Appendix B: POWER TABLE
Fixture type
Fixture load
Isolation transformer
CCR load
Rating
Loss
Efficiency
RS -AM (omnidirectional, inset)
35 VA
45 W
7 VA
0.85
45 VA
Fixture type
Fixture load
Isolation transformer
CCR load
Rating
Loss
Efficiency
RS -TE (omnidirectional, inset)
14 VA
25 / 35 W
4 VA
0.85
20 VA
Note
•
Extra losses in secondary cables or due to extra equipment (e.g. ILCMS remotes) are not included in above table;
these extra losses will result in a higher required size of isolation transformers.
•
Extra losses in primary cables are not included in above table; these extra losses will result in a higher required
CCR load.
•
Efficiency of the secondary transformer depends on the supplier of secondary transformers.
UM-5027, Rev. 1.0, 2020/12/10
59
Copyright
©
ADB SAFEGATE, All Rights Reserved
Summary of Contents for RELIANCE
Page 1: ...RELIANCE Omni Light 8 inch User Manual UM 5027 Rev 1 0 2020 12 10 ...
Page 2: ......
Page 8: ...RELIANCE Omni Light List of Figures viii Copyright ADB SAFEGATE All Rights Reserved ...
Page 10: ...RELIANCE Omni Light List of Tables x Copyright ADB SAFEGATE All Rights Reserved ...
Page 22: ...RELIANCE Omni Light General Information 12 Copyright ADB SAFEGATE All Rights Reserved ...
Page 26: ...RELIANCE Omni Light Installation 16 Copyright ADB SAFEGATE All Rights Reserved ...
Page 36: ...RELIANCE Omni Light Operation 26 Copyright ADB SAFEGATE All Rights Reserved ...
Page 62: ...RELIANCE Omni Light Maintenance 52 Copyright ADB SAFEGATE All Rights Reserved ...
Page 70: ...RELIANCE Omni Light POWER TABLE 60 Copyright ADB SAFEGATE All Rights Reserved ...
Page 72: ...RELIANCE Omni Light CABLE LOSS 62 Copyright ADB SAFEGATE All Rights Reserved ...
Page 76: ......