12
13
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
LED/colour
Symbol
Operation possibilities for:
Alarm/
fire
Comfort
operation
LD1/red
Actuator open (red). Lights when actuator opens
LD2/green
Actuator close (green). Lights when actuator closes
LD3/red
Weather sensor active (red). Lights when weather sensor is active
Yes
No
LD4/red
Line error on actuator (red). Lights when actuator has open circuit,
flashes at earth fail or when short circuit occur.
It is not possible to RESET or close with actuator output (see page 7)
Yes
No
LD5/red
Line error on fire switch (red). Lights when fire switch has line error,
flashes when Fireman’s Priority Switch has line error
Yes
Only
close
LD6/red
Line error on smoke detector (red). Lights when smoke detector has
line error, flashes at temperatures above 75 °C
Yes
Only
close
LD7/red
Bus error (red). Lights when BUS signal from other controls is
missing. Only relevant if J4-J7 is mounted.
Yes
Only
close
Green
Board + Front
lights
if everything is ok
switched off
by local error on this control
flashes
by error message from other controls received by bus
Yes
Yes
Yellow
Board + Front
Fault
lights
by local error on this control
or by error message from other controls received by bus
Yes
Only
close
*Yellow
Board + Front
Line error
flashes
by local error on this control and if the ribbon cable or
jumper is not mounted on J9, or
by error message from other
controls received by bus
Yes
Only
close
*Yellow
Board + Front
AC error
flashes
by local error on this control
or
by error message from other controls received by bus
Yes
Only
close
Red
Board + Front
Alarm
lights
red constantly
Yes
No
*Yellow
Board + Front
DC error
flashes at normal speed (1 Hz)
by local battery error on this control
or
by error message from other controls received by bus
flashes at high speed (10 Hz)
by battery voltage below 19V.
Reset by DIP 4: OFF/ON
Blue
Board + Front
Lights blue constantly in open condition (when windows are open)
flashes when actuator is moving up and down
Lights with*
Time for yearly service - please call for supplier (flashes fast)
Yes
Yes
Fuse specifications
Placement
Fuse value
24V
F1 8A
fast ading fuse
1 pcs. for 24V motor output
LEDs on main board and front panel
Text on board
Factory
mounted
Mounted / ON function
Dismounted / OFF function
DIP 1
Conf. Fireswitch
No
Fire switch active from 500-3 KΩ.
A short circuit of the smoke detector
input will generate a line error
Fire switch active from 0-3 KΩ.
A short circuit of the smoke detector
input will generate alarm
DIP 2
Failsafe
No
Line error on fire switch or detector
puts the control in alarm
Normal mode
DIP 3
Temp. Detekt
No
Line error on motor line
(upper resistor area) = alarm
Normal mode
DIP 4
Ser
Yes
Active
Inactive
DIP 5
Snitch
No
LED’s “remember” errors (line
errors, AC/Batt. error, bus error). The
LED’s can only be switched off/reset
again by setting dip switch off
Normal mode
DIP 6
Fail Relay
No
Failure relay works as indication that
skylight is open
Normal mode (works as failure
relay)
DIP 7
Week open
No
Weekly open (2 sec.) /close
(5 sec.) cycle activated
Weekly open/close not activated
DIP 8
Option
No
Auto reset (see page 9)
Normal mode
DIP 9
Sprinkler
No
Motor output closes by active
detector (opens by activating the fire
switch)
Normal mode - motor output opens
by ative detectors or fire switches
DIP 10
Bus comfort
No
The control reacts on comfort signal
via bus activity
The control does not react on
comfort signals via bus activity //
NB! Always reaction on weather
signal and failures via bus activity
and own comfort signal
DIP 11
Bus fire
No
The control reacts on alarm signal
via bus activity
The control does not react on alarm
signal via bus activity
//NB! Always reaction on weather
signal and failures via bus activity
and own alarm signal (detector or
fire switch)
DIP 12
Lock-Out Mode
No
Slaves can enter Lock-Out Mode
see page 18
Normal mode
J1
J1
Yes
Internal Buzzer ON
Internal Buzzer OFF
J3
(motor)
1 - 2 - 3 - 4
Pos. 1
Connect according to number of
27
KΩ terminal resistors on actuator
No line monitoring
J2
(motor)
Mot Mon act.
Yes
2 wire line monitoring via 27KΩ
terminal 2-3
No line monitoring
Ext Li Mon act.
No
3 wire line monitoring with direct
motor connection actuator
J4(Bus)
Start term.
No
First control panel in the bus network
See section concerning connection
of controls panels in bus connection,
page 14
J5(Bus)
+ Master
No
J6(Bus)
Slave
No
Middle and last control panel in the
bus network
J7(Bus)
End term.
No
Last control panel in the bus network
J9
FOIL
Yes in Basic
Line monotoring of front cabinet
Line error flashes
J11
BatSup->Ø23
No
Battery backup of terminal 23
Terminal 23 only AC supplied
Others: Reset time = 180 sec. closing // Cut-off motor output and loading after 360 sec. // Comf. var (potetiometer): 1-60 sec.
Complete jumper settings for SVM EI PCB