ADAM-3600 Series User Manual
6
2.2.1.2
Input / Output Specification
2.2.1.3
Environmental Specifications
Operating Temperature: -40~70°C
Storage Temperature: -40~85°C
Operating Humidity: 20~95% (non-condensing)
Storage Humidity: 0 ~ 95% (non-condensing)
Analog Input
Channel
8, differential
Input Type
Voltage, Current
Voltage/Current Range
±10V, ±2.5V, 0~20mA, 4~20 mA
Resolution
16-bit
Sampling rate
10 samples/second (total)
Input Impedance
10M
Accuracy
±0.1% or better (Full Scale)
CMR @ 50/60 Hz
120 dB
NMR @ 50/60 Hz
100 dB
Span Drift
± 25 ppm/
O
C
Zero Drift
± 3
μ
V/
O
C, ± 3
μ
A/
O
C
Isolation Voltage
2,000V
DC
Burn-out detection
Yes (Current-only)
Digital Input/Pulse Input
Channel
8
Input Type
Sink (Wet Contact)/ Counter
Wet Contact Input
Logic0: 0 ~ 5 V
DC
Logic 1: 11~30V
DC
Rated Voltage
12/24VDC
Rated Input Current
>5mA@12V
DC
>10mA@24V
DC
Input Filter
Programmable, Default: 3ms
Pulse Input Frequency
150HZ
Over Voltage Protection
+40V
DC
Isolation Voltage
2000V
DC
Digital Output/Pulse Output
Channel
4
Output Type
Open Collector (Sink)
OC Output
Rated Voltage
8~30 V
DC
Rated Current
200mA(max.load)
Over Voltage Protection
+40V
DC
Pulse Output Frequency
1KHz
Isolation Voltage
2000V
DC
Summary of Contents for ADAM-3600-C2G
Page 1: ...User Manual ADAM 3600 C2G iRTU User s Manual...
Page 4: ...ADAM 3600 Series User Manual iv...
Page 8: ...ADAM 3600 Series User Manual viii...
Page 9: ...Chapter 1 1 Introduction...
Page 11: ...Chapter 2 2 Specifications...
Page 18: ...ADAM 3600 Series User Manual 10 2 4 iRTU Dimensions Figure 2 2 ADAM 3600 Dimensions...
Page 19: ...Chapter 3 3 Wiring and Installation...
Page 28: ...ADAM 3600 Series User Manual 20...
Page 29: ...Chapter 4 4 Advantech iRTU Studio...
Page 53: ...Appendix A A ADAM 3600 Naming Rules...
Page 55: ...Appendix B B Interface Definition...
Page 58: ...ADAM 3600 Series User Manual 50 B 1 2 I O Interface Definition...