Operator’s Guide for Rugged-UPS
TM
1252 Series
91-0120 Rev. B 17
© Acumentrics Corporation 2007-2008
upsObjects(1).upsBattery(2
upsSecondsOnBattery(2)
int
If the unit is on battery power, the
elapsed time since the UPS last
switched to battery power, or the time
since the network management
subsystem was last restarted,
whichever is less. Zero shall be
returned if the unit is not on battery
power.
Read
UpsEstimatedMinutes
upsObjects(1).upsBattery(2
Remaining(3)
int
An estimate of the time to battery
charge depletion under the present
load conditions if the utility power is
off and remains off, or if it were to be
lost and remain off.
Read
UpsEstimatedCharge
upsObjects(1).upsBattery(2
Remaining(4)
int
An estimate of the battery charge
remaining expressed as a percent of
full charge.
Read
upsObjects(1).upsBattery(2
upsBatteryVoltage(5)
int
The magnitude of the present battery
voltage.
Read
upsObjects(1).upsBattery(2
upsBatteryTemperature(7)
int
The ambient temperature at or near
the UPS Battery casing.
Read
upsObjects(1).upsInput(3)
upsInputLineBads(1)
int
A count of the number of times the
input entered an out-of-tolerance
condition as defined by the
manufacturer. This count is
incremented by one each time the
input transitions from zero out-of-
tolerance lines to one or more input
lines out-of-tolerance.
Read
upsObjects(1).upsInput(3).upsInputTable(3).upsInputEntry(1)
upsInputVoltage(3)
int
The magnitude of the present input
voltage.
Read
1: other
2: none
3: normal
4: bypass
5: battery
6: booster
upsObjects(1).upsOutput(4)
upsOutputSource(1)
int
The present source of output power.
The enumeration none(2) indicates
that there is no source of output
power (and therefore no output
power), for example, the system has
opened the output breaker.
7: reducer
Read
upsObjects(1).upsOutput(4)
.upsOutputTable(4).upsOutputEntry(1)
upsOutputVoltage(2)
int
The present output voltage.
Read
upsObjects(1).upsOutput(4).
upsOutputPower(4)
int
The present output true power.
Read