ADCP-80-526 • Issue 6 • December 2006
Page 19
© 2006, ADC Telecommunications, Inc.
4. Place the fuse platform in the specified mounting space within the rack.
5. Secure the fuse platform to the equipment rack as shown in
using the four 3/8-
inch (9.53 mm) long pan-head screws and flat washers provided.
Figure 14. Mounting Fuse Platform on Rack
4.3
Grounding Chassis
Use the following procedure to connect the panel to an approved office ground source:
1. Obtain two lengths of #10 AWG wire for use as the chassis grounding wires.
2. Terminate one end of each wire with the #10 ring terminals provided (requires crimper).
Caution:
Do not use any hardware other than the hardware supplied with the fuse platform.
Note:
A single ground wire can also be used. If using a single ground wire, use #6 AWG
wire terminated at either stud.
18865-A
DETAIL DRAWING OF
MOUNTING SCREWS
AND WASHERS
USE #12 STAR WASHERS INSTEAD OF FLAT
WASHERS IF REQUIRED BY LOCAL PRACTICE
TIGHTEN MOUNTING SCREWS
TO 27 POUND-FORCE INCHES
(3.1 NEWTON METERS) OF TORQUE