Acuity Controls nLight ECLYPSE Safety Instructions Download Page 4

nLight ECLYPSE Enclosure

912-00023-001

Page 4

Acuity Brands | One Lithonia Way  Conyers, GA  30012   Phone: 800.535.2465    www.acuitycontrols.com     ©  2017 Acuity Brands Lighting, Inc.  All rights reserved.   06/21/17    

BOX DIMENSIONS & INSTALLATION APPLICATION NOTES

The NECY enclosure was designed with minimal knockouts to provide installers the freedom to add additional conduit feeds to 

better meet specific site conditions without locking them into confined positions or preset trade size fittings.

The dimensions provided are for reference only. Verify all clearances with the actual panel and its components in place prior to 

performing any added punch-out work. Note: For Canadian configured devices with step-down transformers (for 347V), added 

conduit feed access is more constricted as shown by the added step-down transformer.

WIRING INSTRUCTIONS

DE-ENERGIZE THE PANEL BEFORE MAKING ANY WIRING 

CONNECTIONS.

 DO NOT DISCARD THESE INSTALLATION INSTRUCTIONS. 

PLEASE KEEP FOR FUTURE REFERENCE AND OPERATION 

INFORMATION.

NOTE: Make certain that high voltage and low voltage 

wiring enters the enclosure separately. 
High Voltage wiring should be brought into the upper-

right section of the enclosure, inside the high-voltage 

compartment.
Low Voltage wire should enter in the low voltage wiring 

areas of the enclosure.
Failure to separate high voltage from low voltage wiring 

may cause electrical interference.

HIGH VOLTAGE CONNECTIONS
• Always de energize panel before wiring.
• Use only at the listed voltage per panel specs
• All installation service must be performed by qualified 

personnel.

WIRING THE POWER SUPPLY 
• The Acuity Relay Panel is factory configured with a 120-

277V 50W switching power supply (MVOLT) , and optionally 

can be supplied with a 347V to 277V step-down transformer 

(CNDV).

• Connect wires to the power supply. You must provide 

a dedicated circuit with circuit protection for the power 

supply. Earth ground must be connected to the lug labeled 

"FOR EQUIPMENT GROUNDING ONLY," located in the high 

voltage compartment
• It is recommended that all low voltage wiring be done 

with power removed from the system, to protect from 

potential shorts during the wiring process.
• All low voltage wiring must be run in separate conduit 

from line voltage wiring. DO NOT MIX CLASS 1 AND CLASS 2 

CIRCUITS IN THE SAME CONDUIT
• Test all low voltage wiring for shorts to AC ground before 

connection to the controller.
 
APPLYING POWER
• Once the wiring is complete, make certain that the 

enclosure is clean of any wire clippings and that no 

fragments are present. 
• Ensure that there are no loose wires or exposed wires that 

could short to other wires or components.
• Power up the unit from the circuit breaker.

a) The green power supply input terminal block receives 

the line voltage feed wires, 120-277VAC, Neutral, 

Ground

Summary of Contents for nLight ECLYPSE

Page 1: ...S Do not use outdoors Do not mount near gas or electric heaters Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use SAVE THESE INSTRUCTIONS Remove internal assembly pr...

Page 2: ...over hardware is misplaced utilize screws and lockwashers with paint piercing features Enclosure utilizes SEMS and KEPS fasteners with integrated toothed lock washers for paint piercing to ensure proper bonding of painted enclosure parts ENCLOSURE UNTILIZES SEMS AND KEPS FASTENERS INTEGRATED TOOTHED LOCK WASHERS FOR PAINT PIERCING TO ENSURE PROPER BONDING OF PAINTED ENCLOSURE PARTS 912 00023 001 P...

Page 3: ... proper protrusion of box edge to be flush finished wall surface Verify with actual wall material thicknesses to ensure a proper finished installation wall stud wall board align marks with wall stud surface for flush mount installs Flush Mount Install example Flush 8 RELAY SIZED PANEL SHOWN BUT APPLIES TO 16 RELAY VERSION Box Dimensions Installation Application Notes TOP 912 00023 001 Page 3 Acuit...

Page 4: ...closure Failure to separate high voltage from low voltage wiring may cause electrical interference HIGH VOLTAGE CONNECTIONS Always de energize panel before wiring Use only at the listed voltage per panel specs All installation service must be performed by qualified personnel WIRING THE POWER SUPPLY The Acuity Relay Panel is factory configured with a 120 277V 50W switching power supply MVOLT and op...

Page 5: ...2465 www acuitycontrols com 2017 Acuity Brands Lighting Inc All rights reserved 06 21 17 Knockout Knockout High Voltage Knockout Knockout nLight Port 1 nLight Port 2 USB 1 USB 2 DIN Rail DIN Clip nLight Port 3 Supports GFX module Ethernet Secondary Ethernet Primary Modbus RS 485 nLIGHT ECLYPSE WIRING DIAGRAM ...

Reviews: