Pre-Installation
2
Codes Compliance
Water heater installation must conform with the
instructions in this manual and where applicable:
• local, state, provincial, and national codes,
laws, regulations and ordinances.
• in Canada - CAN / CGA B149.1 or B149.2
Installation Code.
COMFORT water heaters are exempt from ASME
Section VIII, Division 1 Code construction per
Interpretation VIII-86-136. Check with local codes
for applicability.
COMFORT Series water heaters will
absorb less than 200,000 BTU/hr when
domestic water outlet temperature is 210ºF
and boiler water supply temperature is
240ºF. Listed outputs are based on ASME
Section VIII Interpretation VIII-1-86-136.
Where recommendations in this manual differ
from local, or national codes, the local or national
codes take precedence.
Codes Restrictions
Single wall heat exchanger in the COMFORT
water heater complies with National Standard
Plumbing Code, provided that:
– boiler water (including additives) is practically
non-toxic, having toxicity rating or class of 1,
as listed in Clinical Toxicology of Commercial
Products, and
– boiler water pressure is limited to maximum
30 psig by approved relief valve.
Single wall heat exchangers are permitted under the
Uniform Plumbing code - Paragraph L3.2. and L3.3
if they satisfy all of the following requirements.
1. The heat transfer medium is potable water or
contains only substances which are recog-
nized as safe by the U.S. Food and Drug
Administration.
2. The pressure of the heat transfer medium is
maintained less than the normal minimum
operating pressure of the potable water system
Exception:
Steam complying with sec-
tion #1 above.
3. The equipment is permanently labeled to
indicate that only additives recognized as
safe by the FDA shall be used in the heat
transfer medium.
Other heat exchanger designs may be permitted
where approved by the Administrative Authority.