Actulux SVM EI 24V-5A Installation Instruction Download Page 7

12

13

Control for Fire and Comfort Ventilation Type SVM EI 24V-5A  /  SVM EI 24V-8A

                                                           

   Control for Fire and Comfort Ventilation Type SVM EI 24V-5A  /  SVM EI 24V-8A

LED/colour

Symbol

 Operation possibilities for: 

Alarm/

fire

Comfort 

operation

LD1/red

Actuator open (red). Lights when actuator opens

LD2/green

Actuator close (green). Lights when actuator closes

LD3/red

Weather sensor active (red). Lights when weather sensor is active

Yes

No

LD4/red

Line error on actuator (red). Lights when actuator has open circuit, 

flashes at earth fail or when short circuit occur.

It is not possible to RESET or close with actuator output (see page 7)

Yes

No

LD5/red

Line error on fire switch (red). Lights when fire switch has line error,

flashes when Fireman’s Priority Switch has line error

Yes

Only 

close

LD6/red

Line error on smoke detector (red). Lights when smoke detector has 

line error, flashes at temperatures above 75 °C

Yes

Only 

close

LD7/red

Bus error (red). Lights when BUS signal from other controls is 

missing. Only relevant if J4-J7 is mounted. 

Yes

Only 

close

Green

Board + Front

      lights

 if everything is ok  

      switched off 

by local error on this control

      flashes

 by error message from other controls received by bus

Yes

Yes

Yellow

Board + Front

Fault

lights

 by local error on this control

      

or by error message from other controls received by bus

Yes

Only 

close

*Yellow

   Board + Front

Line error

flashes

 by local error on this control and if the ribbon cable or

jumper is not mounted on J9, or

 

by error message from other 

controls received by bus

Yes

Only 

close

*Yellow

   Board + Front

AC error

flashes 

by local error on this control 

or

 

by error message from other controls received by bus

Yes

Only 

close

Red

Board + Front

Alarm

lights

 red constantly

Yes

No

*Yellow

   Board + Front

DC error 

flashes at normal speed (1 Hz)

 by local battery error on this control

or

 

by error message from other controls received by bus

flashes at high speed (10 Hz)

 by battery voltage below 19V.

Reset by DIP 4: OFF/ON

Blue

Board + Front

Lights blue constantly in open condition (when windows are open) 

 

flashes when actuator is moving up and down

Lights with*

      Time for yearly service - please call for supplier (flashes fast)

Yes

Yes

Fuse specifications

                               Placement 

Fuse value

24V

F1 8A

 

fast ading fuse

1 pcs. for 24V motor output

LEDs on main board and front panel

Text on board

Factory 

mounted

Mounted / ON function 

Dismounted / OFF function

DIP 1

Conf. Fireswitch

No

Fire switch active from 500-3 KΩ.

 

A short circuit of the smoke detector 

input will generate a line error

Fire switch active from 0-3 KΩ.

A short circuit of the smoke detector 

input will generate alarm

DIP 2

Failsafe

No

Line error on fire switch or detector 

puts the control in alarm

Normal mode

DIP 3

Temp. Detekt

No

Line error on motor line

 

(upper resistor area) = alarm

Normal mode

DIP 4

Ser

Yes

Active

Inactive

DIP 5

Snitch

No

LED’s “remember” errors (line 

errors, AC/Batt. error, bus error). The 

LED’s can only be switched off/reset 

again by setting dip switch off

Normal mode

DIP 6

Fail Relay

No

Failure relay works as indication that 

skylight is open

Normal mode (works as failure 

relay)

DIP 7

Week open

No

Weekly open (2 sec.) /close 

(5 sec.) cycle activated 

Weekly open/close not activated

DIP 8

Option

No

Auto reset (see page 9)

Normal mode

DIP 9

Sprinkler

No

Motor output closes by active 

detector (opens by activating the fire 

switch)

Normal mode - motor output opens 

by ative detectors or fire switches

DIP 10

Bus comfort

No

The control reacts on comfort signal 

via bus activity

The control does not react on 

comfort signals via bus activity // 

NB! Always reaction on weather 

signal and failures via bus activity 

and own comfort signal

DIP 11

Bus fire

No

The control reacts on alarm signal 

via bus activity

The control does not react on alarm 

signal via bus activity 

//NB! Always reaction on weather 

signal and failures via bus activity 

and own alarm signal (detector or 

fire switch)

DIP 12

Lock-Out Mode

No

Slaves can enter Lock-Out Mode

 

see page 18

Normal mode

J1

J1

Yes

Internal Buzzer ON

Internal Buzzer OFF

J3 

(motor)

1 - 2 - 3 - 4

Pos. 1

Connect according to number of  

27

KΩ terminal resistors on actuator

No line monitoring

J2 

(motor)

Mot Mon act. 

Yes

2 wire line monitoring via 27KΩ 

terminal 2-3

No line monitoring

Ext Li Mon act. 

No

3 wire line monitoring with direct 

motor connection actuator 

J4(Bus)

Start term. 

No

First control panel in the bus network

See section concerning connection 

of controls panels in bus connection, 

page 14 

J5(Bus)

+ Master

No

J6(Bus)

Slave

No

Middle and last control panel in the 

bus network

J7(Bus)

End term.

No

Last control panel in the bus network

J9

FOIL

Yes in Basic

Line monotoring of front cabinet

Line error flashes

J11

BatSup->Ø23

No

Battery backup of terminal 23

Terminal 23 only AC supplied

Others: Reset time = 180 sec. closing // Cut-off motor output and loading after 360 sec.  // Comf. var (potetiometer): 1-60 sec.

