To secure all modules in the rectifier shelf, ensure that all modules are fully seated (pushed all the way in).
Pivot the module retainer upward and tighten three captive fasteners.
Do not turn on the rectifier modules at this time.
P/N 73-16-606
1
2
-48V
-48V
-48V
RTN
RTN
-48V
MAX BREAKER 30A
RTN
-48V
RTN
-48V
RTN
-48V
-48V
RTN
RTN
-48V
BATTERY
DISCONNECT
BATTERY
DISCONNECT
BATTERY DISCONNECT
FUSE
ALARM
ALARM
TEST
RTN
3
4
5
6
1
1
5
10
MAX FUSE 15A
TOTAL AMPERAGE
OUTPUT
BREAKERS-80A MAX
GMT FUSES-50A MAX
COMBINED-80A MAX
15
20
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
NO
C
NC
NO
C
NC
FUSE ALARM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
DO NOT ADJUST
FLOAT
VARIES WITH TEMP.
FLT
FAN FAIL
AC ON/
RFA
+
CAL VOLTS
(-48.2V)
CAP
CHARGE
F1
06A 250V
+
OUTPUT
CUR
DC OUTPUT
AC INPUT
DO NOT ADJUST
FLOAT
VARIES WITH TEMP.
FLT
FAN FAIL
AC ON/
RFA
CAP
CHARGE
F1
06A 250V
DC OUTPUT
AC INPUT
+
CAL VOLTS
(-48.2V)
+
OUTPUT
CUR
ALM & CONTROL
ASSY
48631600
(+) HVSD
(+)
(-) VOLTS (X10)
BAT ON
DISCH
HVSD
VOLT
ADJ
BAT ON
DISCH
ADJ
RESTART/
LOCKED
OUT
RESTART
RESET
CAUTION
REMOVE P1 & P2
BEFORE REMOVING
ALARM CARD
CLEI CODE