The current capacity of each bus is 100 Amps maximum. The total current of the circuit breaker
panel (both buses) is 200 Amps maximum.
The power dissipation of the circuit breaker panel is 100 watts maximum at 200 Amps.
The dimensions of the circuit breaker panel are 1.75 inches (4.45 centimeters) high, 17.13 inches
(43.5 centimeters) wide, and 10 inches (25.41 centimeters) deep. This does not include depth of
protective cover and connectors, circuit breakers, and visual indicators that extend beyond the
chassis.
The circuit breaker panel can be mounted in 19- or 23-inch racks (48.26 or 58.42 cm) with
WECO or EIA hole spacing using the mounting brackets provided.
Options
The circuit breaker panel is available with the following options:
• One to eight replaceable circuit breakers can be installed for each bus
• Selection of circuit breaker values (1, 3, 5, 10, 15, or 20 Amps).
• Panel can be equipped with any combination of circuit breakers (with specified values) as
long as total current draw on each bus does not exceed 100 Amps
• Selection of circuit breakers that trip instantly or trip after a short delay
• Two types of alarm contact connectors, either a screw-down terminal strip connector or a
wire wrap pin block connector
• Color of the circuit breaker panel is putty white.
Accessories
Several accessories for the circuit breaker panels are available (see
):
• Circuit breakers with capacity values of 1, 3, 5, 10, 15, and 20 Amperes
• Cable management bar kit
• Compression lugs for connection to the input connectors
• Lug terminals to connect #10 AWG wire to earth ground
• Spare circuit breaker designation card kit
Revision History
ISSUE
DATE
REASON FOR CHANGE
Issue 1
09/2001
Original
Issue 2
03/2002
Updated to cover replaceable circuit breaker feature
Issue 3
07/2004
Updated to add warning saying use of one bus only on dual bus panel will result in false alarms