Complete jumper settings for SVM EI PCB

Summary of Contents for SVM EI 24V-5A

Page 1: ... 24V 8A Fire ventilation Comfort ventilation 24VDC max 5A 8A 1 fire ventilation group 1 comfort group Connection for manual control points wind and rain sensor comfort switches smoke detectors and Fireman s Priority Switch Possibility for bus connection of 35 control panels 211534 ...

Page 2: ..._______________________________________________________ Comfort control ___________________________________________________________________________________________________ Wind and rain sensor ___________________________________________________________________________________________________ 230V power supply from group ______________________________________________________________________________...

Page 3: ...fety rules must therefore always be observed Νever short circuit a back up battery Do not use external chargers on installed batteries If unauthorized chargers are used explosive gasses can be released from the battery Do not drop back up batteries as strong acids can be released if they are broken Installation The control panel can weigh up to 7 kg and must be installed on a stable wall The mount...

Page 4: ... 27 KΩ you wish to detect the same way as the motor line This setting demands 3 wire cable from motor output to motor Current limiter type LIP function and setting if mounted The current limiter type LIP mounted on the opening system is used as current limiter between the 24V 48VDC supply and 1 or 2 actuators When the adjusted current limit is reached the speed of the actuators is reduced When the...

Page 5: ...us up signal gives 3x6 sec 18 sec One press on down closes the actuator completely for a period which is 18 sec longer than the complete opening time In order to avoid actuator pumping max 3 successive closing attempts will be allowed Potentiometer in Const pos As long as up signal or down signal are given the actuators are running Potentiometer in Puls variable pos The time on the above mentioned...

Page 6: ...INE FAIL AC FAIL YEL YEL BAT BAT ON DIP NO 1 2 OFF START termination DOME OPEN BLUE PS PS Black 2 5mm2 24VDC Batteries 2x 12V 7 2 Ah 24V Red 2 5mm2 Connection SVM EI 24V 5A 8A BUZZER B3 J5 J6 J7 A3 B1 B2 Serial Out next unit Connection to A1 prev unit 21 20 Gnd 23 22 Weather Gnd 24V A2 Serial In Connection from Bus connection for serial connection up to 35 pcs control units J4 Set J11 for batteri ...

Page 7: ... ON function Dismounted OFF function DIP 1 Conf Fireswitch No Fire switch active from 500 3 KΩ A short circuit of the smoke detector input will generate a line error Fire switch active from 0 3 KΩ A short circuit of the smoke detector input will generate alarm DIP 2 Failsafe No Line error on fire switch or detector puts the control in alarm Normal mode DIP 3 Temp Detekt No Line error on motor line...

Page 8: ...s adjusted according to the instructions Actuators should be closed when the wind is above 6 m s LED 3 on the main board indicates active weather sensor lights as long as input is active As long as the weather sensor is active motor inputs cannot be opened with comfort switches The weather sensor closes on all controls which are connected through bus connection On the input to weather station a we...

Page 9: ...re on actuator LED 5 Line failure fire switch red Lit for line failure on fire switch LED 6 Line failure smokesensor red Lit for line fail on smokes LED 7 BUS failure red Lit when local unit is not recieving signal LOCKOUT TEMP DETECT SERVICE TIMER SNITCH FAIL RELAY M WEEK OPEN OPTION SPRINKLER BUS COMFORT BUS FIRE 12 3 4 6 7 5 8 11 9 10 BUS Master BUS Slave END termination Con Fire Sig FAIL SAFE ...

Page 10: ...ng the Slave unit in lock out mode is by using a Fireman s Priority Switch 27 02 2018 ALARM ON ONE OF THE SLAVES SLAVE EVENT MASTER ALL OTHER SLAVES SMOKE FIRE MODE FIRE mode Lock Out mode MCP BVT FIRE MODE FIRE mode Lock Out mode MASTER SLAVE SLAVE SLAVE MCP SMOKE MCP SMOKE MCP SMOKE MCP SMOKE LOCK OUT LOCK OUT MASTER SLAVE SLAVE SLAVE MCP SMOKE MCP SMOKE MCP SMOKE MCP SMOKE LOCK OUT LOCK OUT Man...

Page 11: ...sement pour vérins électriques Producenten Manufacture Actulux A S Haandvaerkervej 2 9560 Hadsund Denmark Hersteller Usine de fabrication System for attestering og kontrol af ydeevne System for attestation and verification of performance SYSTEM 1 System zur Bescheinigung und Prüfung der Performance Système s d évaluation et de vérification de la constance des performances du produit Det bemyndiged...

Page 12: ...for Fire and Comfort Ventilation Type SVM EI 24V 5A SVM EI 24V 8A Control for Fire and Comfort Ventilation Type SVM EI 24V 5A SVM EI 24V 8A Service Maintenance Record System ID Date Company Engineer Next Due Comments ...

Page 13: ...act max 48V 0 5A Yes potential free contact max 48V 0 5A Failure output Yes potential free contact max 48V 0 5A Yes potential free contact max 48V 0 5A 24V DC for external use 24V DC max 0 5A at 230V operation 24V DC max 0 5A at 230V operation Bus communication Yes connection of 2 35 pcs control panels line detection Visual LED indication in front panel OK AC fault Low battery Line fault Alarm Com...