ADCP-75-210 • Issue 1 • March 2007
Page 24
© 2007, ADC Telecommunications, Inc.
1.8.2
Low Voltage Disconnect (LVD) Unit
The Low Voltage Disconnect (LVD) Unit (
) disconnects power automatically when
the RAN voltage falls below a specified minimum. The LVD unit also manages the backup
batteries (extended or glitch).
Figure 19. Low Voltage Disconnect Unit
Table 12. Rectifier Indicators
REF #
DESIGNATION
DEVICE
FUNCTIONAL DESCRIPTION
1
(Unmarked)
Green LED
AC OK. Lights when AC power is present
2
(Unmarked)
Green LED
DC OK. Lights when rectifier is limiting current
3
(Unmarked)
Red LED
Over Voltage Protection. Lights when rectifier has failed
4
(Unmarked)
Red LED
Over Temperature Protection. Lights when over temperature compen-
sation circuit is active
Table 13. LVD Indicators
REF #
DESIGNATION
DEVICE
FUNCTIONAL DESCRIPTION
1
OK
Green LED
Okay. Lights when power system is functioning correctly
2
MAJ
Red LED
Major Fault. Lights when a major fault exists
3
MIN
Yellow LED
Minor Fault. Lights when a minor fault exists
4
(Unmarked)
9-pin connector
Connector for cable 1001476P001 to the RECT (RJ45 connector)
port on the STF module
5
LVD
Red LED
Low Voltage Disconnect. Lights when switch has closed due to low
voltage
6
DISC
Switch
Disconnect. Pressing this switch disconnects the backup batteries
1
2
3
4
6
5
OK LED
MAJOR FAULT LED
MINOR FAULT LED
LVD ON LED
21334-A