![ADC PowerWorx Circuit Breaker Panel With Reset Switch User Manual Download Page 34](http://html1.mh-extra.com/html/adc/powerworx-circuit-breaker-panel-with-reset-switch/powerworx-circuit-breaker-panel-with-reset-switch_user-manual_2848184034.webp)
ADCP-80-570 • Issue 2 • March 2006
Page 28
© 2006, ADC Telecommunications, Inc.
9. Disconnect the power and load wires (#14 AWG white and black wires) and the alarm
wires (#24 AWG black wires) from the terminals on the rear side of the circuit breaker as
shown in.
10. Connect the power and load wires to the specified terminals on the rear side of the
replacement circuit breaker (see
Figure 20
). Note that with the circuit breaker oriented as
shown, the black load wire connects to the top terminal and the white power wire connects
to the bottom (LINE) terminal.
11. Connect the two alarm wires to the specified terminals on the rear side of the replacement
circuit breaker (see
Figure 20
).
12. Insert the replacement circuit breaker into the opening in the panel and push inward until it
locks into place.
13. Reconnect the power to the power bus.
Figure 20. Circuit Breaker
Note:
Do not connect any wires to the center terminal on the circuit breaker.
LINE
POWER
(WHITE)
LOAD
(BLACK)
BREAKER ALARM
CONNECTIONS
LOCKING
TAB
LOCKING
TAB
20647-C
NOT USED
FRONT VIEW
SIDE VIEW
Summary of Contents for PowerWorx Circuit Breaker Panel With Reset Switch
Page 36: ...ADCP 80 570 Issue 2 March 2006 Page 30 2006 ADC Telecommunications Inc...
Page 39: ......
Page 40: ...i www adc com...